FA147C Wiring Uplink’s 5530M Cellular Communicators Instruction Manual
- June 1, 2024
- Uplink
Table of Contents
FA147C Wiring Uplink’s 5530M Cellular Communicators
Product Information
- Specifications:
- Product: Honeywell FA147C/FA148C
- Compatible with: Uplink’s 5530M Cellular Communicators
- Alarm Panel Type: Honeywell FA147C/FA148C
Product Usage Instructions
- Wiring the 5530M Communicators to Honeywell FA147C/FA148C:
- Ensure power is off to the alarm panel.
- Identify the communication terminals on the FA147C/FA148C panel.
- Connect the appropriate wires from the 5530M communicator to the designated terminals on the panel.
- Programming the Honeywell FA147C/FA148C Alarm Panel via the Keypad:
- Access programming mode on the alarm panel keypad.
- Enable Contact ID reporting by entering the following sequence:
- Keypad Display 20
- Keypad Entry: 4112,8,00 41 123456 43 1234 45 1 46 77 65 1 66 11 70 1 99
FAQs
- Q: How do I know if the wiring is correct?
- A: You can perform a communication test after wiring to ensure proper connectivity.
- Q: Can I use other brands of communicators with the FA147C/FA148C panels?
- A: It is recommended to use Uplink’s 5530M Cellular Communicators for compatibility and optimal performance.
INTRODUCTION
CAUTION:
- It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
- Do not route any wiring over the circuit board.
- Full panel testing, and signal confirmation, must be completed by the installer.
NEW FEATURE:
- For 5530M Communicators, the status of the panel can be retrieved not only from the status PGM but now also from the Open/Close reports from the dialler.
- Therefore, wiring the white wire and programming the status PGM of the panel is optional. Wiring the white wire is necessary only if the Open/Close reporting is disabled.
IMPORTANT NOTE:
- The Open/Close reporting needs to be enabled during the initial pairing procedure.
Wiring Communicators
Wiring the 5530M communicators to Honeywell FA147C/ FA148C
Keypad Display
Programming the Honeywell FA147C/ FA148C Alarm Panel via the Keypad
Enable Contact ID reporting:
Keypad Display | Keypad Entry | Action Description |
---|---|---|
4112,8,00 | To enter the programming menu. | |
20 | *41 | To go to the primary phone setting. |
123456* | Enter phone number (123456 is an example) * to save. | |
*43 | To go to a primary account number. | |
1234 | Enter the account number (1234 is an example) * to save. | |
*45 | To go to the phone system menu. | |
1 | Press 1 to select tone dialling. | |
46 | Choose Report Format. | |
77 | To select Ademco Contact ID reporting. | |
*65 | To go to Open Report code. | |
1 | To enable Open report code. | |
*66 | To Arm Away/Stay Rpt Code. | |
11 | To enable Away/Stay ARM reporting code. | |
*70 | To go to Alarm/Restore reporting code. | |
1 | To enable alarm/Restore reporting code. | |
*99 | To exit and save. |