Uplink DSC 9045 Alarm Panel User Guide
- June 1, 2024
- Uplink
Table of Contents
Uplink DSC 9045 Alarm Panel
Specifications
- Model : DSC 9045/9047
- Compatible with Uplink’s 5530M Cellular Communicators
- Programming Method: Keypad
Product Usage Instructions
Enabling Contact ID Reporting
- Enter Programming Mode: *85555
- Access Third System Options: 015
- Disable TLM: Toggle Option 7# to OFF
- Set the First Phone Number: 301, Enter any number followed by 6 (e.g., 1234566)
- Set System Account Code: 310, Enter the account number followed by 66 (e.g., 123466)
- Configure Communicator Alarm Format: 350, Enter data 03030303 for Contact ID
- Set Phone 1 Communicator Call Direction: 351, Toggle Option 1# to ON
- Enable Open/Close Reports: 367, Toggle Option 1# to ON
- Configure First Communication Options: 380, Toggle Option 1# to ON, 3 to OFF
- Configure Second Communication Options: 381, Toggle Option 7# to OFF for automatic reporting
Programming Key-switch Zone and Output
- Enter Programming Mode: *85555
- Set Key-switch Zone: Enter Section 206, Toggle Option 1#
- Program Output: Enter Section 013, Toggle Option 1#
- Set Communication Options: Enter Section 133, Toggle Option 9, then Enter Data XX (specific instructions needed)
FAQ
- Q: How do I enter Programming Mode?
- A: To enter Programming Mode, use the code *85555 on the keypad.
- Q : How can I disable TLM?
- A : To disable TLM, access the Third System Options (015) and toggle Option 7# to OFF.
- Q: What is the default account code for System Account Code?
- A : The default account code is typically set as ‘1234’ followed by *66 in hex.
- Q: How do I configure the Communicator Alarm Format?
- A : Access menu 350 and enter ‘03030303’ to set all four phone lines for Contact ID.
CAUTION
- It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
- Do not route any wiring over the circuit board.
- Full panel testing, and signal confirmation, must be completed by the installer.
FEATURE
NEW FEATURE: For 5530M Communicators, the status of the panel can be
retrieved not only from the status PGM but now also from the Open/Close
reports from the dialler.
IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the
initial pairing procedure.
Wiring the Uplink 5530M to DSC 9045/9047
Programming the DSC 9045/9047 Alarm Panel via the Keypad
Enable Contact ID reporting
Keypad Display | Keypad Entry | Action description |
---|---|---|
Enter Section: | *85555 | To enter in Programming mode. |
Enter Section: | 015 | To enter the menu “Third System options”. |
Toggle Option: | 7# | Option 7 must be OFF (TLM disabled). |
Enter Section: | 301 | To enter the menu” First phone number”. |
DFFFFF | 1234566# | Enter an actual or non-existing number (any number will |
do, 123456 is an example) followed by 6 (F in hex).
Enter Section:| 310| To enter the menu “System account code”.
Enter data:| 123466| Enter a 4-digit account number to receive the events
from (1234 is an example) and close it with 66 in hex.
Enter Section:| 350| To enter the “Communicator Alarm Format” options.
Enter Data:| 03030303| 03 is for Contact ID (03030303 is to set all 4 phone
lines).
Enter Section:| 351| To program phone 1 communicator call direction.
Toggle Option:| 1#| Toggle 1 to ON for alarms (it has to appear on screen).
Enter Section:| 367| Open/Close Communicator Call directions.
Toggle Option:| 1#| Toggle 1 to ON to enable Open/Close reports (it has to
appear on screen).
Enter Section:| 380| Enter First Communication Options.
Toggle Option:| 1#| Toggle 1 to ON, 3 to off to enable communications.
Enter Section:| 381| Enter Second Communication Options.
Toggle Option:
|
7#
| Toggle 7 to OFF to enable automatic reporting.
To manually program the reporting codes in menu 381, enable option 7 to ON and then set the desired reporting codes in menus 320 to 348.
| #| Exit Programming mode.
Program Key-switch zone and output
Keypad Display | Keypad Entry | Action Description |
---|---|---|
Enter Section: | *85555 | To enter in Programming mode. |
Enter Section | 206 | Enter Zone Assignment |
Toggle Option | 1# | Toggle option 1 to ON to enable the Keyswitch zone. |
Enter Section | 013 | Enter First System Options (to select I/O as Input or |
PGM).
Toggle Option| 1#| When the panel is defaulted press the toggle buttons until
1 is ON and 2 is OFF.
Enter Section| 133| Enter I/O 1 Programming.
Toggle Option| 9| Press 9 to move to options 9‐16.
Toggle Option| 7#| Make sure that option 15 is selected (shows as 7).
This standard mode of operation REQUIRES a resistor across the STC.
Enter Section:| 009| Enter I/O Programming.
Enter Data: XX| 22| Enter 22 to program zone Type Keyswitch for I/O 1.
Enter Data: XX| 05| Enter 05 to program Armed Status on I/O 2.
| #| Exit Programming mode.