Uplink NX-4 Interlogix Alarm System User Guide

June 1, 2024
Uplink

Interlogix NX-4
Wiring Uplink’s Cellular Communicators
and Programming the Panel

NX-4 Interlogix Alarm System

CAUTION:

  • It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
  • Do not route any wiring over circuit board.
  • Full panel testing, and signal confirmation, must be completed by the installer.

NEW FEATURE: For Uplink 5530M Communicators, the status of the panel can be retrieved not only from the status PGM but now also from the Open/Close reports from the dialler. Therefore, wiring the white wire and programming of the status PGM of the panel is optional.
IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the initial pairing procedure.
Wiring the 5530M communicators to Interlogix NX-4 Uplink NX 4 Interlogix
Alarm System - WiringWiring the 5530M with UDM to Interlogix NX-4 for remote upload/download Uplink NX 4 Interlogix Alarm
System - Wiring 1Programming the Interlogix NX-4 Alarm Panel via the Keypad
Enable Contact ID reporting:

LED Keypad Entry Action description
LEDSs of Ready, Power Steady ON *8 9713 To enter programming mode
Service LED blinks 0# To qo to main panel programming menu
Service LED blinks, Armed LED steady ON 0# To enter phone number menu
Service LED blinks, Ready LED steady ON 15123456*# 15* (to choose

phone dialing), followed by your desired phone number (123456 is just an example) each figure is followed by , # to save and qo back
Service LED blinks, Armed LED steady ON| 1#| To go to account number menu
Service LED blinks, Ready LED steady ON| 1
234#| Enter the desired account number (1234 is an example), # to save and go back
Service LED blinks, Armed LED steady ON| 2#| To go to communication format
---|---|---
Service LED blinks, Ready LED steady ON| 13
| To choose Contact ID, to save
All Zone LEDs are ON| 4#| To go to events reported to phone 1
All Zone LEDs are ON|
| To confirm all events reporting and go to next section
All Zone LEDs are ON| *| To confirm all events reporting and go back
Service LED blinks, Armed LED steady ON| 23#| To go to feature report section
Service LED blinks, Ready LED steady ON| *| To go to section 3 of the toggle options menu
Ready Led steady ON| 1
| To enable Open/Close reporting
Service LED blinks, Armed LED steady ON| Exit, Exit| Press “Exit” two times to exit programming mode

Programming the GE Interlogix NX-4 Alarm Panel via the Keypad for remote Upload/Download
Program the Panel for Upload/Download:

Display Keypad Entry Action Description
System ready *89713 Enter programming mode.
Enter device address 00# To go to main edit menu.
Enter location 19# Start configuring “Download access code”. By default, it

is “84800000”.
Loc#19 Seg#| 8, 4, 8, 0, 0, 0, 0, 0, #| Set download access code to its default value. Press # to save and go back. IMORTANT – This code should match the one set in the “DL900” software.
Enter location| 20#| To qo to “Number of rings to answer” menu.
Loc#20 SW| 1#| Set number of rings to answer to 1. Press # to save and qo back.
Enter location| 21#| Go to “Download control” toggle menu.
Loc#21 Seg#| 1, 2, 3, 8, #| All of these (1,2,3,8) should be OFF in order to disable “AMD” and “Call back”.
Enter location| Exit, Exit| Press “Exit” twice to exit programming mode.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>