Uplink NX-4 Interlogix Alarm System User Guide
- June 1, 2024
- Uplink
Table of Contents
Interlogix NX-4
Wiring Uplink’s Cellular Communicators
and Programming the Panel
NX-4 Interlogix Alarm System
CAUTION:
- It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
- Do not route any wiring over circuit board.
- Full panel testing, and signal confirmation, must be completed by the installer.
NEW FEATURE: For Uplink 5530M Communicators, the status of the panel can be
retrieved not only from the status PGM but now also from the Open/Close
reports from the dialler. Therefore, wiring the white wire and programming of
the status PGM of the panel is optional.
IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the
initial pairing procedure.
Wiring the 5530M communicators to Interlogix NX-4 Wiring the 5530M with UDM to
Interlogix NX-4 for remote upload/download Programming the Interlogix NX-4 Alarm
Panel via the Keypad
Enable Contact ID reporting:
LED | Keypad Entry | Action description |
---|---|---|
LEDSs of Ready, Power Steady ON | *8 9713 | To enter programming mode |
Service LED blinks | 0# | To qo to main panel programming menu |
Service LED blinks, Armed LED steady ON | 0# | To enter phone number menu |
Service LED blinks, Ready LED steady ON | 15123456*# | 15* (to choose |
phone dialing), followed by your desired phone number (123456 is just an
example) each figure is followed by , # to save and qo back
Service LED blinks, Armed LED steady ON| 1#| To go to account number menu
Service LED blinks, Ready LED steady ON| 1234#| Enter the desired account
number (1234 is an example), # to save and go back
Service LED blinks, Armed LED steady ON| 2#| To go to communication format
---|---|---
Service LED blinks, Ready LED steady ON| 13| To choose Contact ID, to save
All Zone LEDs are ON| 4#| To go to events reported to phone 1
All Zone LEDs are ON| | To confirm all events reporting and go to next
section
All Zone LEDs are ON| *| To confirm all events reporting and go back
Service LED blinks, Armed LED steady ON| 23#| To go to feature report section
Service LED blinks, Ready LED steady ON| *| To go to section 3 of the toggle
options menu
Ready Led steady ON| 1| To enable Open/Close reporting
Service LED blinks, Armed LED steady ON| Exit, Exit| Press “Exit” two times to
exit programming mode
Programming the GE Interlogix NX-4 Alarm Panel via the Keypad for remote
Upload/Download
Program the Panel for Upload/Download:
Display | Keypad Entry | Action Description |
---|---|---|
System ready | *89713 | Enter programming mode. |
Enter device address | 00# | To go to main edit menu. |
Enter location | 19# | Start configuring “Download access code”. By default, it |
is “84800000”.
Loc#19 Seg#| 8, 4, 8, 0, 0, 0, 0, 0, #| Set download access code to its
default value. Press # to save and go back. IMORTANT – This code should match
the one set in the “DL900” software.
Enter location| 20#| To qo to “Number of rings to answer” menu.
Loc#20 SW| 1#| Set number of rings to answer to 1. Press # to save and qo
back.
Enter location| 21#| Go to “Download control” toggle menu.
Loc#21 Seg#| 1, 2, 3, 8, #| All of these (1,2,3,8) should be OFF in order to
disable “AMD” and “Call back”.
Enter location| Exit, Exit| Press “Exit” twice to exit programming mode.