Application
Ceiling and wall luminaire · indoor luminaire made of impact-resistant synthetic diffuser and metal housing, for all lighting tasks. They are ideal for places where a soft and uniform lighting distribution is required. Luminaire with motion sensor.

Product Description

  • Metal housing, finish colour white
  • Impact-resistant synthetic diffuser, white, with bayonet closure
  • Integrated HF-motion sensor, maximum range 8 m
  • 2 mounting holes ø 3mm
  • Distance apart 340mm
  • 2 cable entries for through-wiring for mains
  • cable up to ø 10.5 mm max. 3 × 1.5
  • Connection terminal 2.5
  • Earth conductor connection
  • Complies with flicker requirements by IEEE 1789, DIN IEC/TR 63158, DIN IEC/TR 61547-1
  • LED power supply unit
  • 230 V y 50 Hz
  • BEGA Thermal Switch
  • Temporary thermal shutdown to protect
  • temperature-sensitive components
  • Safety class I
  • Impact strength IK10
  • Protection against mechanical
  • impacts < 20 joule
  • Conformity mark
  • Weight: 3.1 kg
  • This product contains light sources of energy efficiency class(es) D, E

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage by DIN EN 61547.
  • To achieve additional protection against e.g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 27.6 W
  • Luminaire connected wattage 33 W
  • Rated temperature ta=25 °C
  • Ambient temperature ta max=30 °C

50 043 PK27

  • Colour temperature 2700 K
  • Colour rendering index CRI >90
  • Module luminous flux 4165 lm
  • Luminaire luminous flux 3473 lm
  • Luminaire luminous efficiency 105,2 lm/W

50 043 PK3

  • Colour temperature 3000 K
  • Colour rendering index CRI >90
  • Module luminous flux 4305 lm
  • Luminaire luminous flux 3590 lm
  • Luminaire luminous efficiency 108,8 lm/W

50 043 PK4

  • Colour temperature 4000 K
  • Colour rendering index CRI >90
  • Module luminous flux 4480 lm
  • Luminaire luminous flux 3735 lm
  • Luminaire luminous efficiency 113,2 lm/W

Luminaire with trim ring

  • Before installing it onto the mounting surface the luminaire housing must be inserted into the trim ring (accessory).
  • InstallatiLEDsLED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Pass the main supply cable through the grommet into the luminaire housing. Fix luminaire housing with enclosed or any other suitable fixing material to the mounting surface.
  • It is imperative to use the enclosed gaskets. Dismantle the mains supply cable approx. 60 mm. Make earth and connections to the terminals.
  • Place the synthetic diffuser to the luminaire housing and observe that the cam pins fit into the notches of the synthetic diffuser.
  • Screw the synthetic diffuser by turning it clockwise. Thus, you reach a safe vibration-resistant holding of the synthetic diffuser.
  • To release the synthetic diffuser from the luminaire housing, turn counterclockwise.

The built-in motion sensor operates at a frequency of 5.8 GHz. By moving within the detection range the motion sensor switches on the LED module inside the luminaire with a defined dwell time – push-button “Dwell time”. With a wall mounting height of 1.8 m or a ceiling mounting height of 2.6 m, the maximum range is 8 meters (see sketch).

The max. wall mounting height is 2.7 m and the max. ceiling mounting height is 4.0 m, in which the range reduces significantly. The range can be set individually – push-button “Sensitivity”. It should be noted that metal parts that are mounted near the luminaire can affect the range.

With the three integrated push-buttons
(Brightness, Dwell time and Sensitivity) on the motion sensor, specific settings can be made. The first keypress activates the setting function. Press a push-button to switch each function to the next level, and the LED indicator on the motion sensor flashes to confirm. After reaching the highest level, level-setting begins with “Level 1”.

The integrated motion sensor can be set individually with the brightness levels on the ambient brightness – Press the button “Brightness”. Further individual illumination levels can be used with the button “Brightness” and set with the “learning mode”. Pre the ss button “brightness” (> 3 s) to enable the “learning mode”. There is a slow flashing of the LED indicator. After about two minutes, the current brightness value is measured for one minute, the LED flashes faster. After completion, the measured brightness value is saved and is available in stage 6 of “Brightness as the new brightness value.

To simplify the initial operation, the settings have been made as follows:

  • Range = 75% (6 m)
  • Dwell time = 10 s
  • Light sensor = daylight

Factory Reset
The motion sensor can be reset to the factory settings (MICAS) by simultaneously pressing the buttons “Sensitivity” and “Dwell time” for about 5 s.
The factory settings are as follows:

  • Range = 75% (6 m)
  • Dwell time = 900 s
  • Light sensor = daylight

Test mode
The test mode can be used to check the change of settings of the motion sensor. Pre the ss button “Sensitivity” (> 3 s) to enable the “test mode”. Each further keystroke of this push-button prolongs the test mode. The active test mode is displayed by a flashing of the LED indicator (2 s interval). After 3 minutes the test mode is automatically disabled.

Replacement of the LED unit

  • The designation of the LED unit is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement units correspond to those of the
  • LED unaware ts originally fitted. The LED unit can be replaced by qualified persons using standard tools.
  • Disconnect frthe om main supply.
  • Unscrthe new synthetic diffuser for the luminaire housing by turning it counter-clockwise.Disassembled le LED unit.
  • Assembthe le LED replacement unit.
  • Note the installation instructions for further LED units.
  • Screw a synthetic diffuser by turning it clockwise.
  • A damaged synthetic diffuser must be replaced.

Accessory · Trim rings

  • For this luminaire metal trim rings in 3 enamel surfaces aoptionallynal available.
  • Trim rings are accessories and must be ordered separately.
  • Item Part. No
  • Colour white 13 007
  • Colour palladium 13 008
  • Colour glossy silver 13 009

Spares

  • Synthetic cover 15 000 457
  • HF-motion sensor 61 001 077
  • LED unit 2700 K 75 003 532 K27
  • LED unit 3000 K 75 003 532 K3
  • LED unit 4000 K 75 003 532 K4