BURK TECHNOLOGY Plus-X 300 Facilities Monitoring & Control Solutions Instruction Manual
- June 13, 2024
- BURK TECHNOLOGY
Table of Contents
Plus-X 300
Installation and Operation Manual
Introduction
The Plus-X 300 works in conjunction with the Burk Technology ARC Plus
transmitter remote control to provide eight inputs and eight outputs for
remote monitoring and control. Metering and status inputs are sent from the
Plus-X 300 to the ARC Plus via Ethernet. The ARC Plus then reports these
values as independent metering and status channels. The relay outputs on the
Plus-X 300 are controlled by the ARC Plus via commands and macros.
The Plus-X 300 has eight (8) inputs, each configurable as metering or status.
Eight (8) output relays allow control of site equipment. Relays may be
activated independently or operated in pairs for mutually-exclusive output.
Compatibility
Before installing the Plus‐X 300, please verify that the ARC Plus firmware,
AutoPilot software and AutoLoad Plus software versions are current. Updates
are available at www.burk.com/downloads.
The following are minimum software and firmware requirements:
Software | Version |
---|---|
ARC Plus firmware | 2.0 or higher |
AutoLoad Plus software | 2.0 or higher |
AutoPilot® software | 2.6 or higher |
Installation
The Plus-X 300 ships with the following parts, which are required for
installation:
(1) Ethernet cable
(1) 15V wall adapter
(1) 2-pin Phoenix-type connector (for power connection)
(1) 9-pin Phoenix-type connector (for input channels)
(2) 12-pin Phoenix-type connectors (for relay outputs)
(4) Rubber feet (for optional horizontal mounting)
Before you start, you will need to use a standard Cat5 cable (included)
to connect the Plus-X 300 to your network. It is recommended that you only set
up one Plus-X 300 device at a time on the network so a unique NETBIOS hostname
can be assigned to each unit.
Mounting the Plus-X 300
The Plus-X 300 may be placed on any shelf or flat surface. For this type of
installation, the rubber feet included in the parts kit should be applied to
the four corners of the bottom of the chassis.
Plus-X 300 Installation and Operation Manual Rev E
The Plus-X 300 can be wall-mounted as follows:
- Remove the cover from Plus-X 300 by first removing four screws on the top of the unit and two screws on the rear panel.
- Secure the Plus-X 300 to the wall with four #10 wood screws (not included).
- Re-install the Plus-X 300 cover.
The Plus-X 300 may also be rack-mounted using the optional RMA 300 Rack Mount Kit. To install the RMA 300 kit:
- Remove the cover from Plus-X 300 by first removing four screws on the top of the unit and two screws on the rear panel.
- The RMA 300 kit includes two rack mount flanges. Install one flange on each side of the Plus-X 300 by inserting the threaded posts on the flange through the mounting holes in the bottom of the unit. Secure with hex nuts included in the RMA 300 kit.
- Re-install the Plus-X 300 cover.
Please contact Burk Sales for RMA 300 ordering information.
Power & Ethernet Connections
Apply power to the Plus-X 300 by connecting the 2-pin power connector to the
rear-panel input marked POWER. The power connector is pre-wired to the 15V
wall adapter. Plug the power adapter into a standard 120V outlet. The POWER
LED will illuminate.
Finally, connect the included Ethernet cable to your network switch.
Important!
The Plus-X 300 must be addressable by the ARC Plus to which it will
communicate. Consult your IT
department prior to configuration to resolve any IP address or firewall
conflicts.
Configuration
Configuring the Plus-X 300 involves establishing the network settings, setting
up channel parameters, setting the password, and then adding the newly
configured Plus-X channels to the ARC Plus system. The username is admin and
the default password is password.
Initial Connection Using DHCP
Plus-X 300 units running firmware 1.0.15 or higher support Dynamic Host
Configuration Protocol (DHCP) as an easy way to do initial setup. Connect the
Plus-X 300 to your LAN and apply power. If this is the first power-up for a
new unit or the first network connection after execution of a master-
initialization, the Plus-X 300 will issue a DHCP request for an IP address. If
the network supports DHCP functionality, a dynamic IP address will be assigned
to the unit. To access the Plus-X 300, launch a web browser and enter the
hostname “PLUSX300/” in the browser’s address field. (Be sure to include the
forward-slash symbol at the end of the hostname.) The login screen for the
unit will be displayed. Go to Log In to the Plus-X 300, below
Note: If the login page is not displayed or the browser indicates that
the page cannot be found, it is possible the connected network does not
support DHCP. In this case follow the steps outlined below for “Initial
Connection Without DHCP”. Otherwise, continue to Log In to the Plus-X 300.
Initial Connection Without DHCP
If your network does not support the DHCP protocol, the Plus-X 300’s request
for a dynamic IP address will fail. If this happens, the Plus-X 300 will
assign itself the default static IP address 192.168.0.100. To access the unit,
it will be necessary to connect your PC directly to the Plus-X 300 using a
crossover LAN cable or using a simple Ethernet switch.
In addition, your PC’s internal network interface must be set to a static IP
address of the form 192.168.0.x. In the Windows Control Panel, search for
Network Connections, then select View network connections then Local Area
Connection. Navigate to the Internet Protocol Version 4 (TCP/IPv4) Properties
dialog box as displayed below.
Select “Use the following IP address:” and enter an address of the form
192.168.0.x, where x is any value between 1 and 255 except 100 which is the
Plus-X 300 default IP address. Also set the subnet mask to 255.255.255.0 as
shown above and click OK.
Next launch a browser and enter 192.168.0.100 in the address field. The login
screen for the Plus-X 300 will be displayed.
Log In to the Plus-X 300
The login screen for the Plus-X 300 is shown below.
Enter the default Username admin, and the default Password password.
You will be prompted that the password is weak and will be recommended to
change it. You can also change the password at any time from the Security link
on the Plus-X 300 web page.
Once the password has been set and confirmed, click update.
Set a Static IP Address
Next, select the Network menu option. The page shown below will be displayed,
showing the current IP address.
Enter a static IP address for this unit as assigned by your network
administrator in the IP Address box and click Save.
Note: It is important that the assigned static IP address be outside the
DHCP address range used by the router to avoid potential conflicts with other
DHCP devices.
Configure Network Settings
Select the Network menu option again. A more extensive selection of network settings will now be displayed as shown below. Explanations for each item are shown at the right of the screen.
It is recommended that you enter a recognizable name for the unit in the Name
field. This name will be displayed on the web page making it easy to confirm
which unit you are connected to.
The NETBIOS Hostname can be used to access the Plus-X 300 on the network if
the IP address is not known. It is highly recommended that you assign a unique
hostname to each Plus-X 300 on your network. By default the Hostname is set to
PLUSX300.
Enter the IP address of the ARC Plus that will host the metering, status and
command channels of the Plus-X 300 in the ARC Plus IP Address field.
The default Plus-X Port setting of 45000 will work in most installations.
However, if you have changed the Plus-X port during ARC Plus configuration,
the Plus-X port you enter here should match that setting.
Press the Save button when you are finished.
If your initial connection was made without DHCP, your PC should now be
restored to its prior network settings, and both the PC and the Plus-X 300
should be connected to the normal LAN.
Configure Channel Settings
The Channels page is where you configure high and low status thresholds for up
to eight status channels, as well as relay behavior for each of eight relay
outputs.
Input Configuration and Wiring
In the Status Thresholds table, enter the input values that will trigger
status changes from low to high and viversa. The Lower threshold is the value
below which avoltage sample must decrease in order to change the status from
high to low. The Upper threshold is the value above which a voltage sample
must increase in order to change the status from low to high.
Voltages between the lower and upper thresholds do not cause a status change
on the ARC Plus. For example, if a voltage sample increases beyond the Lower
threshold, but does not reach the Upper threshold, the status indicated on the
ARC Plus does not change.
Note that each input may be used as a metering channel, status channel or
both. In other words, an analog temperature reading may also drive “high temp”
and “low temp” status alarms.
Metering and status channels are wired to the Plus-X 300 using the included
9-pin connector block. To connect metering and status inputs, loosen the
screws on the connector block and connect voltage wiring from the site
equipment to the Phoenix connector inputs to align with the 1-8 numbering on
the chassis. Insert a common ground reference to the Phoenix connector to
align with the ground symbol on the chassis. Tighten the set screws.
Relay Output Configuration & Wiring
Next, define the behavior for each of eight relay outputs.
Each relay may be set for momentary or latching output.
Check the Pair Relay Channels box in order for the relays to act as mutually
exclusive pairs. When this box is checked, a command to one relay will cause
the second relay to de-energize.
Note: When the Pair Relay Channels box is checked, it is recommended to
configure the two paired relays with the same behavior (Latching / Latching or
Momentary / Momentary). If one relay is configured as Latching and the other
as Momentary, a command to the momentary relay will de-energize the latching
relay. After the momentary command is finished, both relays will remain de-
energized until a new command is issued to one of the relays.
Command output wiring is facilitated by the two 12-pin connector blocks. Each
relay 1-8 has Common (C), Normally Open (NO) and Normally Closed (NC)
connections labeled on the rear panel. Loosen the set screws on the Phoenix
connectors and make wiring connections according to the requirements of the
site equipment under control. Tighten the set screws.
Latching Relay State During Plus-X 300 Reboot
The Plus-X 300 reboots as part of the firmware upload process. The unit will
also reboot to reestablish communications if the network link between the
Plus-X 300 and the ARC Plus unit is interrupted for greater than three
minutes. Plus-X 300 relays configured as Latching will briefly de-energize
during reboot, returning to their preset value when the reboot completes. An
external mechanically latching relay should be used for critical functions to
hold the preset value while the Plus-X 300 is rebooting.
When finished making equipment connections, disconnect the Phoenix connectors
from the Plus-X 300 until configuration is complete..
Security
Navigate to the Security page to set the password for the Plus-X 300. This
password is used only to access the Plus-X configuration screens. ARC Plus
usernames and passwords are set up using AutoLoad Plus software.
The Plus-X 300 username is always admin.
Adding Plus-X Channels to the ARC Plus
Now that you have configured the input and output channels on the Plus-X 300,
these channels may be added to the ARC Plus site using AutoLoad Plus. To add
Plus-X 300 channels to the ARC Plus:
- Launch AutoLoad Plus and connect to the ARC Plus site to which the Plus-X 300 is linked.
- From the Edit menu, select Plus-X Devices…and click New.
- When the Plus-X Settings window appears, select Plus-X 300 from the device type dropdown. Enter a description of the Plus-X 300 for your own reference, followed by the IP address and Plus-X port, both of which are already configured on the Plus-X 300.
- Check the box marked Map Default Set of Channels to add all eight inputs and eight relays to the ARC Plus. If you are not using all Plus-X 300 channels or if you do not wish for them to appear in sequential order, you will need to manually map these channels later. In this case, leave the Map Default Set of Channels box unchecked.
- Press OK to close the Plus-X Settings window. Press OK to close the Plus-X Devices window.
- To manually map Plus-X 300 channels to the ARC Plus, click the Metering, Status or Commands tabs, as appropriate. Locate an unused channel and click the […] button in the Source column. This will bring up the Source dialog box. Click the Plus-X button and choose the Plus-X 300 channel you wish to use. At least one meter channel and one command channel on the Plus-X 300 must be configured within the ARC Plus for the Plus-X device to register as online in the ARC Plus system.
- Configure labels, limits and alarms for the newly added Plus-X 300 channels in the same way as you would configure labels, limits and alarms for other ARC Plus channels.
- Lastly, you will need to calibrate the Plus-X 300 channels. If you have not already connected the input connector blocks, do so now. Then click the Calibration icon in the AutoLoad Plus toolbar to complete the calibration process.
Restoring Factory Configuration
To reset the unit to its default configuration, press the front panel Config
button three times.
The Power LED will blink to confirm the configuration has been reset.
Note that the restoring default configuration will reset the unit’s
password to password and revert the IP address to 192.168.0.100.
Uploading New Firmware
For instructions on updating the firmware on the Plus-X 600, visit
www.burk.com/downloads, select the support
page for the Plus-X 300 and download Manual – Burk Firmware Loader.
Operation
Taking Readings & Issuing Commands
Once you have added Plus-X 300 channels to the ARC Plus, they appear on the
ARC Plus front panel, AutoPilot® software, Web Interface and RSI speech
interface just as any other ARC Plus channel. They can be used in macros and
custom views. The Plus-X 300 is responsible for reporting the raw sample
values to the ARC Plus, while the ARC Plus applies the calibration constant,
limits and alarm settings.
Maintenance Mode
Maintenance Mode is a safety feature that prevents command execution while
personnel are performing work at the remote site. Maintenance Mode on the
Plus-X 300 can be activated by two means: 1) placing the ARC Plus in
maintenance mode using the ARC Plus front panel menus; and 2) placing the
Plus-X 300 in maintenance mode using the Plus-X front panel MAINT button.
When the ARC Plus is in maintenance mode, it will not issue commands or macros
to any ARC Plus channels, including Plus-X 300 channels. It is still possible
to issue test commands via the Plus-X 300 diagnostics page (see Diagnostics ).
When the Plus-X 300 is in maintenance mode, the ARC Plus can issue commands
and macros to other channels, but Plus-X 300 commands are disabled.
Maintenance mode must be toggled from the respective front panels. For safety
reasons, maintenance mode cannot be enabled or disabled by any remote means.
The front LED will illuminate red to indicate that maintenance mode is
enabled.
Diagnostics
The Plus-X 300 has a diagnostics page built into the configuration web pages.
This allows administrators to verify raw input voltage readings against real-
world measurements and to test relay behavior; it is not intended for routine
monitoring and control of equipment.
To access the diagnostics page, open a web browser and enter the IP address of
the Plus-X 300. After logging in, use the links at the top of the screen to
navigate to the Diagnostics page.
Getting Help
For technical support, please email support@burk.com or call our direct technical support line at 978-486-3711. We will be glad to assist you. The technical support office is open Monday – Friday, 9AM to 5PM Eastern time.
Warranty
Burk Technology, Inc. warrants the Plus-X 300 to be free of defects in
materials and workmanship for a period of 24 months from the date of purchase.
Equipment will be repaired or replaced at the option of Burk Technology and
returned freight prepaid to the customer. Damage due to abuse or improper
operation or installation of the equipment or caused by fire or flood or harsh
environment is not to be covered by this warranty. Damage in shipping is not
the responsibility of Burk Technology. A return authorization must be obtained
before returning any equipment. Materials returned under this warranty must be
shipped freight prepaid and insured in the original shipping carton or
suitable substitute to Burk Technology, Inc., 7 Beaver Brook Road, Littleton,
MA 01460. Repairs not covered under this warranty will be made at prevailing
shop rates established by Burk Technology.
THE WARRANTY SET FORTH ABOVE IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. BURK TECHNOLOGY, INC. SHALL NOT BE LIABLE TO
ANY PARTY FOR ANY INCIDENTAL, SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES
ARISING FROM THE USE OF THIS EQUIPMENT.
Specifications
Dimensions:
1.35” (3.43cm) H
9.2” (23.4cm) W
3.85” (9.78cm) D
Operating Temperature:
o° to 50° C
0 to 95% RH, non-condensing
Power Requirements:
15VDC at 0.5A (power adapter included)
Metering Inputs:
0 to 10VDC, 10mV resolution
Status Inputs:
0 to 28VDC or switch closure
Relay Outputs:
5A, 240VAC, form C relay outputs, (C, NO, NC), each user-configurable for momentary or latching output
Hysteresis:
User-configurable set points per input channel
Mounting:
Desktop or shelf mounting using supplied rubber feet
Wall mounting using #10 wood screws, not included
Optional RMA 300 Rack Mount Kit is available. Please contact Burk Sales.
Copyright © 2023 Burk Technology, Inc.
Rev. F
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>