BEGA 512651K3 LED Pendant Luminaire Light Instruction Manual

May 15, 2024
BEGA

BEGA 512651K3 LED Pendant Luminaire Light

BEGA-512651K--LED-Pendant-Luminaire-Light-PRODUCT

Specifications

  • Lamp Module connected wattage: 42.4 W
  • Luminaire connected wattage: 49 W
  • Rated temperature: 25 – 65°C
  • Ambient temperature: max. 60 – 80°C
  • Colour temperature: 3000 K
  • Colour rendering index (CRI): > 90
  • Module luminous flux: 6600 lm
  • Luminaire luminous flux: 2840 lm
  • Luminaire luminous efficiency: 58 lm / W

Safety
The installation and operation of this luminaire must comply with national safety regulations. Only a qualified electrician should carry out installation and commissioning. Any modificationsshould be done by an authorized person.

Overvoltage Protection
The luminaire’s electronic components have overvoltage protection according to DIN EN 61547. For extra protection against transients, separate overvoltage protection components are recommended and can be found on the manufacturer’s website.

Trimming the Cable Pendant

  1. Lift the pendant luminaire by the cables and clip the strain relievers into the recesses on the hangers.
  2. Establish the earth conductor connection between the luminaire hanger and the mounting plate.
  3. Connect the red wire to + and the black wire to – on the marked terminals.

Replacing the LED Module

  1. Disconnect the system and open the luminaire.
  2. Follow the installation instructions for replacing the LED module.
  3. Defective luminaire covers must be replaced before closing the luminaire.

FAQ (Frequently Asked Questions)

Q: Can I replace the LED module myself?
A: Yes, the LED module can be replaced by qualified persons using standard tools. Follow the provided installation instructions.

Pendant luminaire for indoor use

BEGA-512651K--LED-Pendant-Luminaire-Light- \(2\)

Instructions for use

Application
Pendant luminaire · Indoor luminaire with metal housing and diffuser for glare-free, shielded light directed upward and downward.
A luminaire with uniform light distribution for linear indoor illumination.

Product description

  • Luminaire housing and canopy made of metal, finish Colour velvet white
  • Silicone light diffuser
  • 3 elongated fixing holes
  • Width 4.5 mm · 540 mm spacing
  • Mounting plate with several openings for cable entry and through-wiring for mains cable Synthetic 2-piece line connector (clamp part with screw cap) for braided coaxial cables With internal pressure spring and contact wire Cable pendant · Sheath cable white 2 x
  • 0,75@ Overall length of luminaire approx. 2000 mm Connecting terminals 2.5@
  • Earth conductor connection
  • LED power supply unit inside canopy
  • 220-240 V x 0/50-60 Hz
  • DC 176-264 V
  • DALI-controllable
  • Number of DALI addresses: 2
  • A basic isolation exists between power cable and control line
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire

Safety class I

  • – Conformity mark
  • This product contains light sources of energy efficiency class(es) D
  • Weight: 4.2 kg

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to
the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 42.4 W
  • Luminaire connected wattage 49 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 65 °C

51 265.1 K3

  • Module designation LED-1320/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 6600 lm
  • Luminaire luminous flux 2840 lm
  • Luminaire luminous efficiency 58 lm / W

Prior to installation, please note

  • To ensure correct mounting and installation of the luminaire, the mounting plate must be installed on an even ceiling surface. When mounting the luminaires, it must be ensured that the ceiling surface has sufficient load-bearing capacity.
  • The fixing material provided must be checked for compatibility with the specific mounting surface. If necessary, replace with suitable fixing material.
  • Please check the secure mounting of the luminaires after installation.
  • IMPORTANT: The pendant luminaire must only be mounted in a horizontal burning position.

Installation

  • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Remove the canopy and luminaire from the packaging and position them on a soft surface. Detach the canopy downwards from the mounting plate against the magnetic resistance.
  • Disconnect the earth conductor connection between the canopy and the mounting plate (plug contact).
  • Unclip the snap hooks on both sides of the mounting plate.
  • Disconnect the wires (red / black) of the luminaire cables from the power supply unit terminals near the magnets on both sides. Unclip the strain relievers from the hanger eyelets on both sides.
  • Lead the power connecting cable through the mounting plate.
  • Attach the mounting plate to the ceiling using the fastening material supplied or other suitable fixing material.
  • Make sure to use the gaskets supplied. Shorten mains supply cable as required and dismantle max. 80 mm.
  • Make the electrical connection to the terminals. Please ensure correct wire assignment for the connecting cable.
  • Connect the earth conductor to the green-yellow wire (1). Connect the live conductor to the brown wire (L) and the neutral conductor to the blue wire (N).
  • Use the terminals marked DA, DA for digital control.
  • If these terminals are not used, the luminaire will operate at full light output.
  • Lift the pendant luminaire by the luminaire cables and clip both strain relievers into the eyelets on the luminaire hanger.

BEGA-512651K--LED-Pendant-Luminaire-Light- \(5\) Trimming the cable pendant

  • IMPORTANT: Ensure the pendant luminaire is held firmly in place when setting the desired suspension height!
  • To fine tune the suspension height, loosen the knurled nut, adjust the cable length and tighten the knurled nut again.
  • Once the correct suspension height is adjusted, unhook the luminaire hanger from the mounting plate and carefully place the pendant luminaire onto a safe surface.
  • Remove the strain reliever from the luminaire hanger.
  • Shorten the excess luminaire cable so that a projection of 120-130 mm remains above the strain reliever.
  • Strip 60 mm to max. 80 mm of the insulation from the luminaire cable at the top end.

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · [email protected] · www.bega.com

  • BEGA-512651K--LED-Pendant-Luminaire-Light- \(1\)Installing the coaxial cable connector Unscrew the line connector.
  • Guide the stripped cable end (A) into the lower part of the connector (clamp part) (B) until it stops.
  • Hold the luminaire cable below the lower part of the connector.
  • Carefully push together the coaxial mesh of the stripped section with two fingers of your other hand bit by bit directly above the connector thread, until the black wire is laid bare.
  • Make sure that the coaxial mesh is inserted into the recess on the lower part of the connector – see diagram (C).
  • Guide the black wire through the opening in the middle of the screw cap.
  • Make sure that the red wire is correctly positioned in the cap with the internal pressure spring. Screw the closing cap (top part of the connector) in clock-wise direction onto the clamp part (lower part of the connector) until it stops (D).
  • Strip back 7–8 mm of the black wire (E).
  • Lift the pendant luminaire by the luminaire cables and clip the strain relievers into the recesses on the luminaire hangers.
  • Establish the earth conductor connection between the luminaire hanger and the mounting plate (plug connector).
  • Make connection red wire to “+” and connection black wire to “-” to the marked terminals.
  • Guide the canopy evenly upward along the luminaire cables and hook the safety steel wire into the mounting plate on both sides using the snap hooks.
  • NOTE: Using two knurled nuts over the strain relievers of the luminaire cables, an additional fine adjustment can be carried out on the horizontal orientation of the pendant luminaire. By turning the knurled nuts to the left/right, a maximum height adjustment of 5 mm
  • (± 2.5 mm) is possible in either direction. Establish the earth conductor connection between the canopy and the mounting plate (plug contact).
  • IMPORTANT: Make sure that none of the luminaire wires are pinched in when installing the canopy.
  • Guide the canopy all the way to the ceiling until the magnets on the mounting plate secure it in its final position.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those  of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
  • Defective luminaire cover must be replaced. Close the luminaire.

Spares

  • LED power supply unit DEV-0388/700i
  • LED module 3000 K LED-1320/930
  • Strain relief 75 004 118
  • Cable connector 75 004 119

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · [email protected] · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEGA User Manuals

Related Manuals