BEGA 24537K3 Wall Luminaire
Dimension
Instructions for use
Application
Wall luminaire with two-sided light output. For illumination and design tasks in architecture. The light directed downwards is intended to illuminate the wall and the horizontal surface in front of it. The light directed upwards is intended to illuminate the wall and ceiling surfaces.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Colour graphite, silver or white Matt safety glass
Reflector surface made of pure aluminium
Mounting plate with 2 fixing
holes ø 5.4 mm · 70 x 125 mm spacing
2 screw cable glands with strain relief for through-wiring power connecting
cable ø 7–12 mm
1 screw cable gland closed at the factory with
a dummy plug
Connecting terminal 2.5@ with plug connection
Earth conductor connection
BEGA Ultimate Driver®
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect
temperature-sensitive components without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK03
Protection against mechanical
impacts < 0.35 joule
– Safety mark
– Conformity mark
Weight: 3.8 kg
This product contains light sources of energy
efficiency class(es) D
Lighting technology
Wall luminaire with narrow beam light distribution.
Half beam angle of the light distribution in both half spaces 14°.
Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Lamp
Module connected wattage| 35.4 W
Luminaire connected wattage| 39 W
Rated temperature| ta=25 °C
Ambient temperature| ta max=35 °C
24 537K3
Module designation| 2x LED-0800/830
Color temperature| 3000 K
Color rendering index| CRI >80
Module luminous flux| 5960 lm
Luminaire luminous flux| 1897 lm
Luminaire luminous efficiency| 48,6 lm/W
24 537K4
Module designation| 2x LED-0800/840
Color temperature| 4000 K
Color rendering index| CRI >80
Module luminous flux| 6120 lm
Luminaire luminous flux| 1948 lm
Luminaire luminous efficiency| 49,9 lm/W
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend
separate overvoltage protection components. You can find them on our website
at www.bega.com.
Installation
Undo hexagon socket head screws (wrench size 3mm) up to the stop and
disassemble the mounting plate. Pass the power connecting cable through the
cable entry in the mounting plate. The installed black gasket insert is
intended for cables ø < 10mm. For cables ø 10-12mm the enclosed grey gasket
insert must be used. In case of through-wiring replace the factory installed
dummy plug with the enclosed corresponding gasket insert. At the same time,
use the enclosed synthetic cone-thrust collar between gasket insert and thrust
screw (wrench size 22 mm) (see sketch).
Fix the mounting plate with enclosed or any other suitable fixing material
onto the mounting surface. Tighten screw cable gland. Make earth conductor
connection and electrical connection to the connecting terminal (plug
connection). For digital control please use the connecting terminal DA, DA. In
case this terminal is not used the luminaire will be operated at full light
output.
Make sure that gasket is positioned correctly. Push plug into coupler as far
as it will go. Place the luminaire onto the mounting plate and fix it.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits. Do not use high pressure cleaners.
Please note:
Do not remove the desiccant bag from the luminaire housing. It is needed to
remove residual moisture.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Inspect and, if necessary, replace the luminaire gaskets. Defective glass must be replaced. Close the luminaire.
Spares
16 006 367 | Shield inside |
---|---|
DEV-0270/1050i | LED power supply unit |
LED-0800/830 | LED module 3000 K |
LED-0800/840 | LED module 4000 K |
76 001 986 | Reflector narrow beam |
83 002 076 | Gasket housing |
83 002 077 | Gasket mounting box |