BEGA 33062 Recessed Wall Luminaire
Product Information
Specifications:
- Luminaire made of aluminium alloy, aluminium, and stainless steel
- Colour options: graphite or silver
- Safety glass with optical structure
- Silicone gasket
- Reflector made of pure anodised aluminium
- Fixing with two adjustable wedge-shaped claws
- Required recessed opening: 315 x 110 mm
- Recessed depth: 90 mm
- LED power supply unit: 220-240 V x 0/50-60 Hz DC 176-276 V
- DALI-controllable with one DALI address
- Safety class I
- Protection class IP65 for dust-tight and protection against water jets
- Impact strength IK08
Product Usage Instructions
Installation:
- Ensure to follow national safety regulations during installation.
- Installation and commissioning should only be done by a qualified electrician.
- Use bounce-free switching contacts for optimal protection of electronic components.
Maintenance:
Use chemical cleaning agents cautiously around the luminaire if coated with
BEGA Tricoatb to avoid damage to the coating.
FAQ:
-
Q: Can this luminaire be used for surface mounting?
A: Yes, this luminaire can be used for flush or surface mounting installations. -
Q: What is the recommended power supply for this luminaire?
A: The recommended LED power supply unit is rated at 220-240 V x 0/50-60 Hz DC 176-276 V.
Application
- Recessed wall luminaire with asymmetrical flat beam light distribution, for flush or surface mounting installation.
- For the wide beam and uniform illumination of surfaces and paths.
Product Description
- Luminaire made of aluminium alloy, aluminium and stainless steel
- BEGA Tricoat® coating technology
- Colour graphite or silver
- Safety glass with optical structure
- Silicone gasket
- Reflector made of pure anodised aluminium
- Fixing is achieved by using two adjustable wedge-shaped claws
- Required recessed opening 315 x 110 mm
- Recessed depth 90 mm 2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G 1.5@
- Connecting terminal and earth conductor terminal 2.5@
- BEGA Ultimate Driver®
- LED power supply unit 220-240 V x 0/50-60 Hz
- DC 176-276 V
- DALI-controllable
- Number of DALI addresses: 1
- Basic insulation is provided between the mains and control cables
- BEGA Thermal Control®
- Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
- Safety class I
- Protection class IP 65
- Dust-tight and protection against water jets
- Impact strength IK08
- Protection against mechanical impacts < 5 joule
- – Safety mark
- – Conformity mark
- Weight: 2.0 kg
- This product contains light sources of energy efficiency class(es) C
Safety
- The installation and operation of this luminaire are subject to national safety regulations.
- Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation.
- If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage by DIN EN 61547.
- To achieve additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
- The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71 320.
Please note:
- This luminaire is coated with BEGA Tricoatb.
- BEGA Tricoatb is a registered trademark for a technology that we use to achieve optimal corrosion resistance.
- Even the best possible surface protection and the highest corrosion resistance can be rendered almost ineffective in some cases by aggressive media caused by the leaching of building materials.
- Where such media are suspected, a material analysis must be carried out before installation.
- Always avoid excessive use of chemical cleaning agents in the vicinity of the luminaire.
Installation
-
The recessed opening will be covered by the frame of the luminaire housing.
-
Fixing of the luminaire is achieved by using two adjustable wedge-shaped claws.
-
Installation in solid, plastered walls:
The installation housing 10 436 is available for this purpose. If this is not used, an exact recessed opening of 315 x 110 mm with a minimum depth of 90 mm is required. -
Installation in exposed brickwork:
The construction of an on-site recessed opening with the exact installation dimensions of 315 x 110 mm with a minimum depth of 90 mm is required. An installation housing cannot be used. -
Installation in drywalling:
A recessed opening of 315 x 110 mm with a minimum depth of 90 mm is required. The claws grip behind drywall. -
Installation into insulated façades:
For installation in EWIS external wall insulation systems please use installation housing 13 522 in combination with a plaster frame 10 036 or 13
Open luminaire:
- Undo the screws and remove the housing cover.
- Disconnect the plug-connection of the LED connecting cable.
- Disconnect the earth conductor connection from the plug connection.
- Lead the main supply cable through the cable entry into the luminaire housing.
- Make the earth conductor connection and the electrical connection.
- For digital control please use the connecting terminal DA, DA.
- In case this terminal is not used the luminaire will be operated at full light output.
- To guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
- Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.
- Connect the LED connection cable using a plug connector.
- Put on earth conductor connection of the housing cover. Assemble the housing cover.
- Make sure that the gasket is positioned correctly.
- Tighten the screws evenly.
- Insert luminaire housing into the recessed opening. Hand-tighten the screws of the claw fastener evenly. Do not use an electric screwdriver!
Dimension
Lamp
- Module connected wattage 12 W
- Luminaire connected wattage 15 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 45 °C
- When installed in heat-insulating material ta max = 35 °C
33 062 K3
- Module designation LED-0575/830
- Colour temperature 3000 K
- Colour rendering index CRI > 80
- Module luminous flux 2095 lm
- Luminaire luminous flux 1331 lm
- Luminaire luminous efficiency 88,7 lm/W
33 062 K4
- Module designation LED-0575/840
- Colour temperature 4000 K
- Colour rendering index CRI > 80
- Module luminous flux 2125 lm
- Luminaire luminous flux 1350 lm
- Luminaire luminous efficiency 90 lm/W
Cleaning And Maintenance
- Clean the luminaire regularly with solvent-free cleansers from dirt and deposits.
- Do not use high-pressure cleaners.
Replacing the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
- The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire.
- Please follow the installation instructions for the LED module.
- Inspect and, if necessary, replace the luminaire gaskets.
- The defective glass must be replaced.
- Close the luminaire.
Accessories
- 10 436 Installation housing
- 13 522 Installation housing for installation in insulated façades (EWIS)
- 10 036 Plaster frame
- 13 506 Plaster frame flush
Separate instructions for use can be provided upon request.
Spares Parts
- LED power supply unit DEV-0312/700
- LED module 3000 K LED-0575/830
- LED module 4000 K LED-0575/840
- Reflector 76 001 442
- Gasket 83 001 561
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com.