67 683.3
Wall luminaire for indoor use
Instructions
for use
Application
Wall luminaire · indoor luminaire made of handblown opal glass, satin matt and
metal housing.
For all lighting tasks in interior applications.
Luminaire with a high protection class.
Product description
Die-cast aluminium and aluminium housing, finish Chrome
Hand-blown opal glass, satin matt
Silicone gasket
2 mounting holes ø 5.5 mm
Distance apart 440 x 56 mm
2 cable entries for through-wiring of mains
supply cable ø 7-10.5 mm, max. 5 G 1.5@
Connection terminal 2.5@
Earth conductor connection
2-pole connecting terminal for digital control
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect
temperature-sensitive components without switching off the luminaire
Safety class I
Protection class IP 44
Protected against granular foreign bodies
≥ 1 mm and splash water
Impact strength IK04
Protection against mechanical
impacts < 0.5 joule
– Safety mark
– Conformity mark
Weight: 2.0 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 12.4 W |
---|---|
Luminaire connected wattage | 15.3 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 45 °C |
67 683.3 K27
Module designation | 4x LED-0546/927 |
---|---|
Colour temperature | 2700 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1820 lm |
Luminaire luminous flux | 1282 lm |
Luminaire luminous efficiency | 83,8 lm / W |
67 683.3 K3
Module designation | 4x LED-0546/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1880 lm |
Luminaire luminous flux | 1325 lm |
Luminaire luminous efficiency | 86,6 lm / W |
67 683.3 K4
Module designation | 4x LED-0546/940 |
---|---|
Colour temperature | 4000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 2020 lm |
Luminaire luminous flux | 1427 lm |
Luminaire luminous efficiency | 93,3 lm / W |
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Loosen screw of the lateral cover and take off the glass from the luminaire
housing.
Lead the mains supply cable through the cable entry into the luminaire
housing.
Secure the luminaire housing to the installation surface with the fixing
materials provided or other suitable materials.
Make sure to use the gaskets supplied.
Establish earth conductor connection and make the electrical connection to the
terminals.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Position glass into the base plate and fix it with the screw and the cover.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass | 11 002 799 .0R G |
---|---|
LED power supply unit | DEV-0388/370i |
LED module 2700 K | LED-0546/927 |
LED module 3000 K | LED-0546/930 |
LED module 4000 K | LED-0546/940 |
Gasket glass | 81 000 277 .2 |
Gasket | 83 001 249 |
BEGA Gantenbrink-Leuchten KG
Postfach 31 60 · 58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>