17.23 Technical amendments reserved
Wall luminaire
Instructions for use
Application
Wall luminaire with asymmetrical light distribution for in-depth illumination
of surfaces.
The angle of attack of the luminaire is adjustable at 0° or 15° and thus can
be aligned to the surface to be illuminated.
The colour temperature of the luminaire can be set optionally to 3000 K and
4000 K.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Colour graphite or silver
Safety glass, antireflection-coated
Silicone gasket
Reflector made of pure anodised aluminium
Toolless closure
Adjustable joint for beam direction 0° or 15°
Mounting plate with 2 fixing holes ø 5.5 mm · 85 mm spacing 2 cable entries
for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G 1.5◻
Connecting terminal 2.5◻ with plug connection
Earth conductor connection
BEGA Ultimate Driver®
Complies with flicker requirements in accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V 0/50-60 Hz
DC 176-264 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Protection class IP 66
Dust-tight and protection against strong water jets
Impact strength IK08
Protection against mechanical
impacts < 5 joule
– Safety mark
**** – Conformity mark
Wind catching area: 0.03 m²
Weight: 4.2 kg
Dark Sky
The light of this luminaire is directed evenly and highly efficiently onto the surface to be illuminated. No light is emitted into the upper half-space of the luminaire.
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e. g. transients, etc. we recommend separate overvoltage
protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 32.1 W |
---|---|
Luminaire connected wattage | 37 W |
Module designation | LED-1446/83040 |
Colour rendering index | CRI > 80 |
Rated temperature | t a= 25 °C |
Ambient temperature | t a max = 30 °C |
Operation at colour temperature | 4000 K |
Module luminous flux | 5930 lm |
Luminaire luminous flux | 4843 lm |
Luminaire luminous efficiency | 130,9 lm / W |
Operation at colour temperature | 3000 K |
Module luminous flux | 5650 lm |
Luminaire luminous flux | 4615 lm |
Luminaire luminous efficiency | 124,7 lm / W |
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.The colour temperature of the LED module was set to
3000 K by default (switch position 1: “off”, 2: “on”).
For colour temperature 4000 K, the switch position 1: “on” and 2: “off” must
be selected.
Switching may only be carried out when disconnected from the power supply!
Open the luminaire (no tools needed). Release the lock and swivel the cover
frame complete with the glued-in glass and the reflector away from the
housing.
Use the switch located on the LED module to implement the desired setting.
Swivel cover frame onto the luminaire housing and lock. Make sure that the
gasket is positioned correctly.
Undo hexagon socket head screw (wrench size 3 mm) up to the stop and
disassemble the mounting plate.
Pass the power connecting cable through the cable entry in the mounting plate.
Note position of application of the mounting plate “arrow down”.
Fix the mounting plate with enclosed or any other suitable fixing material
onto the mounting surface.
Be sure to use the gasket rings supplied.
Make earth conductor connection and electrical connection to the connecting
terminal (plug connection).
For digital control please use the 2-pole plug connector DA, DA.
In case this connector is not used the luminaire will be operated at full
light output.
Adjustment of the beam direction:
Joint adjustment is factory-set at 0°.
For adjustment 15° :
Undo hexagon nut (wrench size 13) and adjust the joint. Make sure that the
tooth system is positioned correctly.
Tighten hexagon nut firmly.
Torque = 16 Nm (see sketch).
Make sure
that gasket is positioned correctly.
Place luminaire onto the mounting plate as displayed in the sketch align and
screw together firmly. Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
LED power supply unit | DEV-0270/1400i |
---|---|
LED module | LED-1446/83040 |
Reflector | 76 001 409 |
Gasket housing | 83 001 126 |
Gasket wall box | 83 001 838 |