BEGA 50607.1 Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 50607.1 Wall Luminaire

Product Information

This product is a luminaire that requires installation and operation according to national safety regulations. It is recommended to have a qualified electrician carry out the installation and commissioning. The manufacturer does not accept liability for damage caused by improper use or installation. If any modifications are made to the luminaire, the person responsible for these modifications is considered the manufacturer. The electronic components in the luminaire are protected against overvoltage in accordance with DIN EN 61547. For additional protection against transients, it is recommended to use separate overvoltage protection components, which can be found on the manufacturer’s website at www.bega.com.

The product has different specifications based on the module designation, color temperature, color rendering index (CRI), module luminous flux, luminaire luminous flux, and luminaire luminous efficiency. Please refer to the table below for the specific values:

Module Designation| Color Temperature| Color Rendering Index (CRI)| Module Luminous Flux| Luminaire Luminous Flux| Luminaire Luminous Efficiency
---|---|---|---|---|---
2x LED-0551/927| 2700 K| CRI > 90| 1540 lm| 1084 lm| 87.4 lm/W
2x LED-0551/930| 3000 K| CRI > 90| 1590 lm| 1120 lm| 90.3 lm/W

The product also has spare parts available, including spare glass, LED power supply unit, LED module 2700 K, LED module 3000 K, and a gasket. The part numbers for these spares are as follows:

  • Spare glass: 11 002 798 .0R G
  • LED power supply unit: DEV-0194/370
  • LED module 2700 K: LED-0551/927
  • LED module 3000 K: LED-0551/930
  • Gasket: 83 001 249

Product Usage Instructions

To use the luminaire, follow these instructions:

  1. Ensure that the luminaire is installed and commissioned by a qualified electrician according to national safety regulations.
  2. If any modifications are made to the luminaire, the person responsible for these modifications is considered the manufacturer.
  3. For additional protection against overvoltage and transients, it is recommended to use separate overvoltage protection components.
  4. Refer to the table above to determine the specific specifications of the product based on the module designation, color temperature, CRI, module luminous flux, luminaire luminous flux, and luminaire luminous efficiency.
  5. If any spare parts are required, refer to the part numbers provided and contact the manufacturer or visit their website for purchasing.

DIMENSIONS

BEGA-50607-1-Wall-Luminaire-FIG-1Instructions for use

Application

  • Wall luminaire · indoor luminaire made of handblown opal glass, satin matt and metal housing.
  • For all lighting tasks in interior applications.
  • Luminaire with a high protection class.

Product Description

  • Die-cast aluminium and aluminium housing, finish Colour white
  • Hand-blown opal glass, satin matt
  • Silicone gasket 2 mounting holes ø 5.5 mm
  • Distance apart 340×56 mm 2 cable entries for through-wiring for mains cable up to ø 10.5 mm max. 3 × 1.5@
  • Connection terminal 2.5@
  • Earth conductor connection
  • LED power supply unit 220-240 V 0/50-60 Hz
  • DC 176-276 V
  • Safety class I
  • Protection class IP 44
  • Protected against granular foreign bodies ≥ 1 mm and splash water
  • Impact strength IK03
  • Protection against mechanical
  • impacts < 0.35 joule
  •  – Safety mark
  •  – Conformity mark
  • Weight: 1.8 kg
  • This product contains light sources of energy efficiency classes D

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at  www.bega.com.

Lamp

  • Module connected wattage 10.4 W
  • Luminaire connected wattage 12.4 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 45 °C

50 607.1 K27

  • Module designation 2x LED-0551/927
  • Colour temperature 2700 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1540 lm
  • Luminaire luminous flux 1084 lm
  • Luminaire luminous efficiency 87,4 lm / W

50 607.1 K3

  • Module designation 2x LED-0551/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1590 lm
  • Luminaire luminous flux 1120 lm
  • Luminaire luminous efficiency 90,3 lm / W

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Loosen screw of the lateral cover and take off the glass from the luminaire housing.
  • Lead mains supply cable through the cable entry into the luminaire housing.
  • Fix the luminaire housing with enclosed or any other suitable fixing material onto the mounting surface.
  • It is imperative to use the enclosed gaskets.
  • Make earth conductor connection.
  • Push silicone sleeves over the lines and make electrical connection.
  • Position glass into the base plate and fix it with the screw and the cover.

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Inspect and, if necessary, replace the luminaire gaskets.
  • Defective glass must be replaced.
  • Close the luminaire.

Spares

  • Spare glass 11 002 798 .0R G
  • LED power supply unit DEV-0194/370
  • LED module 2700 K LED-0551/927
  • LED module 3000 K LED-0551/930
  • Gasket 83 001 249