BEGA Led-0447-930 Recessed Ceiling Luminaire For Indoor Use Instruction Manual

June 12, 2024
BEGA

BEGA Led-0447-930 Recessed Ceiling Luminaire For Indoor Use Instruction Manual

BEGA Led-0447-930 Recessed Ceiling Luminaire For Indoor Use Instruction
Manual

Instructions for use

Application

Recessed ceiling luminaire · indoor luminaire with impact resistant synthetic diffuser, translucent white and aluminium housing for connection to an external LED power supply unit. For installation in suspended ceilings of 9-25 mm in interior applications.

Product description

Recessed ceiling luminaire downlight »STUDIO LINE« without power supply unit Luminaire housing made of aluminium inside hue aluminium matt Impact resistant synthetic diffuser, translucent white, with bayonet closure Recessed opening ø 280 mm Required installation depth 145 mm Luminaire housing with 3 fastening springs and guide screws 1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI Safety class III 3 c ­ Conformity mark Weight: 1.4 kg This product contains light sources of energy efficiency classes D

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp
Module connected wattage 17.6 W
Luminaire connected wattage 20.5 W
Rated temperature ta=25 °C
Ambient temperature ta max=35 °C

50 892.2K3
Module designation LED-0447/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 2780 lm
Luminaire luminous flux 1761 lm
Luminaire luminous efficiency 85,9 lm/W

Installation

Luminaire housing must not be installed in heat-insulating material. A separate power supply unit is required to operate the luminaire. For connection to external LED-power supply unit ­ accessory 13 177 or 13 173 ­ the luminaire is equipped with a 2-pin connector. Note operating instructions of the LED-power supply units. LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or revamping.

Connect to the LED power supply unit. Guide the LED power supply unit through the opening in the ceiling and position it on the suspended ceiling. The recessed opening is covered by the frame of the luminaire housing. Fixing of the installation housing in the recessed opening is achieved by using three adjustable springs. Luminaire housing and external LED power supply unit must not be covered by any heat insulating materials.

Installation into inserted ceilings: A recessed opening of 280 mm with a minimum depth of 145 mm is required. Push luminaire housing into the ceiling cut-out and tighten evenly screws (T 20) of the three mounting springs. The mounting springs catch the ceiling facing from the back side. The minimum thickness of the panel must be 9 mm and the maximum thickness 25 mm. If the ceiling facing has a thickness of less than 3 mm, the facing thickness in the region of the mounting springs must be increased from the back side.

Connect the 2-pin plug connector between luminaire and external LED power supply unit. Unpack LED unit, lift it with enclosed gloves and insert it into the luminaire housing ­ keyholes ­ . Turn the LED device anticlockwise until it stops and tighten the screws (T 10) evenly.
Place the synthetic diffuser to the luminaire housing and observe that the cam pins fit into the notches of the synthetic diffuser. Screw in synthetic diffuser by turning it clockwise. Thus, you reach a safe and vibration resistant holding of the synthetic diffuser.

To release the synthetic diffuser from the luminaire housing, turn it counter- clockwise.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleaning agents to remove dirt.
A defective synthetic cover must be replaced.

Replacement of the LED module

The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system. Unscrew synthetic diffuser from luminaire housing by turning it counter-clockwise. Please follow the installation instructions for the LED module. Screw in synthetic diffuser by turning it clockwise. Defective synthetic diffuser must be replaced.

Accessories

Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.
13 177 Power supply unit on/off 13 173 Power supply unit DALI
The power supply units are only suitable for the operation of one LED luminaire.

For the accessories a separate instructions for use can be provided upon request.

Spares
Synthetic cover 15 000 424
LED module 3000 K LED-0447/930

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com