BEGA 50 158.1 Recessed Wall Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA 50 158.1 Recessed Wall Luminaire

Product Information

This product is a luminaire that requires installation and operation according to national safety regulations. It should only be installed and commissioned by a qualified electrician. The manufacturer is not liable for any damage caused by improper use or installation. The luminaire is equipped with electronic components that are protected against overvoltage according to DIN EN 61547. For additional protection against transients, it is recommended to use separate overvoltage protection components available on the manufacturer’s website at www.bega.com.

Lamp Module Specifications

Module Designation| Color Temperature| Colour Rendering Index| Module Luminous Flux| Luminaire Luminous Flux| Luminaire Luminous Efficiency
---|---|---|---|---|---
LED-0815/927| 2700 K| CRI > 90| 155 lm| 50 lm| 23.8 lm/W
LED-0815/930| 3000 K| CRI > 90| 160 lm| 52 lm| 24.8 lm/W

Installation Instructions

  1. Pass the mains cable through a cable entry of the recess box and fit the recess box.
  2. Ensure that the countersunk screws of the recess box are horizontal relative to the ground.
  3. Connect the earth conductor to the link on the luminaire housing.
  4. Make an electrical connection to the terminal of the power supply unit.
  5. Insert the luminaire into the recess box and use the two countersunk screws to adjust and secure it.
  6. Use retention pins to mount the trim ring with glass on the luminaire housing such that the two rear magnets are seated on the countersunk screws.

Note: The luminaire is supplied with a matching cavity-wall box. If using cavity-wall boxes from other manufacturers, ensure they are made of electrical insulating material such as plastic.
Please note that the through-wiring of the luminaire is only possible with an electronic box. For flush-mounting, it is recommended to use a flush-mounted box Kaiser 1068-02, and for cavity wall mounting, use a cavity-wall box Kaiser 9268-94.

Dimension

Instructions for use

Application

  • Recessed wall luminaire · indoor luminaire with crystal glass, inside white and metal housing. Luminaire with unshielded light for directing and conducting lighting.

Product Description

  • Recessed ceiling luminaire »ACCENT«
  • Die-cast zinc luminaire housing
  • Metal frame ring with safety glass, white inside
  • White finish
  • Cavity-wall box with 2 fixing claws and fixing screws
  • Ceiling aperture ø 68 mm
  • Free space installation depth required 65 mm
  • Mains cable up to ø 10.5 mm, max. 3 × 1.5@
  • Connecting terminal 1.5@
  • Earth conductor connection
  • LED power supply unit 220-240 V x 0/50-60 Hz
  • DC 176-264 V
  • Safety class I
  • r – Safety mark
  • c – Conformity mark
  • Weight: 0.25 kg
  • This product contains light sources of energy efficiency classes D

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 1 W
  • Luminaire connected wattage 2.1 W
  • Rated temperature ta=2 5 °C
  • Ambient temperature ta max =45 °C
  • When installed in heat-insulating material ta max =35 °C 50 158.1K27
  • Module designation LED- 0815/927
  • Color temperature 2700 K
  • Color rendering index CRI >90
  • Module luminous flux 155 lm
  • Luminaire luminous flux 50 lm
  • Luminaire luminous efficiency 23,8 lm/W 50 158.1K3
  • Module designation LED -0815/930
  • Color temperature 3000 K
  • Color rendering index CRI >90
  • Module luminous flux 160 lm
  • Luminaire luminous flux 52 lm
  • Luminaire luminous efficiency 24,8 lm/W

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.

Installation into solid walls

  • For this purpose, a recess box, ø 68 mm, and a recessed depth of min. 62 mm is necessary.

Installation into wall panels

  • A recessed opening of ø 68 mm is necessary to accept the cavity-wall box.
  • Recessed depth min. 65 mm.
  • The lateral distance between the cavity-wall box and standard combustible building parts must be at least 40 mm.
  • The claws of the cavity-wall box catch the wall panel from the backside.
  • If the minimum thickness is less than 7 mm, it must be reinforced from the back side.
  • The maximum thickness of the panel must be no more than 35 mm.
  • Pass the mains cable through a cable entry of the recess box and fit the recess box.
  • Make sure that the countersunk screws of the recess box are horizontal relative to the ground.
  • Connect the earth conductor to the link on the luminaire housing.
  • Make electrical connection to the terminal of the power supply unit.
  • Insert the luminaire into the recess box and use the two countersunk screws to adjust and secure it.
  • Use retention pins to mount the trim ring with glass on the luminaire housing such that the two rear magnets are seated on the countersunk screws

Note:

  • This luminaire is supplied with a matching cavity-wall box.
  • If cavity-wall boxes of other manufacturers are used, they must be made of electrical insulating material such as plastic!

Through-wiring

  • Please note : Through wiring of the luminaire is only possible by means of an electronic box.
  • We recommend the use of a flush-mounted box Kaiser 1068-02 for flush mounting and a cavity-wall box Kaiser 9268-94 for cavity wall mounting.

Cleaning · Maintenance

  • Clean the luminaire regularly with solvent-free cleansers from dirt.
  • The defective glass must be replaced.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light color and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the
  • LED module.
  • The defective glass must be replaced.
  • Close the luminaire.

Spares

  • Glass/Trim frame 20 000 040M
  • LED power supply unit DEV-0231/350
  • LED module 2700 K LED-0815/927
  • LED module 3000 K LED-0815/930
  • BEGA Gantenbrink-Leuchten KG
  • Postfach 3160
  • 58689 Menden
  • info@bega.com
  • www.bega.com

Documents / Resources

| BEGA 50 158.1 Recessed Wall Luminaire [pdf] Instruction Manual
50 158.1 Recessed Wall Luminaire, 50 158.1, Recessed Wall Luminaire, Wall Luminaire, Luminaire
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals