BEGA 50001.1 Recessed Ceiling Luminaire Instruction Manual

June 12, 2024
BEGA

50001.1 Recessed Ceiling Luminaire
Instruction Manual 50 001.1

 50001.1 Recessed Ceiling Luminaire

Technical amendments reserved
Recessed ceiling luminaire for indoor use

Instructions for use

Application
Recessed ceiling luminaire with crystal glass for wide beam light.
For installation in suspended ceilings of 10- 45 mm in interior applications.

Product description

Recessed LED luminaire
with a remote non-dimmable power supply unit
Luminaire made of aluminium alloy, luminium and stainless steel
Crystal glass with thread, partially frosted
Silicone gasket
Reflector made of pure anodised aluminium
Metal ceiling frame ring, Colour white
Luminaire housing with 2 fixing claws and guide screws
Ceiling aperture ø 71 mm
Free space installation depth required 75 mm
Connecting compartment with 2 cable entries for through-wiring of the mains supply cable from ø 8–10 mm max. 3 × 1.5@
1 screw cable gland factory-closed with sealing plug
Connecting terminals 2.5@
LED power supply unit
220-240 V x 0/50-60 Hz
DC 170-280 V
Safety class II 2
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK06
Protection against mechanical impacts < 1 joule
– Safety mark
****– Conformity mark
Weight: 0.47 kg
This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp

Module connected wattage 4.1 W
Luminaire connected wattage 5.6 W
Rated temperature ta = 25 °C
Ambient temperature material ta max = 50 °C

50 001.1 K3

Module designation LED-0458/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 600 lm
Luminaire luminous flux 309 lm
Luminaire luminous efficiency 55,2 lm / W

Lighting technology
Half beam angle 40°

Installation

LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.

Installation into concrete ceilings:
For the installation of luminaire and external power supply unit we recommend to use installation housing 10 407.
Installation into inserted ceilings:
A recessed opening of ø 71 mm is necessary to accept the luminaire housing.
Free space depth min. 75 mm.
The lateral distance between recessed luminaire and other building parts must be at least 50 mm.
The claws catch the ceiling facing from the back side. Minimum thickness of the ceiling facing is 10 mm.
If the ceiling facing has a thickness of less than 10 mm or in case of an installation into plasterboard ceilings, the facing thickness in the region of the claws must be increased from the back side.
Undo screw and remove cover from the connection housing.
Lead mains supply cable through the screw cable gland.
The installed gasket insert is intended for cables ø 8 mm. For cables ø 9-10 mm use the gasket insert that you will find in the enclosed bag.
In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
Make electrical connection. If an earth conductor is carried with the mains supply cable, this earth conductor is to be connected to the terminal block designated as “E”.
Tighten screw cable gland.
Install cover and fix with screws.
Remove glass with reflector from luminaire housing by turning counter- clockwise.
Push external LED power supply unit and luminaire housing into the ceiling cut-out.
Tighten guide screws.
When tightening the screws, the fixing claws must swivel onto the inside of the suspended ceiling. The luminaire is fixed.
When undoing the guide screws, the fixing claws swivel back and the luminaire can be removed.
Lead enclosed trim ring with gasket over the screw-neck of the glass.
Make sure that gasket is positioned correctly.
Insert glass with mounted reflector and frame ring by turning it clockwise into luminaire housing.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.

Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect from main supply.
Unscrew glass with ceiling frame ring from luminaire housing by turning it counterclockwise.
Please follow the installation instructions for the LED module.
Check gasket.
Screw in glass with ceiling frame ring by turning it clockwise beyond the stop.
Defective glass must be replaced.

Accessories

10 407.. ……………….. Installation housing
A separate instructions for use can be provided upon request.
Spares

Spare glass 11 003 089 10R G
LED power supply unit DEV-0141/350
LED module 3000 K LED-0458/930
Trim ring 71 001 570 M2
Reflector 76 001 333

BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com