BEGA 84165 In Ground Luminaire Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 84165 In Ground Luminaire
Product Information
Floodlight with symmetrical light distribution. For recessed mounting in compacted surfaces, paths and places. Drive-over luminaire for vehicles with pneumatic tyres. Please note: Luminaire must not be used for installation in road lanes, where the fixture is exposed to a horizontal strain due to braking, acceleration and change of direction.
Dimensions
Product Description
- Material: Aluminium casting, Aluminium, and Stainless Steel
- Protection Class: I
- Protection Rating: IP 67 (Dustproof and protection against temporary submersion)
- Pressure Load: 1,000 kg (~10 kN)
- Impact Resistance: IK09
Luminaire made of aluminium alloy, aluminium and stainless steel Cover frame
made of stainless steel, steel grade number 1.4301
Recess housing with cable entry for cable conduit, max ø 20 mm Matt safety
glass
BEGA Vortex Optics® .
Reflector surface made of pure aluminium 1,8 m water-resistant connecting
cable 07RN8-F 5 G 1@ with implemented water stopper and 1.2 m PVC cable
conduit
BEGA Ultimate Driver®
LED power supply unit220-240 V x 0/50-60 Hz
DC 176-264 V
DALI controllable
A basic isolation exists between power cable and control line BEGA Thermal
Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire Safety class I
Protection class IP 67
Dust-tight and protection against temporary immersion Pressure load 1,000 kg
(~10 kN)
Impact strength IK09
Protection against mechanical impacts < 10 joule
Maximum surface temperature 25 °C (measured according to EN 60598 of ta 15 °C)
c – Conformity mark
r – Safety mark
Weight: 5.4 kg
This product contains light sources of energy efficiency class(es) C
Safety:
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- For additional protection against transients, etc., separate overvoltage protection components are recommended.
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. We recommend fuse protection via a residual current circuit breaker to be provided by the customer. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e. g. transients, etc. we recommend separate overvoltage
protection components.
You can find them on our website at www.bega.com.
Lamp Module Information:
Module Designation| Colour Temperature| Colour Rendering Index| Module
Luminous Flux| Luminaire Luminous Flux| Luminaire Luminous Efficiency
---|---|---|---|---|---
2x LED-0771/827| 2700 K| CRI > 80| 2860 lm| 1822 lm| 99.6 lm/W
2x LED-0771/830| 3000 K| CRI > 80| 2950 lm| 1879 lm| 102.7 lm/W
2x LED-0771/840| 4000 K| CRI > 80| 3030 lm| 1930 lm| 105.5 lm/W
Product Usage Instructions
- Ensure that the luminaire is suitable for recessed mounting in compacted surfaces, paths, and places.
- Do not use the luminaire for installation in road lanes where it may be subjected to horizontal strain due to braking, acceleration, and change of direction.
- Connect the lamp module with the appropriate designation (2x LED-0771/827, 2x LED-0771/830, or 2x LED-0771/840) based on the desired colour temperature.
- Ensure that the ambient temperature does not exceed the maximum rated temperature specified for the luminaire.
- When installing the luminaire in heat-insulating material, follow the recommended connected wattage guidelines: 15.8 W for the 2x LED-0771/827 module, 18.3 W for the 2x LED-0771/830 module, and 18.3 W for the 2x LED-0771/840 module.
- For additional safety, consider using separate overvoltage protection components to protect against transients.
Instructions for use
Application
Floodlight with symmetrical light distribution. For recessed mounting in
compacted surfaces, paths and places. Drive-over luminaire for vehicles with
pneumatic tyres.
Please note:
Luminaire must not be used for installation in road lanes, where the fixture
is exposed to a horizontal strain due to braking, acceleration and change of
direction.
Light technique
Broad spread light distribution.
Half beam angle 55°
Lamp
Module connected wattage 15.8 W
Luminaire connected wattage 18.3 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 55 °C
When installed in heat-insulating material ta max = 35 °C
84 165 K27
Module designation 2x LED-0771/827
Colour temperature 2700 K
Colour rendering index CRI > 80
Module luminous flux 2860 lm
Luminaire luminous flux 1822 lm
Luminaire luminous efficiency 99,6 lm / W
84 165 K3
Module designation 2x LED-0771/830
Colour temperature 3000 K
Colour rendering index CRI > 80
Module luminous flux 2950 lm
Luminaire luminous flux 1879 lm
Luminaire luminous efficiency 102,7 lm / W
84 165 K4
Module designation 2x LED-0771/840
Colour temperature 4000 K
Colour rendering index CRI > 80
Module luminous flux 3030 lm
Luminaire luminous flux 1930 lm
Luminaire luminous efficiency 105,5 lm / W
Notice prior to installation:
To accept the maximum pressure load of 1,000 kg (~10 kN) a proper foundation
must be provided by the customer. The luminaire is mounted in a recess housing
made of high-strength aluminium profile. The pressure load is transferred to
the foundation by this housing. Foundation to be provided at site. The
foundation must be carried out on firm subgrade. In order to obtain a firm
stableness, the recess housing must be firmly concreted in. During preperation
of the foundation proper drainage must be provided, so that entering surface
water can drain off. The lacquering of the recess housing must not be damaged.
For the tightness of the luminaire it is important that the ground surface (1)
prepared later is either on the same level or slightly below top edge of the
recess housing (2) – see sketch (detail A).
Soil Conditions
The luminaire must not permanently have contact with aggressive media.
Aggressive media might be washed out of the soil and might corrode the housing
of the luminaire. In case of an unknown composition of the soil a soil
analysis should be made before installation. Aggressive media that is outgoing
from the ground surface might also affect the luminaire. Thus an overuse of
de-icing agents in the surroundings should be avoided. Parasitic current,
occuring from the outside, can cause corrosion damage at the luminaire.
Suitable counter measures must be carried out.
Installation
Dismantle luminaire from the recess housing. For this purpose undo screws in
the stainless steel frame. Lift luminaire out of the recess housing. Position
recess housing on the foundation (as described above) and fix it with enclosed
or any other suitable fixing material. To stabilize the recess housing when
preparing the foundation, insert the enclosed wooden spacer into the the
recess housing. 0.3 m of cable is provided in the installation housing so that
the luminaire may be removed. To protect the luminaire connecting cable from
damage push the enclosed cable conduit over the cable. The electrical
connection must be carried out with matching protection class and safety class
with suitable connection terminals (not included in the scope of delivery) at
the luminaire power supply cable. We recommend that you use distribution box
70 730 or 71 053 for this purpose. Ensure that the connection cable is
correctly connected. Make the mains connection to the brown (L), blue (N) and
green-yellow wires (1). The control cables are connected via the two wires
marked DALI. If these wires are not assigned, the luminaire will work with
full light output. Insert the lamp housing into the outer housing. Tighten
locking screws firmly.
Cleaning · Maintenance
After installation, the luminaire should first be cleaned. Building dust, residues from contact adhesives, paint splashes and rust film must be completely removed. Never use high pressure cleaners and cleaning implements made of normal steel, steel brushes or steel wool because they cause extraneous rust to form. When using stainless steel cleaners, please read the directions carefully. Cleaning agents containing hydrochloric acid and chlorides should never be used. We recommend cleaning the luminaires regularly.
Maintenance
Disconnect the electrical installation. Clean dirt and deposits from key
openings of screw head. Do not use a high pressure cleaner. Undo counter sunk
screws. Lift luminaire out of the recess housing and place it with the glass
side facing downwards onto an even and clean underlay. Undo the round nuts
(torx drive T25) and lift luminaire housing. Clean the luminaire – see
Cleaning · Maintenance. Remove reflectors from the housing groove carefully.
Replace LED modules:
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools Note installation instructions of the LED module.
Replacing the LED power supply unit:
To replace the power supply unit, the LED module carrier must be removed from
the luminaire housing. Loosen the hexagon socket screws (SW 3) and remove the
module carrier from the housing using the two metal pins. Replace power supply
unit.
Please note:
Do not remove the desiccant pouch from the luminaire housing. It is needed to
remove residual moisture. Insert the LED module carrier into the housing in a
diagonal downwards direction and push it down until the springs snap into
place.
Check all screws and threads thoroughly and grease them. Check the gasket and
replace, if necessary. A broken glass must be replaced. The luminaire housing
must be completely clean and absolutely dry. Insert reflectors. Ensure that
the reflector is positioned correctly in the housing recess. Insert glass with
gasket with stepped side turned upward into the luminaire housing. Make sure
that gasket is positioned correctly. Place cover ring onto glass step and
tighten round nuts firmly and evenly.
Torque = 2.5 Nm.
Insert the lamp housing into the outer housing and tighten locking screws
firmly.
Accessories
70 730 Distribution box for installation in soil with 7 cable entries
Connection terminals 5 x 4@
Spares
Spare glass 14 001 286
LED power supply unit DEV-0293/350
LED module 2700 K 2x LED-0771/827
LED module 3000 K 2x LED-0771/830
LED module 4000 K 2x LED-0771/840
Reflector 2x 76 001 591
Gasket glass 83 001 664
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>