BEGA 50029K27 LED Ceiling and Wall Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA 50029K27 LED Ceiling and Wall Luminaire

BEGA 50029K27 LED Ceiling and Wall Luminaire-product

Product Information

Product Name: Luminaire
Model Number: 50 029
Application: Indoor lighting

Safety

The installation and operation of this luminaire should be carried out by a qualified electrician. The manufacturer is not liable for damage caused by improper use or installation. Overvoltage protection is recommended for additional safety.

Technical Specifications

Lamp Module Connected Wattage: 8.2 W
Luminaire Connected Wattage: 10.3 W –
Rated Temperature: 25-35°C
Ambient Temperature: 25-35°C – Colour
Temperature: 2700 K (warm white), 3000 K (neutral white)
Colour Rendering Index (CRI): >90
Module Luminous Flux: 1165 lm (2700 K), 1205 lm (3000 K) – Luminaire Luminous
Flux: 648 lm (2700 K), 671 lm (3000 K)
Luminaire Luminous Efficiency: 62.9 lm/W (2700 K), 65.1 lm/W (3000 K) Product Usage

Instructions

  1. Safety Precautions: – The installation and commissioning of the luminaire should only be done by a qualified electrician. – Follow national safety regulations during installation and operation. – Avoid improper use or installation to prevent damage. – If modifications are made to the luminaire, the person responsible for the modifications will be considered the manufacturer.
  2. Overvoltage Protection: – The electronic components in the luminaire are protected against overvoltage according to DIN EN 61547. – For additional protection against transients and other issues, separate overvoltage protection components are recommended. – Visit the manufacturer’s website at www.bega.com to find suitable overvoltage protection components.
  3. Installation: – Before installing the luminaire onto a mounting surface, insert the luminaire housing into the trim ring (accessory). – To release the glass from the luminaire housing, turn it counter-clockwise.
  4. LED Handling: – LED units are high-quality electronic components. Avoid touching the light output opening directly during installation or relamping.
  5. Replacement of LED Unit: – The designation of the LED unit is noted on a label in the luminaire. – BEGA replacement units have the same light color and output as the originally fitted LED units. – Qualified individuals can replace the LED unit using standard tools. – Disconnect from the main power supply before starting the replacement process. – Unscrew the glass from the luminaire housing by turning it counter-clockwise. – Replace the LED unit with a new one. – Screw in the glass by turning it clockwise. – Defective glass must be replaced.
  6. Optional Accessories: – Metal trim rings in three enamel surfaces (white, palladium, glossy silver) are available for this luminaire. – Trim rings are accessories and must be ordered separately. – Part numbers: 13 001 (white), 13 002 (palladium), 13 003 (glossy silver).

Ceiling and wall luminaire for indoor use

BEGA 50029K27 LED Ceiling and Wall Luminaire-fig1

Instructions for use

Application
Ceiling and wall luminaire · indoor luminaire made of hand-blown opal glass and metal housing, for all lighting tasks. They are ideal for places where a soft and uniform lighting distribution is required.

Product description

  • Metal housing, finish Colour white
  • Hand-blown opal glass, satin matt, with bayonet closure
  • 2 mounting holes ø 5.5 mm
  • Distance apart 180 mm
  • 2 cable entries for through-wiring for mains cable up to ø 10.5 mm max. 3 × 1.5@ Connection terminal 2.5@
  • Earth conductor connection
  • LED power supply unit
  • 220-240 V y 50-60 Hz
  • BEGA Thermal Switch®
  • Temporary thermal shutdown to protect temperature-sensitive components
  • Safety class I
  • r – Safety mark
  • c  – Conformity mark
  • Weight: 1.7 kg
  • This product contains light sources of energy efficiency class(es) D, E

Safety

  • The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 8.2 W
  • Luminaire connected wattage 10.3 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 35 °C

50 029 K27

  • Colour temperature 2700 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1165 lm
  • Luminaire luminous flux 648 lm
  • Luminaire luminous efficiency 62,9 lm / W

50 029 K3

  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1205 lm
  • Luminaire luminous flux 671 lm
  • Luminaire luminous efficiency 65,1 lm / W

Luminaire with trim ring:

Before installing onto the mounting surface the luminaire housing must be inserted into the trim ring (accessory).

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Pass the mains supply cable through the grommet into luminaire housing.
Fix luminaire housing with enclosed or any other suitable fixing material on to the mounting surface.
It is imperative to use the enclosed gaskets. Dismantle the mains supply cable
approx. 60 mm.
Make earth and electrical connections to the terminals.
Place glass to the luminaire housing and observe that the cam pins fit into the notches of the glass.
Screw in glass by turning it clockwise.
Thus, you reach a safe and vibration-resistant holding of the glass.
To release the glass from the luminaire housing, turn it counterclockwise.

Replacement of the LED unit

  • The designation of the LED unit is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement units correspond to those of the LED units originally fitted. The LED unit can be replaced by qualified persons using standard tools.
  • Disconnect from main supply.
  • Unscrew glass from luminaire housing by turning it counterclockwise.
  • Replace the LED unit.
  • Screw in glass by turning it clockwise. Defective glass must be replaced.

Accessory · Trim rings

For this luminaire metal trim rings in 3 enamel surfaces are optional available.
Trim rings are accessories and must be ordered separately.

Item Part. No

  • Colour white 13 001
  • Colour palladium 13 002
  • Colour glossy silver 13 003

Spares

  • Spare glass 11 003 179 .0R G
  • LED unit 2700 K 75 001 897 .1K 27
  • LED unit 3000 K 75 001 897 .1K 3

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com