BEGA 51252.1 LED Recessed Ceiling Downlight Instruction Manual

June 12, 2024
BEGA

BEGA 51252.1 LED Recessed Ceiling Downlight

Product Information

The product is a luminaire that requires installation and operation according to national safety regulations. It is recommended to have a qualified electrician carry out the installation and commissioning. The manufacturer does not accept liability for damage caused by improper use or installation. The luminaire is equipped with electronic components that are protected against overvoltage in accordance with DIN EN 61547. However, for additional protection against transients, it is recommended to use separate overvoltage protection components, which can be found on the manufacturer’s website. The product features LED technology, and it is important to avoid touching the light output opening of the LED directly during installation or relamping.

Product Usage Instructions

  1. Ensure that the luminaire is installed and operated in compliance with national safety regulations.
  2. Have a qualified electrician carry out the installation and commissioning.
  3. Do not make any modifications to the luminaire without proper authorization from the manufacturer.
  4. For additional protection against transients, consider using separate overvoltage protection components available on the manufacturer’s website.
  5. Avoid touching the light output opening of the LED directly during installation or relamping.
  6. When installing the luminaire in heat-insulating material, ensure that the rated temperature and ambient temperature are within the specified limits.
  7. Refer to the module designation for information on connected wattage, colour temperature, colour rendering index, module luminous flux, luminaire luminous flux, and luminaire luminous efficiency.
  8. For any accessories required, request separate instructions for use.
  9. If any spare parts are needed, refer to the provided part numbers for spare glass, LED power supply unit, LED module 3000 K, and reflector.

Recessed ceiling downlight for indoor use

Instructions for use

Application
Recessed ceiling luminaire · indoor luminaire with adjustable wide beam light distribution.
With external DALI controllable power supply unit for installation into concrete ceilings or suspended ceilings.

Product Description

  • Recessed ceiling downlights with external PSU
  • Luminaire made of aluminium alloy, aluminium and stainless steel
  • Metal ceiling frame ring, Colour velvet white Clear safety glass
  • Reflector surface made of pure aluminium Optical silicone lens · BEGA Hybrid Optics® Luminaire housing with 3 fixing claws and guide screws
  • Recessed opening ø 202 mm
  • Required installation depth 140 mm
  • 1 connecting cable with strain relief and plug connector system for BEGA DALI-power supply unit
  • External LED power supply unit 700 mA 220-240 V x 0/50-60 Hz
  • DC 176-276 V
  • During DC operation the LED power is reduced to 15 %
  • DALI controllable
  • A basic isolation exists between power cable and control line
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class II
  • – Conformity mark
  • Weight: 2.0 kg

This product contains light sources of energy efficiency class(es) E

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
The recessed opening is covered by the frame of the luminaire housing.
Fixing of the luminaire in the structure is achieved by using three adjustable wedge-shaped claws.

Installation in concrete ceilings:
To accommodate the luminaire and the external power supply unit we recommend using the installation housing 10 443.

Installation in suspended ceilings:

  • A recessed opening of ø 202 mm with a minimum installation depth of 140 mm is required.
  • The external power supply unit requires a minimum of 90 mm clearance above the ceiling (see drawing).
  • The claws grip behind the ceiling cladding. The minimum thickness of the ceiling cladding is 5 mm.
  • If the thickness is less, and if installation is to be effected in plasterboard ceilings, the back of the ceiling cladding must be reinforced in the region of the claws.
  • The electrical connection must be made on site in the appropriate safety class on the LED power supply unit connecting cable. A distribution box must be used.
  • Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires. The two connecting terminals marked DA, DA are provided for digital control purposes.
  • If these terminals are not assigned, the luminaire will work with full light output.
  • Pull cover ring (magnetic) off the installation ring of the pivoting housing.
  • Connect plug part of the luminaire with power supply unit.
  • Push external LED power supply unit and luminaire housing into the ceiling cut-out. Tighten guide screws.
  • When tightening the screws, the fixing claws must swivel onto the inside of the suspended ceiling. The luminaire is fixed.
  • When undoing the guide screws, the fixing claws swivel back and the luminaire can be removed.

Adjustment of the direction of radiation:
Undo both hexagon socket head screws and remove transportation lock. Adjust tilt angle and beam direction of the LED. Tighten latching screw.
Mount the cover ring onto installation ring of the housing (magnetic).

Lamp

  • Module connected wattage 24.1 W
  • Luminaire connected wattage 28.5 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 45 °C
  • When installed in heat-insulating material ta max = 25 °C

51 252.1 K3

  • Module designation LED-0800/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 3350 lm
  • Luminaire luminous flux 2616 lm
  • Luminaire luminous efficiency 91,8 lm / W

Light technique

  • Recessed luminaire with adjustable optical system, 0-30° swivel-mounted and ±180° infinitely rotatable.
  • Wide beam light distribution.
  • Half beam angle 18°
  • The symmetrical light cone can be modified to resemble flat beam light distribution for special lighting applications by replacing the cover glass.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Inspect and, if necessary, replace the luminaire gaskets.
  • Defective glass must be replaced.
  • Close the luminaire.

Accessories

  • 10 443 Installation housing
  • 10 016 Exchangeable lens flat beam

For the accessories a separate instructions for use can be provided upon request.

Spares
Spare glass 14 001 562
LED power supply unit DEV-0144/700i
LED module 3000 K LED-0800/930
Reflector 76 001 852

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com