universal douglas BT-IHBS-x High Bay Sensor
The BT-IHBS-x (x= A or B) connects to the auxiliary power and 0-10V dimming connections on the LED driver equipped with these features. The BT-IHBs-x has an integral photo and occupancy sensor and will also receive Bluetooth® commands from other Bluetooth equipped controls and sensors. The commands will be used to set the control voltage of the 0-10V dimming circuit which controls the output of the LED driver.
Part Numbers
- BT-IHBS-A: 18” Leads, 4-wires
- BT-IHBS-B: 3-wire Harness and plug for RHBB fixtures
INSTALLATION
BT-IHBS-A
The BT-IHBS-A has a half-inch nipple for connection to fixture.
- Install the BT-IHBS-A in a location where direct light from the fixture does not enter the sensor.
- Install the BT-IHBS-A vertically with the sensor facing directly to the floor or work surface below (Fig. 1)
- Feed wires through the ½ inch knockout on the fixture and use the screw nut provided to secure the BT-IHBS-A. (Fig. 2)
- The gasket provided should be placed between the BT-IHBS-A and the fixture to prevent moisture intrusion into the fixture or BT-IHBS-A.
- Wires shall be connected as shown in the wiring diagram.
- The BT-IHBS-A may be provided with a right-angle adapter to allow for it to mount on the side of a fixture and have the sensor point down. (Fig. 3)
- The collar on the right –angle adapter can be removed and the nipple shortened to fit on fixtures where longer extension is undesirable.
- Follow commissioning instructions from the Douglas Lighting Controls Bluetooth® Commissioning and Room Control App (BTCC iOS APP) for final set up.
Wiring Diagram
BT-IHBS-B
The BT-IHBS-B has a 3-terminal plug that mates with a 3-terminal harness that
is installed on the fixture (ex. RHBB high-bay fixture). For installation,
-
Remove the existing center plastic piece on the RHBB fixture. (Fig. 1)
Separate the installed dimming wiring harness on the RHBB fixture and remove the end with the loose wire.(Fig. 2)
Feed the harness from the BT-IHBS-B through the middle of the RHBB fixture, mate them together and tightly screw them together. (Fig 3. & Fig.4) -
Insert the sensor into the center of the fixture and press and twist for it to lock into place. (Fig. 5)
-
Follow commissioning instructions from the Douglas Lighting Controls Bluetooth® Commissioning and Room Control App (BTCC iOS APP) for final set up.
Emergency Test
The BT-IHBS-x can be configured to act as an Emergency mode controller turning
on its connected fixture at full brightness when failure of normal power is
detected. See the Douglas Lighting Controls BTCC App Field Manual for details.
The BT-LRT Emergency operation can be tested using the iOS mobile device (e.g.
iPod Touch) that was used to commission the BT-IHBS-x with the Douglas
Lighting Controls BTCC App (BTCC).
To test Emergency operation, perform the following steps:
- Ensure the emergency circuit is connected to the fixture controlled by the BT-LRT and is energized.
- Use a Douglas Lighting Controls Bluetooth switch to turn OFF the BT-IHBS-x, or use the BTCC “Room Setup” tab on the commissioning mobile device to access control of the device and turn it OFF.
- Use the BTCC “System Setup” tab on the commissioning mobile device to navigate to the commissioned devices list and select the sengs cogwheel for the BT-LRT to test.
- In the settings page for the BT-IHBS-x, select the “Test Emergency Mode” button on the boom of the setting page. The BT-LRT will turn on to 100% brightness for approximately 30 seconds. Following the 30-second test, the fixture will remain ON and return to its previous dimming state. The device will resume normal operaon, e.g. responding to occupancy and switch control.
- Use the “Cancel” button in the upper le corner to exit the BT-IHBS-x Settings page WITHOUT wring the configuraon parameters.