INSTALLATION INSTRUCTIONS
LED T8 TUBE & DRIVER RETROFIT
SAFETY WARNINGS
IMPORTANT SAFETY INFORMATION
DANGER Risk of shock. Disconnect power before installation.
WARNING Risk of fire or electric shock. LED Retrofit Kit installation
requires knowledge of luminaire electrical systems. If not qualified, do not
attempt installation. The product must be installed in accordance with NEC or
your local electrical code. If you are not familiar with these codes and
requirements, contact a qualified electrician.
WARNING Risk of fire or electric shock. To prevent wiring damage or
abrasion, do not expose wires to the edge of sheet metal or any other sharp
objects.
WARNING Risk of fire or electric shock. Check the existing wiring and lamp
holders before installing the upgrade kit. Replace any damaged parts prior to
installation- Latin.
WARNINGRisk of fire or electric shock. Luminaire wiring and electrical
parts may be damaged when drilling for the installation of the LED upgrade
kit. Check for enclosed wiring and components.
SUITABLE FOR DRY LOCATIONS.
CONVIENT AUX EMPLACEMENTS HUMIDES.
WARNING Risk of fire or electric shock. Install this kit only in
luminaires that have the construction features and dimensions shown in the
photographs and/ or drawings, and where the input rating of the retrofit kit
does not exceed the input rating of the luminaire.
Only the holes indicated in the photographs or drawings may be made or altered
as a result of the kit installation. Do not leave any other holes open in a
wiring enclosure or electrical component.
NOTE THE RETROFIT KIT iS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE
SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY CSA OR AUTHORITIES
HAVING JURISDICTION.
Bluetooth Control: Included with models having the XCT suffix
Catalog #: BT-LRT-B LED Driver Compatibility Requirements
Qty of
Lamps| Kit Part Number| Driver Rating| Input
Voltage| Drivers Catalog#
---|---|---|---|---
Current| Voltage
2| LR22T8-24L8xx-10DU| 580mA| 45V min| 120-277V| D700C2OUNVPW-C
LR22T8-24L8xx-10DU-XCT| D700C2OUNVPWX12-C
3| LR32T8-36L8xx-10DU| 870mA| 45V min| 120-277V| D1OCC3OUNVPW-C
LR32T8-36L8xx-10DU-XCT| D1OCC3OUNVPWX12-C
4| LR42T8-48L8xx-10DU| 1160mA| 45V min| 120-277V| D15CC55UNVPW-C
LR42T8-48L8xx-10DU-XCT| D15CC55UNVPWX12-C
xx: 35/3500K, 40/4000K, 50/5000K
Module p/n: LR2FT8M12L/8xxA
INSTALLATION
For installation in lensed or parabolic 2’ x 2’ or 2’x4’ troffers. Type IC
(Insulated Ceiling) or type Non-IC, 40°C max ambient. Requires minimum 3”
depth.
STEP 1: Disconnect Power to the fixture
STEP 2: Remove existing lamps, ballast cover plate, and ballast. Leave
existing wire in place and as long as possible . Replace lamp holders if
necessary.
STEP 3: Verify that the luminaire is connected to the ground wire from the AC
supply.
STEP 4: Secure the driver into the fixture. Use a self-tapping screw (not
provided) if necessary.
STEP 5: Connect existing leads to the driver as shown. The lamps are connected
and operated in parallel to both ends of the lamps. Wires should be 18AWG
solid conductors with ¼” strip length.
STEP 6: Connect the BT-LRT-B controller and mount it adjacent to the LED
tubes, outside of the ballast wiring channel in recessed troffers (where
applicable).
STEP 7: Insert the line and neutral wires into their connectors.
STEP 8: Replace the ballast cover plate, take care not to pinch wires.
STEP 9: Insert the lamps with the label side facing the back of the fixture.
STEP 10: Place relamp label at a visible location in the fixture. Close or
replace the lens and secure latches or other fastening means.
STEP 11: Restore power and confirm lamps are operating properly.
BT-LRT-B INSTALLATION (where applicable)
The sensor has a magnet which allows for it to be mounted to the metal tray or
panel of the luminaire. The BT-LRT-B should not be mounted within the ballast
channel where it is completely enclosed in metal. The leads of the BT-LRT-B
are to be connected to the driver as shown in the wiring diagram.
For installation outside of the wiring channel of the fixture the leads should
be routed away from the input power leads and not come in contact with the
power leads. Leads should exit the end of the channel and the sensor be placed
between lamps.
CONNECTION DIAGRAMS
|
---|---
Models without Controls have Violet and Gray leads for 0-10V dimming and do
not have aux power.