universal douglas STRP4 Strip-Style Luminaire Instruction Manual

June 3, 2024
universal douglas

INSTALLATION INSTRUCTIONS
STRP4 Strip-Style Luminaire

SAFETY WARNINGS

IMPORTANT SAFETY INFORMATION
Before you begin.
Read these instructions completely & carefully.
**WARNING Risk of electrical shock. Disconnect power before servicing or installing the luminaire. Avertissement –
WARNING Risk of injury or damage. The luminaire will fall if not installed properly. Follow installation instructions, NEC and local codes, and best trade knowledge.
WARNING Risk of injury. Wear safety glasses and gloves during installation and servicing.
**
  WARNING Risk of injury or damage. Mount only to a mechanically sound surface; All fixtures must be connected to a grounded, three-wire supply; All electrical connections must be capped with UL-listed wire connectors rated 600V or higher; If supply wires are located within three inches of the LED driver, use wire rated for at least 90°C; Consult qualified electrician before installing.
Follow information on labels & instructions regaling installation near combustible materials, insulation, and building materials & in Dry or Wet locations. DD did not install h areas exposed to combustible vapors or gases. This product must be installed by a person familiar with the construction and operation of the product and the hazards involved, in accordance with the applicable intonation. Be an to-ground product to avoid potential electrical shock or another potential hazard. Use of accessory equipment not recommended by the manufacturer or instated consistent with instructions may case an unsafe condition. Do not completely or partially book light emerging from the product, as this could case an unsafe condition. Do not allow other items to come into contact with the product, as this may case an unsafe condition.
WARNING This product may contain cherntas known to the State of Caccia to cause cancer, birth defects and/or other reproductive ham. Roughly wash your hands after instating, servicing, handling, cleaning, or otherwise touching this product. This device compies with FCC CFR Tine 47 Pat 15, Class A requirements for EMI RFI.

INSTALLATION

Step 1: Unpack & Inspect
Carefully remove the fixture from the packaging. Use gloves to prevent dirt and oils from transferring to the unit. Inspect the fixture for any defects before proceeding. Confirm the product ordered matches the product received
Step 2: Remove Cover Plate
Disengage the cover plate from the fixture housing, being careful not to touch the LED diodes. Pull the assembly away from the housing, disconnect and set it aside in a location where it will not be exposed to moisture, dirt or mechanical damage. Be careful to avoid abrading low-voltage wires connecting the LED driver and LED module assembly.

Step 3: Install End Plates
At each end of the housing, snap in a standard end plate (2pc included). Use extended end plates (LNPL accessory sold separately) if using a lens. Alternatively, for continuous run installations use a standard end plate to align adjoining housings and ensure an end plate, either standard or extended is installed at the end of each run.
Step 4: Mount Housing
Use appropriate fasteners (not provided) to secure fixture housing to a mechanically sound surface. Use mounting holes in the top of the housing. Alternatively, for chain-mounted installations, use the PNDKIT chain mounting accessory kit.

Step 5: Electrical Connections
Route the power circuit to an appropriate knock-out. Secure the conduit or M/C cable to the fixture housing and make electrical connections: line to black, neutral to white and earth ground to the fixture housing using the designated ground screw.
Step 6: Replace Cover Plate and Test
Reconnect the LED module assembly and snap the cover plate into place. Be careful not to pinch, cut or abrade wires. Attach lens if using the LEN accessory (sold separately). Apply electrical power and confirm proper operation.

APPLICATION ADVICE

  • Do not touch LED diodes or connecting clips on the LED modules.
    This product is intended for application in indoor, dry and non-corrosive environments.

www.universaldouglas.com