Product Information
- Safety: The installation and operation of this luminaire must be done in accordance with national safety regulations. Only a qualified electrician should carry out the installation and commissioning. The manufacturer is not liable for damage caused by improper use or installation. Any modifications made to the luminaire should be done by the person responsible for those modifications.
- Overvoltage Protection: The electronic components in the luminaire are protected against overvoltage according to DIN EN 61547. For additional protection against transients and other issues, separate overvoltage protection components are recommended, which can be found on the manufacturer’s website.
- Lamp Specifications:
- Lamp Module Connected Wattage: 52.2 W
- Luminaire Connected Wattage: 61 W
- Rated Temperature: 25-45°C
- Ambient Temperature: 50-217.1 K3
- Module Specifications:
- Module Designation: 6x LED-0694/930
- Color Temperature: 3000 K
- Colour Rendering Index (CRI): >90
- Module Luminous Flux: 8310 lm
- Luminaire Luminous Flux: 6905 lm
- Luminaire Luminous Efficiency: 113.2 lm/W
- Note: If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to ensure that the mounting surface is connected conductively to the earth conductor of the luminaire.
- Note: If planning a linear arrangement of multiple luminaires, a minimum distance of 30 mm between the luminaire caps must be maintained for installation reasons.
Product Usage Instructions
- To prevent dirt accumulation on the LED modules, press the supplied plugs into the housing holes of the luminaire profile above the screw-fitting points.
- Clip the luminaire cover into the groove of the aluminum profile and push it until the top of the luminaire housing.
- Replace the housing cap and tighten the lateral Torx countersunk screw T25.
- To replace the LED module, refer to the designation noted on a label in the luminaire. The replacement modules from BEGA have the same light color and output as the originally fitted modules.
- Disconnect the system and open the luminaire. Follow the installation instructions for the LED module. If the luminaire cover is defective, it must be replaced. Close the luminaire after replacing the module.
Ersatzteile (Replacement Parts): Kunststoffabdeckung (Plastic Cover), LED- Netzteil (LED Power Supply), LED-Modul 3000 K (LED Module 3000 K)
DIMENSION
Instructions for use
Application
Ceiling and wall luminaire · indoor luminaire made of impact resistant
synthetic diffuser and aluminum housing. Luminaire with free-radiating and
uniform light distribution for linear illumination in the interior.
Product Description
Luminaire made of Aluminium, finish Colour white Light-diffusing synthetic
luminaire cover 3 elongated fixing holes Width 5.5 mm Connection terminal 2.5@
Earth conductor connection 2-pole connecting terminal for digital control LED
power supply unit 220-240 V x 0/50-60 Hz DC 176-276 V During DC operation the
LED power is reduced to 15 % DALI-controllable Basic insulation is provided
between the mains and control cables BEGA Thermal Control® Temporary thermal
regulation to protect temperature-sensitive components without switching off
the luminaire Safety class I r – Safety mark c – Conformity mark Weight: 3.9
kg This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp
- Module connected wattage 52.2 W
- Luminaire connected wattage 61 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 45 °C
50 217.1 K3
- Module designation 6x LED-0694/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 8310 lm
- Luminaire luminous flux 6905 lm
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface,
it is mandatory to make sure that the mounting surface is connected
conductively to the earth conductor of the luminaire! Luminaire luminous
efficiency 113,2 lm / W
Note:
If you a planning a linear arrangement of several luminaires, you must keep a
minimum distance of 30 mm between the luminaire caps for installation reasons.
Installation
LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping. Remove the luminaire from the packaging and put it down so that the open rear side of its housing rests on a soft surface. Undo the lateral Torx countersunk screw T25 and remove the luminaire cap. Make earth conductor connection. Push silicone sleeves over the lines and make an electrical connection to the terminals. For digital control please use the connecting terminal DA, DA. In case this terminal is not used the luminaire will be operated at full light output. Drill mounting holes into the mounting surface. Secure the luminaire housing to the installation surface with the fixing materials provided or other suitable materials. For wall installation note the position of the application “arrow down”.
To prevent dirt from accumulating on the LED modules, press the supplied plugs into the housing holes of the luminaire profile above the screw-fitting points. Clip the luminaire cover into the groove of the aluminum profile and push it until the stop of the luminaire housing. Replace the housing cap and tighten the lateral Torx countersunk screw T25.
Cleaning · Maintenance
Clean the luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools. Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module. The defective
luminaire cover must be replaced. Close the luminaire.
Spares
- Synthetic cover 15 000 481 .2
- LED power supply unit DEV-0214/2100i
- LED module 3000 K LED-0694/930
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com