Application

Ceiling and wall luminaire · indoor luminaire made of impact resistant synthetic diffuser and metal housing.
Large-area luminaire with high light output, high uniform light distribution and adjustable colour temperature (Tunable White).

Product description

Large-area LED luminaire »MAXIMA«
Metal luminaire mounting plate, finish Colour white
Light-diffusing synthetic luminaire cover Silicone gasket
Mounting plate with 2 key holes, pitch circle ø
220 mm and 3 elongated holes, pitch circle ø 1.090 mm, width 6 mm
Connecting terminals 2.5@ · Plug system
Earth conductor terminal 2-pole connecting terminal for digital control
LED power supply unit 220-240 V 0/50-60 Hz DC 176-280 V
DC Start ≥ 190 V
DALI controllable (Device Type 8 for Tunable
White according to IEC 62386-209)
A basic isolation exists between power cable and control line
Safety class I
Impact strength IK10
Protection against mechanical impacts < 20 joule
– Safety mark
– Conformity mark
Weight: 30.2 kg
This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

Module connected wattage| 123.2 W
Luminaire connected wattage| 144 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 45 °C
Module designation| 8x LED-0702/9TW
Colour temperature| adjust. 2700 – 6500 K
Colour rendering index| Ra > 90
Module luminous flux| 19360 lm
Luminaire luminous flux| 15960 lm
Luminaire luminous efficiency| 110,8 lm / W

Setting the colour temperature

The LED colour temperature of the luminaire can be set from 2700 to 6500 K (“Tunable White”).
Please note: To be able to set the LED colour temperature, the controller used must support DALI Device Type 8. If no LED colour temperature setting is made, 3000 K will be used by default.
Notice prior to installation:
For fixing the luminaire please consider sufficient load capacity of ceiling or wall.
For the electrical connection the position of the entry openung of the mounting plate must be considered (see sketch).
General fixing material may not be suitable for all applications.
Note approval of building supervision.
It is essential to make sure that the outrigger arms of the mounting plate do not lose their exact arrangement of 6 x 60° when mounting them on the mounting surface!

Installation

LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
Unpack mounting plate.
Pass the power connecting cable through the opening in the mounting plate.
Fasten the mounting plate with the supplied or other suitable fastening materials to the mounting surface – key holes -.
Mark the fastening points of the outrigger arms precisely on the mounting surface.
Fasten the outrigger arms of the mounting plate with the supplied or other suitable fastening materials to the mounting surface – elongated holes -.
Make sure that all the fastening points of the mounting plate and the outrigger arms are fully screw-fitted – see drawing!
Make the earth conductor connection and the electrical connection to the terminals of the mounting plate – plug connection.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light output.
Unpack luminaire and lift it with enclosed gloves.
ATTENTION: In order to avoid deformation under its own weight, do not deposit luminaire on its domed synthetic cover outside the package!
Wall mounting:
Pick up the luminaire and connect the plug-in terminal of the luminaire to the socket of the mounting plate.
Place the key holes at the rear of the fitting for the locking mechanism over the turn-and-lock parts of the outrigger arms and move as far as the stop.
Turn the luminaire clockwise and tighten as far as the stop.

BEGA 50193 Large-Area Luminaire for Indoor Use - Fig2

Ceiling installation:
IMPORTANT: When the luminaire is installed on the ceiling, it is essential to use the provided steel retention wires.
Pick up the luminaire and hook the steel retention wires by the spherical nipple into the recesses of the outrigger arms.
Use a suitable tool to bend the lateral metal lugs towards the ceiling – see drawing.
This will ensure that the spherical nipple of the steel retention wire cannot disconnect itself.
Connect the plug-in terminal of the luminaire to the socket of the mounting plate.
Place the key holes at the rear of the fitting for the locking mechanism over the turn-and-lock parts of the outrigger arms and move as far as the stop.
Turn the luminaire clockwise and tighten as far as the stop.

BEGA 50193 Large-Area Luminaire for Indoor Use - Fig3

To prevent unintentional loosening of the luminaire cover, turn the torx screw (T 10) in the edge of the luminaire housing until it stops (lock).

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleaning agents to remove dirt.
A defective synthetic cover must be replaced.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective luminaire cover must be replaced.
Close the luminaire.

Spares

Synthetic cover| 15 000 476
LED power supply unit| DEV-0263/700
LED module| LED-0702/9TW

‘Technical amendments reserved
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
[email protected]
www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEGA User Manuals

Related Manuals