BEGA 50292.1 Recessed LED Ceiling and Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 50292.1 Recessed LED Ceiling and Wall Luminaire Instruction Manual
Recessed LED Ceiling and Wall Luminaire

Application

Recessed ceiling and wall luminaire · indoor luminaire with hand-blown opal glass, satin matt and metal housing with cover ring and with external LED power supply unit.
Luminaire with adjustable colour temperature (Tunable White).
They are ideal for places where a soft and uniform lighting distribution is required.
For installation into ceilings with a shallow .depth in interior areas.

Product description

Dimension The Recessed LED Ceiling and Wall Luminaire

Recessed LED-ceiling and wall luminaire with a remote DALI controllable power supply unit Luminaire housing made of aluminum Metal cover ring Finish Color white Opal glass, satin matt, with screw neck Silicone gasket
Recessed opening ø : 414mm
Dimension The Recessed LED Ceiling and Wall Luminaire
Required installation depth : 65mm
Luminaire housing with 3 fixing claws and guide screws 2-pole connecting terminal for digital control
BEGA Ultimate Driver®
LED power supply unit : 220-240 V x 0/50-60 Hz
DC : 176-264 V
During DC operation the LED power is reduced to : 50%
DALI controllable (Device Type 8 for Tunable
White according to IEC : 62386-209)
A basic isolation exists between power cable and control line Safety class II
– Safety mark
– Conformity mark
Weight: 4.1 kg
This product contains light sources of energy efficiency class(es) E

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

Module connected wattage : 33 W
Luminaire connected wattage : 37.5 W
Rated temperature : ta=25 °C
Ambient temperature : ta max=30 °C
Module designation : LED-0805/9TW
Colour temperature adjust : 2700-6500 K
Colour rendering index : Ra > 90
Module luminous flux : 4050 lm
Luminaire luminous flux :  2200 lm
Luminaire luminous efficiency : 58,7 lm/W

  • preliminary data

Setting the colour temperature

The LED colour temperature of the luminaire can be set from 2700 to 6500 K (“Tunable White”). Please note: To be able to set the LED colour temperature, the controller used must support DALI Device Type 8. If no LED colour temperature setting is made, 3000 K will be used by default.

Installation

LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
The recessed opening is covered by the frame of the luminaire housing.
Fixing of the luminaire in the structure is achieved by using three adjustable wedge shaped claws. Installation The Electronic
Components

Installation in solid walls or ceilings
To accommodate the luminaire and the external power supply unit we recommend using the installation housing 13 030.
Please note:
To ensure that the luminaire is securely held in the plastered installation housing, it is essential to unscrew the screws on the underside of the fastening claws and remove the adapter for the fastening claws (see drawing).

Installation in suspended ceilings
A recessed opening of ø 414 mm with a minimum installation depth of 65 mm is required.
The lateral distance between the luminaire housing and parts of the building must be at least 50 mm.
The claws grip behind the panel.
The minimum thickness of the panel must be 3 mm and the maximum thickness 20 mm. A panel with less than 5 mm thickness must be reinforced on the reverse side

Remove glass from luminaire housing by turning it counter-clockwise.
Open cover of the LED-power supply unit and lead mains supply cable into it.
Make electrical connection to the terminals. For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light output.
Close cover of the LED-power supply unit.
Push external LED power supply unit and luminaire housing into the ceiling cut-out.
Luminaire housing and external LED power supply unit must not be covered by any heat insulating materials.
Tighten guide screws.
When tightening the screws, the fixing claws must swivel onto the inside of the suspended ceiling. The luminaire is fixed. When undoing the guide screws, the fixing claws swivel back and the luminaire can be removed. Screw the glass into the luminaire housing by turning it clockwise. Make sure the seal is properly located.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.

Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Unscrew glass with cover ring from luminaire housing by turning it counter- clockwise.
Please follow the installation instructions for the LED module.
Check the gasket and replace, if necessary.
Screw glass with mounted cover ring into luminaire housing by turning it clockwise. Make sure that gasket is positioned correctly. Defective glass must be replaced.

Accessories

13 030 Installation housing

For the accessories a separate instructions for use can be provided upon request.

Spares

Spare glass 11 003 071 40R
LED power supply unit DEV-0264/700
LED module LED-0805/9
Trim ring 71 001 525
Gasket glass 83 001 462

BEGA Gantenbrink-Leuchten KG
Postfach 3160 · 58689 Menden
Email : info@bega.com
website : www.bega.com