BEGA 50068.3 Linear Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 50068.3 Linear Wall Luminaire

BEGA-50068-3-Linear-Wall-Luminaire-PRODUCT-IMG

DIMENSIONS

BEGA-50068-3-Linear-Wall-Luminaire-FIG-1

Instructions for use

Application

  • Free radiating wall luminaire · indoor luminaire with hand-blown three-ply opal glass for a soft and uniform light distribution.
  • The elongated design of this wall luminaire particulary provides suitability for installation on pillars, columns and for the front surface of walls, as well as for recesses or profiles.
  • The luminaire may be installed horizontally or vertically.

Product Description

  • Metal luminaire housing, finish Chrome
  • Hand-blown opal glass
  • The electrical equipment can be hinged 2 mounting holes ø 6 mm
  • Distance apart 300 mm
  • Jointing sleeve with cable entry for mains supply cable up to ø 14 mm, max. 5 x 1.5@
  • Connecting terminals 2.5@
  • Earth conductor terminal
  • LED power supply unit 220-240 V x 0/50-60 Hz
  • DC 176-276 V
  • During DC operation the LED power is reduced to 15 %
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Protection class IP 65
  • Dust-tight and protection against water jets
  • Impact strength IK03
  • Protection against mechanical
  • impacts < 0.35 joule
  •  – Safety mark
  •  – Conformity mark
  • Weight: 3.0 kg
  • This product contains light sources of energy efficiency class(es) D

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at  www.bega.com.

BEGA-50068-3-Linear-Wall-Luminaire-FIG-5

Installation

  • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Undo hexagon socket (wrench size 5) in the locking cap and remove it.
  • The opal glass can now be hinged together with the electrical equipment to the front.
  • Remove opal glass.
  • Note position of application of the luminaire »arrow down«.
  • Drill mounting holes into the mounting surface – spacing 300 mm and turn in enclosed or suitable fixing screws.
  • For the electrical connection undo the screw connection at the line connector and remove terminal block.
  • Make earth conductor connection and electrical connection.
  • Make connection of the phase with the L marked, the neutral wire at the N marked and earth conductor at the PE marked connecting terminal.
  • For digital actuation please use the two connecting terminals DA. The luminaire will work with full light output if these terminals are not assigned.
  • Bolt together both screw cable glands firmly.
  • Hook luminaire into the fixing screws and tighten.
  • Slide opal glass over the lamp and fasten with the locking cap.
  • Make sure that the gaskets are positioned correctly.

Lamp

  • Module connected wattage 19.2 W
  • Luminaire connected wattage 22.5 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 45 °C 50 068.3 K3
  • Module designation
  • 2x LED-0626/930 + 2x LED-0627/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 3210 lm
  • Luminaire luminous flux 2286 lm
  • Luminaire luminous efficiency 101,6 lm / W

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.
  • Defective glass must be replaced.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Defective glass must be replaced.
  • Close the luminaire.

Spares

  • Spare glass 11 002 763 .1R G
  • LED power supply unit DEV-0158/700i
  • LED module 3000 K LED-0627/930
  • LED module 3000 K LED-0626/930
  • Gasket glass 2x 83 000 788

BEGA Gantenbrink-Leuchten KG

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals