BEGA 50001.2 Recessed Ceiling Luminaire Instructions
- June 13, 2024
- BEGA
Table of Contents
- BEGA 50001.2 Recessed Ceiling Luminaire
- Product Information
- Product Usage Instructions
- DIMENSIONS
- Instructions for use
- Application
- Product description
- Safety
- Overvoltage protection
- Installation
- Cleaning · Maintenance
- Accessories
- Spares
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEGA 50001.2 Recessed Ceiling Luminaire
Product Information
- Product Name: Recessed Ceiling Luminaire
- Model Number: 50 001.2
- IP Rating: IP65
- Dimensions: 65 x 60 mm
- Application: Wide beam light for installation in suspended ceilings of 1045 mm in interior applications
- Safety: Installation and operation must comply with nationalsafety regulations. Only qualified electricians should carry out installation and commissioning. The manufacturer is not liable for damage caused by improper use or installation. Any modifications to the luminaire should be done by a responsible person considered as the manufacturer.
- Overvoltage Protection: The luminaire’s electronic components are protected against overvoltage according to DIN EN 61547. Additional overvoltage protection components are recommended for enhanced protection.
Product Usage Instructions
- Ensure that the luminaire is installed and operated according to national safety regulations.
- Installation and commissioning should only be carried out by a qualified electrician.
- Avoid touching the light output opening of the LED directly during installation or relamping to prevent damage to the high-quality electronic components.
- If additional overvoltage protection is desired, refer to the manufacturer’s website at www.bega.com for suitable components.
- For replacements or spare parts, refer to the provided part numbers:
- Spare Glass: 11 003 089
- LED Power Supply Unit: DEV-0141/350
- LED Module (3000 K): LED-0458/930
- Trim Ring: 71 001 570 M1
- Reflector: 76 001 333
DIMENSIONS
Instructions for use
Application
- Recessed ceiling luminaire with crystal glass for wide beam light.
- For installation in suspended ceilings of 10-45 mm in interior applications.
Product description
- Recessed LED luminaire with a remote non-dimmable power supply unit
- Luminaire made of aluminium alloy, aluminium and stainless steel
- Crystal glass with thread, partially frosted Silicone gasket
- Reflector made of pure anodised aluminium
- Ceiling frame ring made of stainless steel
- Luminaire housing with 2 fixing claws and guide screws
- Ceiling aperture ø 71 mm
- Free space installation depth required 75 mm
- Connecting compartment with 2 cable entries for through-wiring of the mains supply cable from ø 8–10 mm max. 3 × 1.5@1 screw cable gland factory-closed with sealing plug
- Connecting terminals 2.5@
- LED power supply unit 220-240 V x 0/50-60 Hz
- DC 170-280 V
- Safety class II 2
- Protection class IP 65
- Dust-tight and protection against water jets Impact strength IK06
- Protection against mechanical
- impacts < 1 joule
- – Safety mark
- CE – Conformity mark
- Weight: 0.47 kg
- This product contains light sources of energy efficiency class(es) D
Safety
- The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
Lamp
- Module connected wattage 4.1 W
- Luminaire connected wattage 5.6 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 50 °C
- When installed in heat-insulating
- material ta max = 35 °C
50 001.2 K3
- Module designation LED-0458/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 600 lm
- Luminaire luminous flux 309 lm
- Luminaire luminous efficiency 55,2 lm / W
Lighting technology
- Half beam angle 40°
Installation
- LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Installation into concrete ceilings:
- For the installation of luminaire and external power supply unit we recommend to use installation housing 10 407.
Installation into inserted ceilings:
- A recessed opening of ø 71 mm is necessary to accept the luminaire housing.
- Free space depth min. 75 mm.
- The lateral distance between recessed luminaire and other building parts must be at least 50 mm.
- The claws catch the ceiling facing from the back side. Minimum thickness of the ceiling facing is 10 mm. If the ceiling facing has a thickness of less than 10 mm or in case of an installation into plasterboard ceilings, the facing thickness in the region of the claws must be increased from the back side.
- Undo screw and remove cover from the connection housing.
- Lead mains supply cable through the screw cable gland.
- The installed gasket insert is intended for cables ø 8 mm. For cables ø 9-10 mm use the gasket insert that you will find in the enclosed bag. In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
- Make electrical connection. If an earth conductor is carried with the mains supply cable, this earth conductor is to be connected to the terminal block designated as “E”. Tighten screw cable gland.
- Install cover and fix with screws.
- Remove glass with reflector from luminaire housing by turning counter-clockwise.
- Push external LED power supply unit and luminaire housing into the ceiling cut-out. Tighten guide screws.
- When tightening the screws, the fixing claws must swivel onto the inside of the suspended ceiling. The luminaire is fixed.
- When undoing the guide screws, the fixing claws swivel back and the luminaire can be removed.
- Lead enclosed trim ring with gasket over the screw-neck of the glass.
- Make sure that gasket is positioned correctly. Insert glass with mounted reflector and frame ring by turning it clockwise into luminaire housing.
Cleaning · Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt.
- Defective glass must be replaced.
- Replacement of the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
- Disconnect from main supply.
- Unscrew glass with ceiling frame ring from luminaire housing by turning it counter-clockwise.
- Please follow the installation instructions for the LED module.
- Check gasket. Screw in glass with ceiling frame ring by turning it clockwise beyond the stop. Defective glass must be replaced.
Accessories
- 10 407 Installation housing
A separate instructions for use can be provided upon request.
Spares
- Spare glass 11 003 089 10R G
- LED power supply unit DEV-0141/350
- LED module 3000 K LED-0458/930
- Trim ring 71 001 570 M1
- Reflector 76 001 333
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>