77 019
IP 68
In-ground luminaire
Instructions for use
Application
Floodlight with asymmetrical light distribution for recessed mounting in
compacted surfaces, paths and places.
Drive-over luminaire for vehicles with pneumatic tyres.
Please note:
Luminaire must not be used for installation in road lanes, where the fixture
is exposed to a horizontal strain due to braking, acceleration and change of
direction.
Product description
Cover ring Luminaire housing made of stainless steel and cast stainless steel
Steel grade number 1.4301 Clear safety glass Reflector made of pure anodised
aluminium 2 mounting holes ø 5 mm Distance apart 120 mm 1,8 m water-resistant
connecting cable
05RN8-F 3 G 1@ with implemented water stopper and 1.2 m PVC cable conduit BEGA
Ultimate Driver® LED power supply unit 220-240 V x 0/50-60 Hz DC 176-264 V
BEGA Thermal Switch® Temporary thermal shutdown to protect temperature-
sensitive components Safety class I Protection class IP 68 10 m Dust-tight and
water pressure tight Maximum submersion depth 10 m Not suitable for permanent
operation under water Pressure load 2,000 kg (~20 kN) Impact strength IK10
Protection against mechanical impacts < 20 joule Maximum surface temperature
20 °C (measured according to EN 60598 of ta 15 °C)
– Safety mark
**** – Conformity mark
Weight: 1.6 kg
This product contains light sources of energy efficiency class(es) C
Lighting technology
Half beam angle 34/35°
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
We recommend fuse protection via a residual current circuit breaker to be
provided by the customer.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components. You can find them on our
website at www.bega.com.
Notice prior to installation:
To accept the maximum pressure load of 2,000 kg (~20 kN) a proper foundation
must be provided by the customer.
The pressure load is transferred to the foundation by this luminaire housing
provided at site.
The foundation must be carried out on firm subgrade.
In order to obtain a firm stableness, the luminaire housing must be firmly
concreted in.
Installation
Position luminaire housing on the foundation (as described above) and fix it
with enclosed or any other suitable fixing material.
Note alignment of the surface to be illuminated.
The electrical connection at the luminaire connecting cable must be carried
out on site according to the protection class and safety class.
We recommend to use a distribution box 70 730.
If the luminaire connecting cable is laid in the soil the enclosed protective
conduit must be used.
After finishing the ground works remove protection film from the luminaire
cover.
Tighten the screws in the trim ring evenly crosswise.
Torque = 3 Nm.
Cleaning · Maintenance
After installation, the luminaire should first be cleaned. Building dust, residues from contact adhesives, paint splashes and rust film must be completely removed. Never use high pressure cleaners and cleaning implements made of normal steel, steel brushes or steel wool because they cause extraneous rust to form. When using stainless steel cleaners, please read the directions carefully. Cleaning agents containing hydrochloric acid and chlorides should never be used. We recommend cleaning the luminaires regularly.
Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.
Lamp
Module connected wattage | 3 W |
---|---|
Luminaire connected wattage | 4.1 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 50 °C |
When installed in heat-insulating material | ta max = 35 °C |
77 019 K27
Module designation| LED-0291/827
Colour temperature| 2700 K
Colour rendering index| CRI > 80
Module luminous flux| 535 lm
Luminaire luminous flux| 369 lm
Luminaire luminous efficiency| 90 lm / W
77 019 K3
Module designation| LED-0291/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 550 lm
Luminaire luminous flux| 379 lm
Luminaire luminous efficiency| 92,4 lm / W
77 019 K4
Module designation| LED-0291/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 565 lm
Luminaire luminous flux| 389 lm
Luminaire luminous efficiency| 94,9 lm / W
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
thoseof the modules originally fitted. The module can be replaced by qualified
persons using standard tools.
Disconnect the electrical installation.
Clean dirt and deposits from key openings of screw head. Do not use a high
pressure cleaner. Open the luminaire and clean. Use only solvent-free
cleansers. Dismantle the LED-board unit and disconnect the connecting cable at
the terminal of the LED board unit.
Make electrical connection of the new LED board unit.
Fix LED board unit in the luminaire housing.
Check all screws and threads thoroughly and grease. Check the gasket and
replace, if necessary. The luminaire housing must be completely clean and
absolutely dry. Close the luminaire. Torque = 3 Nm. Chemicals which have a
corroding effect must not affect the
luminaire housing.
Accessories
70 730 Distribution box
The distribution box is meant for installation in the soil and allows a
junction from the supply cable to the luminaire and through-wiring to the next
luminaire.
After the electrical connection the distribution box is filled up with gel and
closed.
Spares
Spare glass | 14 000 918 |
---|---|
LED power supply unit | DEV-0303/350 |
LED module 2700 K | LED-0291/827 |
LED module 3000 K | LED-0291/830 |
LED module 4000 K | LED-0291/840 |
Reflector | 76 001 146 |
Gasket insert | 83 001 437 |
Gasket | 83 001 786 |
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com