BEGA 99 396 Outdoor Recessed Lighting Aluminum Instructions
- June 13, 2024
- BEGA
Table of Contents
In-ground luminaire
99 396 Instructions for use
Application
Floodlight for recessed installation in compacted surfaces with ø 70 mm
provided by the customer.
Drive-over luminaire from vehicles with pneumatic tyres.
Please note:
Luminaire must not be used for installation in road lanes, where the fixture
is exposed to a horizontal strain due to braking, acceleration and change of
direction.
Product description
In-ground LED luminaire without power supply unit Luminaire made of stainless
steel Steel grade no 1.4301
Installation bush made of polyamide Clear safety Class
Reflector made of pure anodised aluminium 3 m water-resistant connecting cable
05RN8-F 2 × 1◻ with implemented water stopper
Safety class III
Protection class IP 68 20 m
Dust-tight and water pressure tight
Maximum submersion depth 20 m
Not suitable for permanent operation under water
Impact strength IK08
Protection against mechanical impacts < 5 joule
– Safety mark
– Conformity mark
Weight: 0.8 kg
This product contains light sources of energy efficiency class(es) E, F
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Please note:
The luminaire can only be operated with an operating device that fulfills the
requirements according to EN 61347-2-13.
The maximum idle voltage of 60 V DC must conform to SELV or SELV equivalent.
Installation
Luminaire housing must not be installed in heat-insulating material.
A separate power supply unit is required to operate the luminaire – see
accessories.
For installation in drilled holes, a recessed
opening of ø 70 mm with a minimum depth of 100 mm is required to hold the
installation sleeve.
Press the installation sleeve firmly into the recessed opening.
For installation in paved surfaces, the appropriate installation housing is 70
745 available.
In this case, the polyamide installation sleeve is not used.
The cable connection must be established on site with the correct protection
class and safety class for the luminaire.
We recommend that you use distribution box 70 730 or 71 053 for this purpose.
To protect the luminaire power supply cable against damage we recommend you to
use a PVC conduit on-site.
A 24 V safety direct voltage source with a smoothed residual ripple of max. 10
% is required for the electrical connection of the luminaire – see
accessories.
If other safety direct voltage sources are used, an upstream fuse (max. 6 A)
must be provided by the customer.
The black wire is to be connected to the negative terminal, the red wire to
the positive terminal on the power supply unit.
Press the luminaire into the installation sleeve.
Lamp
Rated temperature | ta = 25 °C |
---|---|
Ambient temperature | a max = 65 °C |
When installed in heat-insulating | a max = 40 °C |
material Voltage | 24 V = DC |
99 396 K27
Module connected wattage | 3.4 W |
---|---|
Luminaire connected wattage | 4 W |
Colour temperature | 2700 K |
Colour rendering index | CRI > 80 |
Module luminous flux | 490 lm |
Luminaire luminous flux | 268 lm |
Luminaire luminous efficiency | 67 lm / W |
99 396 K3
Module connected wattage | 3.4 W |
---|---|
Luminaire connected wattage | 4 W |
Colour temperature | 3000 K |
Colour rendering index | CRI > 80 |
Module luminous flux | 495 lm |
Luminaire luminous flux | 271 lm |
Luminaire luminous efficiency | 67,8 lm / W |
99 396 K4
Module connected wattage | 4.6 W |
---|---|
Luminaire connected wattage | 5.2 W |
Colour temperature | 4000 K |
Colour rendering index | CRI > 80 |
Module luminous flux | 500 lm |
Luminaire luminous flux | 272 lm |
Luminaire luminous efficiency | 52,3 lm / W |
Cleaning · Maintenance
After installation, the luminaire should first be cleaned. Building dust,
residues from contact adhesives, paint splashes and rust film must be
completely removed.
Never use high pressure cleaners and cleaning implements made of normal steel,
steel brushes or steel wool because they cause extraneous rust to form.
When using stainless steel cleaners, please read the directions carefully.
Cleaning agents containing hydrochloric acid and chlorides should never be
used.
We recommend cleaning the luminaires regularly.
Accessories
Power supply unit for LED luminaires 24 V DC Safety transformer according to
EN 61558/VDE 0570 part 2-6
70 564 Power supply unit for 5-15 W
70 465 Power supply unit for 10-25 W
70 565 Power supply unit for 20-35 W
70 566 Power supply unit for 30-50 W
70 567 Power supply unit for 40-75 W
70 169 Power supply unit for 70-150 W
230 V ⁓ 50-60 Hz
70 114 Power supply unit for 0-70 W
AC range: AC: 198-264 V ⁓ 50-60 Hz
DC range: DC: 176-275 V
The power supply units are also suitable for the operation of several LED luminaires. In this case, the maximum wattage of the power supply unit must not be exceeded.
70 745 Installation housing made of stainless steel
70 730 Distribution box for installation in soil with 7 cable entries
Connection terminals 5 x 4◻
For the accessories a separate instructions for use can be provided upon
request.
Spares
Gasket housing | 83 001 363 .1 |
---|
Technical amendments reserved
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com