Product Information

  • Safety: The installation and operation of this luminaire should be done by a qualified electrician in compliance with national safety regulations. The manufacturer is not liable for damages caused by improper use or installation.
  • Overvoltage Protection: The luminaire has built-in protection against overvoltage. For additional protection against transients, it is recommended to use separate overvoltage protection components available on the manufacturer’s website.
  • Lamp: The connected wattage for the lamp module is 34.8 W, and for the luminaire is 42 W.
  • Temperature: The rated temperature for the luminaire is 25°C to 50°C, and the ambient temperature should be within the range of 50°C to 216.2°C.
  • Module Information: The module designation is 4x LED-0694/930 with a color temperature of 3000 K. The color rendering index (CRI) is greater than 90. The module luminous flux is 5540 lm, and the luminaire luminous flux is 4760 lm. The luminaire luminous efficiency is 113.3 lm/W.

Product Usage Instructions

  1. If the luminaire is to be mounted onto a metallic, electroconductive surface, ensure that the mounting surface is connected conductive to the earth conductor of the luminaire.
  2. If planning a linear arrangement of several luminaires, maintain a minimum distance of 30 mm between the luminaire caps for installation reasons.
  3. To prevent dirt accumulation on the LED modules, insert the supplied plugs into the housing holes of the luminaire profile above the screw-fitting points. Clip the luminaire cover into the groove of the aluminum profile and push it until it reaches the stop of the luminaire housing. Replace the housing cap and tighten the lateral Torx countersunk screw T25.
  4. When replacing the LED module, refer to the label in the luminaire for the designation of the module. The replacement modules from BEGA have the same light color and light output as the original modules. Only qualified individuals using standard tools should perform the replacement. Disconnect the system and open the luminaire following the LED module installation instructions. Replace any defective luminaire cover and then close the luminaire.
  5. The available spares for this product include a synthetic cover, LED power supply unit, and LED module with a color temperature of 3000 K. The part numbers are 15 000 481 .3 DEV-0159/1050i for the synthetic cover and LED-0694/930 for the LED module.

Instructions for use

BEGA-50216-2-Ceiling-and-Wall-Luminaire-for-Indoor-
Use-1

Application
Ceiling and wall luminaire · indoor luminaire made of impact-resistant synthetic diffuser and aluminium housing. Luminaire with free-radiating and uniform light distribution for linear illumination in interior.

Product Description

  • Luminaire made of aluminium, matt surface finish

  • Light-diffusing synthetic luminaire cover 2 elongated fixing holes

  • Width 5.5mm · 900mm spacing

  • Connection terminal 2.5@

  • Earth conductor connection 2-pole connecting terminal for digital control

  • LED power supply unit 220-240 V x 0/50-60 Hz DC 176-276 V

  • During DC operation the LED power is reduced to 15%

  • DALI-controllable

  • Basic insulation is provided between the mains and control cables
    BEGA Thermal Control®

  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire

  • Safety class I

  • Impact strength IK04

  • Protection against mechanical impacts < 0.5 joule

    • Weight: 2.7 kg
  • This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 34.8 W
  • Luminaire connected wattage 42 W
  • Rated temperature ta=25 °C
  • Ambient temperature ta max=50 °C

50 216.2K3

  • Module designation 4x LED-0694/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 5540 lm
  • Luminaire luminous flux 4760 lm
  • Luminaire luminous efficiency 113,3 lm/W

Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to make sure that the mounting surface is connected conductive to the earth conductor of the luminaire!

Note:
If you a planning a linear arrangement of several luminaires, you must keep a minimum distance of 30mm between the luminaire caps for installation reasons.

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Remove the luminaire from the packaging and put it down so that the open rear side of its housing rests on a soft surface.
  • Undo the lateral Torx countersunk screw T25 and remove the luminaire cap.
  • Make earth conductor connection.
  • Push silicone sleeves over the lines and make electrical connection to the terminals.
  • For digital control please use the connecting terminal DA, DA.
  • In case this terminal is not used the luminaire will be operated at full light output.
  • Drill mounting holes into the mounting surface – spacing 900 mm
  • Secure the luminaire housing to the installation surface with the fixing materials provided or other suitable materials.
  • For wall installation note the position of application “arrow down”.BEGA-50216-2-Ceiling-and-Wall-Luminaire-for-Indoor-Use-2
  • To prevent dirt accumulating on the LED modules, press the supplied plugs into the housing holes of the luminaire profile above the screw-fitting points.
  • Clip the luminaire cover into the groove of the aluminium profile and push it until the stop of the luminaire housing.
  • Replace the housing cap and tighten lateral Torx countersunk screw T25.

Cleaning and Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Defective luminaire cover must be replaced. Close the luminaire.

Spares

  • Synthetic cover 15 000 481 .3
  • LED power supply unit DEV-0159/1050i
  • LED module 3000 K LED-0694/930

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals