Product Information

  • Product Description: The luminaire is made of aluminium alloy with a graphite or white color. It has a matt safety glass and a silicone gasket. The reflector surface is made of pure aluminium. It has an earth conductor connection and an LED power supply unit. The luminaire is DALI-controllable and has basic insulation between the mains and control cables. It has safety class I and protection class IP 65, making it dust-tight and protected against water jets. The luminaire has an impact strength of IK08 and weighs 3.4 kg. It contains light sources of energy efficiency class(es) B, C.
  • Safety: The installation and operation of this luminaire should follow national safety regulations. Only qualified electricians should perform the installation and commissioning. The manufacturer is not liable for damage caused by improper use or installation. Any modifications made to the luminaire are the responsibility of the person making the modifications.
  • Overvoltage Protection: The luminaire’s electronic components are protected against overvoltage according to DIN EN 61547. Additional protection against transients and other events is recommended through separate overvoltage protection components available on the manufacturer’s website.

Product Usage Instructions

  1. Installation:
    • Undo the screws and lift off the luminaire top.
    • Lead the mains supply cable through the cable entry of the luminaire base.
    • Fix the luminaire base onto the mounting surface using the enclosed or suitable fixing material. Ensure to use the gasket rings supplied.
    • Make an earth conductor connection.
    • Push silicone sleeves over the lines and make electrical connections. For digital control, use the connecting terminal DA, DA. If not used, the luminaire will operate at full light output.
  2. Desiccant Pouch:
    • To ensure the maximum service life of the electrical components, place the enclosed desiccant pouch in the luminaire.
    • Remove the desiccant pouch from the foil packaging.
    • Place the desiccant pouch in the position marked by the red information label before finally closing the luminaire.

Dimension

Ceiling luminaire · WallwasherBEGA-24-090-Ceiling-luminaire-Wallwasher-fig
1

Application

  • Ceiling luminaire · Wallwasher
  • With asymmetrical light distribution for soft lighting effects without any harsh light cones on the illuminated wall surface.

Product description

  • Luminaire made of aluminium alloy,
  • aluminium and stainless steel
  • Colour graphite or white
  • Matt safety glass
  • Silicone gasket
  • Reflector surface made of pure aluminium
  • 2 mounting holes ø 6 mm
  • Distance apart 210 mm
  • 2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G 1.5@ Connecting terminal 2.5@
  • with plug connection
  • Earth conductor connection
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 170-276 V
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Protection class IP 65
  • Dust-tight and protection against water jets Impact strength IK08
  • Protection against mechanical
  • impacts < 5 joule
  • – Safety mark
  • – Conformity mark
  • Weight: 3.4 kg
  • This product contains light sources of energy efficiency class(es) B, C

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against
  • e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Installation

  • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Undo the screws and lift off the luminaire top. Lead the mains supply cable through the cable entry of the luminaire base.
  • Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
  • Be sure to use the gasket rings supplied. Make earth conductor connection.
  • Push silicone sleeves over the lines and make electrical connection.
  • For digital control please use the connecting terminal DA, DA.
  • In case this terminal is not used the luminaire will be operated at full light output.
  • In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
  • Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.
  • Make earth conductor connection between luminaire top and luminaire base.
  • Push plug into coupler as far as it will go. Make sure that gasket is positioned correctly. Install the luminaire top, press-on and tighten screws evenly.

Lamp

  • Module connected wattage 36.8 W

  • Luminaire connected wattage 40 W

  • Rated temperature ta = 25 °C

  • Ambient temperature ta max = 40 °C
    24 090 K3

  • Module designation LED-0891/830

  • Colour temperature 3000 K

  • Colour rendering index CRI > 80

  • Module luminous flux 7145 lm

  • Luminaire luminous flux 5379 lm

  • Luminaire luminous efficiency 134,5 lm / W
    24 090 K4

  • Module designation LED-0891/840

  • Colour temperature 4000 K

  • Colour rendering index CRI > 80

  • Module luminous flux 7345 lm

  • Luminaire luminous flux 5529 lm

  • Luminaire luminous efficiency 138,2 lm / W

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits. Do not use high pressure cleaners.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Inspect and, if necessary, replace the luminaire gaskets.
  • Defective glass must be replaced.
  • Close the luminaire.

Spares
LED power supply unit DEV-0391/700
LED module 3000 K LED-0891/830
LED module 4000 K LED-0891/840
Reflector 76 001 793
Gasket 83 001 575

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals