DAA100 Wilo PARA Pump Instruction Manual

June 16, 2024
wilo

DAA100 Wilo PARA Pump
Instruction Manual

DAA100 Wilo PARA Pump

DAA100 Wilo PARA Pump

DAA100 Wilo PARA Pump - fig![DAA100 Wilo PARA Pump

General

About these instructions
These installation and operating instructions are an integral part of the product. Read these instructions before commencing work and keep them in an accessible place at all times.
Strict adherence to these instructions is a requirement for intended use and correctly operating the product. Allspecifications and markings on the product must be observed.
The language of the original operating instructions is German. All other languages of these instructions are translations of the original operating instructions.
CE-Declaration of conformity
This product complies with European directives in terms of design and performance characteristics, as well as to supplementary national requirements. Conformity has been certified with the CE mark. Further information on the declaration of conformity for this product can be found online at https://wilo.com/oem/en/Support/Documentation or requested from the relevant Wilo branch.

Safety

This section contains basic information which must be adhered to during installation, operation and maintenance. Additionally, the instructions and safety instructions in the other sections must be followed. Failure to follow the installation and operating instructions will result in the risk of injury to persons and damage to the environment and the product. This will result in the loss of any claims for damages. Failure to follow the instructions will, for example, result in the following risks:

  • Injury to persons from electrical, mechanical and bac- teriological factors as well as electromagnetic fields
  • Environmental damage from leakage of hazardous substances
  • Property damage
  • Failure of important functions of the product

Identification of safety instructions

These installation and operating instructions set out safety instructions for preventing personal injury and damage to property, which are displayed in different ways:

  • Safety instructions relating to personal injury start with a signal word and are preceded by a corresponding symbol.
  • Safety instructions relating to property damage start with a signal word and are displayed without a symbol.

Signal words
DANGER!
Failure to observe safety instructions will result in serious  injury or death!
WARNING!
Failure to follow instructions can lead to (serious) injury!
CAUTION!
Failure to follow instructions can lead to property damage and possible total loss.
NOTICE
Useful information on handling the product
Symbols These instructions use the following symbols:

| Danger due to electrical voltage
---|---
| General danger symbol
****| Warning of hot surfaces/fluids
| Warning of magnetic fields

Notices
Personnel qualifications
Personnel must:

  • Be instructed about locally applicable regulations governing accident prevention.

  • Have read and understood the installation and operating instructions.
    Personnel must have the following qualifications.

  • Electrical work must be carried out by an authorised electrician (in accordance with EN 50110-1).

  • Installation/dismantling must be carried out by a qualified technician who is trained in the use of the necessary tools and fixation materials.

  • The product must be operated by persons who are instructed on how the complete system functions.

Definition of “qualified electrician”
A qualified electrician is a person with appropriate technical training, knowledge and experience who can identify and prevent electrical hazards.
Electrical work

  • Electrical work must be performed by a qualified electrician.
  • Nationally applicable guidelines, standards and regulations as well as specifications issued by the local energy supply companies for connection to the local power supply system must be observed.
  • Before commencing work, disconnect the product from the mains and safeguard it from being switched on again.
  • The connection must be protected by means of a residual-current device (RCD).
  • The product must be earthed.
  • Have defective cables replaced immediately by a qualified electrician.
  • Never open the control module and never remove operating elements.

Operator responsibilities

  • Have all work carried out by qualified personnel only.
  •  Ensure on-site guard against hot components and electrical hazards.
  • Have defective gaskets and connection pipes replaced.

This device can be used by children from 8 years of age as well as by people with reduced physical, sensory or mental capacities or lack of experience and knowledge if they are supervised or instructed in the safe use of the device and they understand the dangers that can occur. Children are not allowed to play with the device. Cleaning and user maintenance must not be carried out by children without supervision.

Product description and function

Overview
Wilo-Para (Fig. 1)

  1. Pump housing with screwed connections
  2. Glandless motor
  3. Condensate drain openings (4x around circumference)
  4. Housing screws
  5. Control module
  6. Rating plate
  7. Operating button for pump adjustment
  8. Run signal/fault signal LED
  9.  Display of selected control mode
  10.  Display of selected characteristic curve (I, II, III)
  11. PWM or LIN signal cable connection
  12. Mains connection: 3-pin plug connection

Function
High-efficiency circulator for hot-water heating systems with integrated differential pressurecontrol. Control mode and delivery head (differential pressure) are adjustable. The differential pressure is controlled via the pump speed.
Type key
Example: Wilo-Para 15-130/7-50/SC-12/I

Para High-efficiency circulator
15 15 = screwed connection DN 15 (Rp ½) DN 25 (Rp 1), DN 30 (Rp 1¼)
130 Port-to-port length: 130 mm or 180 mm
7 7 = maximum delivery head in m at Q = 0 m³/h
50 50 = max. power consumption in watts

Example: Wilo-Para 15-130/7-50/SC-12/I

SC| SC = Self-Control
iPWM1 = external control via iPWM1 signal
iPWM2 = external control via iPWM2 signal
---|---
12| Position of the control module at 12 o’clock
I| Individual packaging

Technical data

Connection voltage 1 ~ 230 V +10%/-15 %, 50/60 Hz
Protection class IPX4D
Energy efficiency index EEI See rating plate (6)
Fluid temperatures at max. ambient temperature +40 °C -20 °C to +95 °C

(Heating/GT) -10 °C to +110 °C (ST)
Ambient temperature +25 °C| 0 °C to +70 °C
Max. operating pressure| 10 bar (1000 kPa)
Min. inlet pressure at +95 °C/+110 °C| 0.5 bar / 1.0 bar (50 kPa / 100 kPa)

Indicator lights (LEDs)

  • Signal display

  • LED is lit up in green in normal operation

  • LED lights up/flashes in case of a fault (see chapter 10.1)

  • Display of selected control mode Δp-v, Δp-c and constant speed

  • Display of selected pump curve (I, II, III) within the control mode

  • LED indicator combinations during the pump venting function, manual restart and key lock

Operating button

Press

  • Select control mode
  •  Select pump curve (I, II, III) within the control mode

Press and hold

  • Activate the pump venting function (press for 3 seconds)
  •  Activate manual restart (press for 5 seconds)
  •  Lock/unlock button (press for 8 seconds)

3.1 Control modes and functions
Variable differential pressure Δp-v (I, II, III)
Recommended for two-pipe heating systems with radiators to reduce the flow noise at hermostatic valves.

The pump reduces the delivery head to half in the case of decreasing volume flow in the pipe network.
Electrical energy saving by adjusting the delivery head to the volume flow requirement and lower flow rates. There are three pre-defined pump curves (I, II, III) to choose from.
Constant differential pressure Δp-c (I, II, III) Recommended for underfloor heating for large-sized pipes or all applications without a variable pipe network curve (e.g. storage charge pumps), as well as single- pipe heating systems with radiators.
The control keeps the set delivery head constant irrespective of the pumped volume flow.
There are three pre-defined pump curves (I, II, III) to choose from.
Constant speed (I, II, III)

Recommended for systems with fixed system resistance requiring a constant volume flow.
The pump runs in three prescribed fixed speed stages (I, II, III).
NOTICE
Factory setting: Constant speed, pump curve III
External control via iPWM signal
The required setpoint/actual value comparison for control is performed by an external controller.
A PWM signal (pulse-width modulation) is fed as a correcting variable to the pump.  The PWM signal generator gives the pump a periodic sequence of impulses (the duty cycle) in accordance with DIN IEC 60469-1.
iPWM 1 mode (heating application):
In iPWM 1 mode, the pump speed is controlled according to the PWM input signal.
Behaviour in the event of a cable break: If the signal cable is disconnected from the pump, e.g. due to a cable break, the pump accelerates to maximum speed. PWM signal input [%]

< 5: Pump runs at maximum speed
5-85: The speed of the pump decreases linearly from nmax to n min
85-93: Pump runs at minimum speed (operation)
85-88: Pump runs at minimum speed (starting)
93-100: Pump stops (standby)

iPWM 2 mode:
In iPWM 2 mode, the pump speed is controlled according to the PWM input signal.
Behaviour in the event of a cable break: If the signal cable is disconnected from the pump, e.g. due to a cable break, the pump stops. PWM signal input [%]

0-7: Pump stops (standby)
7-15: Pump runs at minimum speed (operation)
12-15: Pump runs at minimum speed (starting)
15-95: The speed of the pump increases linearly from n min to n max
> 95: Pump runs at maximum speed

Venting
The pump venting function is activated by pressing and holding the operating button (for 3 seconds) and automatically vents the pump.
However, this function does not vent the heating system.
Manual restart
A manual restart is initiated by pressing and holding the operating button (for 5 seconds) and unblocks the pump as required (e.g. after a long idle time in the summer).
Lock/unlock the button
The key lock is activated by pressing and holding the operating button (for 8 seconds) and locks the pump’s current settings. It protects against undesired or unauthorised adjustment of the pump.
Activating factory setting
The factory setting is activated by pressing and holding the operating button whilst switching off the pump. When the pump is switched on again, the pump runs using the factory settings (delivery condition).

Intended use

High-efficiency circulators in the Wilo-Para series are exclusively intended for circulating fluids in hot-water heating systems and similar systems with constantly changing volume flows.
Permitted fluids:

  • Heating water according to VDI 2035 (CH: SWKI BT 102-01).

  • Water-glycol mixtures* with a maximum of 50% glycol.

  • Glycol has a higher viscosity than water. If admixtures of glycol are used, the pumping data of the pump must be corrected to match the mixing ratio.
    NOTICE
    Only introduce ready-to-use mixtures to the system. The pump must not be used to mix fluid in the system.
    Intended use includes observing these instructions and the specifications and markings on the pump.
    Misuse Any use beyond the intended use is considered misuse and will void any warranty claims.
    WARNING!
    Danger of injury or material damage from improper use!

    • Never use non-specified fluids.
    • Never allow unauthorised persons to carry out work.
    • Never operate the pump beyond the specified limits of use.
    • Never carry out unauthorised conversions.
    • Use authorised accessories only.
    • Never operate with phase angle control.

Transportation and storage

Scope of delivery

  • High-efficiency circulator
  • Installation and operating instructions

Accessories
Accessories must be ordered separately. For a detailed list and description, consult the catalogue. The following accessories are available:

  • Mains connection cable
  •  iPWM/LIN signal cable
  • Thermal insulation shell
  •  Cooling shell

Transport inspection
Immediately check for transportation damage and completeness upon delivery, and lodge any complaints immediately.
Transport and storage conditions
Protect against moisture, frost and mechanical loads. Permissible temperature range: -40 °C to +85 °C (for max. 3 months)

Installation and electrical connection

6.1 Installation
May only be installed by qualified technicians.
WARNING!
Risk of burns from hot surfaces!
Pump housing (1) and glandless motor (2) may become hot and cause burns if touched.

  • During operation, only touch the control module (5).
  • Allow the pump to cool down before commencing any work.

WARNING!
Risk of scalding from hot fluids!
Hot fluids can cause scalding. Before installing or removing the pump, or loosening the housing screws (4), note the following:

  • Allow the heating system to cool down completely.
  • Close shut-off devices or drain the heating system.

Preparation Installation within a building:

  • Install the pump in a dry, well-ventilated, frost-free room.

Installation outside a building (outdoor installation):

  • Install the pump in a chamber with cover or in a cabinet/housing as weather protection.
  • Avoid exposure of the pump to direct sunlight.
  •  Protect the pump against rain.
  • Keep the motor and electronics continually ventilated to avoid overheating.
  •  The permitted fluid temperatures and ambient tem- peratures should not be exceeded or undershot.
  •  Choose an installation point that is as easily accessible as possible.
  •  Observe the pump’s permitted installation position (Fig. 2).

CAUTION!
An incorrect installation position may damage the pump.

  • Select the installation point in line with the permis- sible installation position (Fig. 2).
  •  The motor must always be installed horizontally.
  •  The electrical connection must never face upwards.
  • Install shut-off devices upstream and downstream of the pump to facilitate pump replacement.

CAUTION!
Leaking water may damage the control module.

  • Align the upper shut-off device so that leaking water cannot drip onto the control module (5).
  •  If the control module is sprayed with liquid, the surface must be dried off.
  • Align the upper shut-off device laterally.
  • When installing in the feed of open systems, the safety supply must branch off upstream of the pump (EN 12828).
  • Complete all welding and brazing work.
  • Flush the pipe system.
  • Do not use the pump to flush the pipe system.

Installing the pump
Observe the following points when installing the pump:

  • Note the direction arrow on the pump housing (1).
  •  Install glandless motor (2) horizontally, without mechanical tension.
  • Place gaskets in the screwed connections.
  • Screw on threaded pipe unions.
  •  Use an open-end wrench to secure the pump against twisting and screw tightly to piping.
  • Re-mount the thermal insulation shell if required.

DAA100 Wilo PARA Pump - Installing the pump CAUTION!
Insufficient heat dissipation and condensation water may damage the control module and the glandless motor.

  • Do not thermally insulate the glandless motor (2).
  • Ensure all condensate drain openings (3) are kept free.

WARNING!
Risk of fatal injury from magnetic field!
Risk of fatal injury for people with medical implants due to permanent magnets installed in the pump.

  • The motor must never be removed.

6.2 Electrical connection
The electrical connection may only be carried out by a qualified electrician.
DANGER!
Risk of fatal injury from electrical voltage!
Immediate risk of fatal injury if live components are touched.

  • Before commencing work, switch off the power sup- ply and secure it from being switched on again.
  • Never open the control module (5) and never remove operating elements.

CAUTION!
Pulsed mains voltage can cause damage to electronic components.

  • Never operate the pump with phase angle control.
  •  For applications where it is not clear whether the pump is operated with pulsed voltage, get the control/system manufacturer to confirm that the pump is operated with sinusoidal AC voltage.
  •  Switching the pump on/off via triacs/solid-state relays must be examined on a case-by-case basis.

Preparation

  • The current type and voltage must correspond to the specifications on the rating plate (6).
  •  Maximum back-up fuse: 10 A, slow-blow.
  •  Only operate the pump with sinusoidal AC voltage.
  •  Note the switching frequency: – On/off switching operations via mains voltage ≤ 100/24 h. – ≤ 20/h for a switching frequency of 1 min. between switching on/off via mains voltage.
  •  The electrical connection must be made via a fixed connecting cable equipped with a connector device or an all-pole switch with a contact opening width of at least 3 mm (VDE 0700/Part 1).
  •  Use a connecting cable with sufficient outer diameter (e.g. H05VV-F3G1.5) to protect against leaking water and to ensure strain relief on the threaded cable connection.
  •  Use a heat-resistant connecting cable where fluid temperatures exceed 90 °C.
  •  Ensure that the connecting cable does not make contact with either the pipes or the pump.

Mains cable connection Installing the mains connection cable (Fig. 3):

  1. Standard: 3-core coated cable with brass ferrules
  2.  Optional: Mains cable with 3-pin connection plug
  3.  Optional: Wilo-Connector cable (Fig. 3, item b)
    • Cable assignment:
    1 yellow/green: PE ( )
    2 blue: N
    3 brown: L
    • Press down the locking button of the 3-pin pump
    plug and connect the plug to the plug connection (12)
    of the control module until it snaps into place (Fig. 4).

Wilo-Connector connection
Installing Wilo-Connector

  • Disconnect the connecting cable from the power supply.
  • Observe terminal assignment ( ; (PE), N, L ).
  • Connect and install the Wilo-Connector (Fig. 5a to 5e). Connecting the pump
  • Earth the pump.
  • Connect the Wilo-Connector to the connection cable until it snaps into place (Fig. 5f). Removing the Wilo-Connector
  • Disconnect the connecting cable from the power supply.
  •  Remove the Wilo-Connector using a suitable screwdriver (Fig. 6).

Connection to an existing device
The pump can be directly connected to an existing pump cable with a 3-pin plug (e.g. Molex) when being replaced (Fig. 3, item a).

  • Disconnect the connecting cable from the power supply.
  • Press down the locking button of the installed plug and remove the plug from the control module.
  •  Observe the terminal assignment (PE, N, L).
  • Connect the existing device plug to the plug connection (12) of the control module.

iPWM/LIN connection
Connecting the iPWM/LIN signal cable (accessories)

  • Connect the signal cable plug to the iPWM/LIN connection (11) until it snaps into place.

iPWM:

  • Cable assignment:
    1 brown: PWM input (from controller)
    2 blue or grey: Signal earth (GND)
    3 black: PWM output (from the pump)

  • Signal properties:
    – Signal frequency: 100 Hz – 5000 Hz (1000 Hz nominal)
    – Signal amplitude: Min. 3.6 V at 3 mA to 24 V for 7.5 mA, absorbed by the pump interface.
    – Signal polarity: yes

LIN:

  • Cable assignment:
    1 brown: 12 V DC to 24 V DC (+/-10 %)
    2 blue or grey: Signal earth (GND)
    3 black: LIN bus data

  • Signal properties:
    – Bus speed: 19200 bit/s

CAUTION!
The connection of mains voltage (230 V AC) to the communication pins (iPWM/LIN) will destroy the product.

  • At the PWM input, the maximum voltage is 24 V pulsed input voltage.

Commissioning

Commissioning only by qualified technicians.

7.1 Venting

DAA100 Wilo PARA Pump - Venting

  • Fill and vent the system correctly.
    If the pump does not vent automatically:

  • Activate the pump venting function via the operating button: press and hold for 3 seconds, then release.
    The pump venting function is initiated and lasts 10 minutes.
     The top and bottom LED rows flash in turn at 1 second intervals.

  • To cancel, press and hold the operating button for 3 seconds.

NOTICE
After venting, the LED display shows the previously set values of the pump.

7.2 Setting the control mode
Select control mode

The LED selection of control modes and corresponding pump curves takes place in clockwise succession.

  • Press the operating button briefly (approx. 1 second).
    LEDs display the set control mode and pump curve.
    The following shows the various possible settings (for example: constant speed / characteristic curve III):

| LED display| Control mode| Pump curve
---|---|---|---
1| | Constant speed| II
2| | Constant speed| I
3| | Variable differential
pressure Δp-v| III
4| | Variable differential
pressure Δp-v| II
5| | Variable differential
pressure Δp-v| I
6| | Constant differential
pressure Δp-c| III
7| | Constant differential
pressure Δp-c| II
8| | Constant differential
pressure Δp-c| I
9| | Constant speed| III

  • Pressing the button for the 9th time returns to the basic setting (constant speed / characteristic curve III).

  • Lock/unlock the button
    To activate the key lock, press and hold the operating button for 8 seconds until the LEDs for the selected setting briefly flash, then release.
    LEDs flash constantly at 1-second intervals.
    The key lock is activated: pump settings can no longer be changed.

  • The key lock is deactivated in the same manner as it is activated.

NOTICE
All settings/displays are retained if the power supply is interrupted.

Activating factory setting
The factory setting is activated by pressing and holding the operating button whilst switching off the pump.

  • Press and hold the operating button for at least 4 seconds.
    All LEDs flash for 1 second.
    The LEDs for the last setting flash for 1 second.
    When the pump is switched on again, the pump runs using the factory settings (delivery condition).

Decommissioning

Shutting down the pump
Shut down the pump immediately if the connecting cable or other electrical components are damaged.

  • Disconnect the pump from the power supply.
  • Contact Wilo customer service or a specialist technician.

Maintenance

Cleaning

  • Carefully remove dirt from the pump on a regular basis using a dry duster.
  • Never use liquids or aggressive cleaning agents.

Installation and operating instructions Wilo-Para

Faults, causes and remedies

The troubleshooting must only be carried out by a qualified specialist, and work on the electrical connection must only be carried out by a qualified electrician.

Faults Causes Remedy
Pump is not running although the power supply is switched on Electrical fuse
defective Check fuses
No voltage supply at pump Rectify the power interruption
Noisy pump Cavitation due to insufficient suction pressure Increase the

system pressure within the permissible range
Check the delivery head and set it to a lower head if necessary
Building does not warm up| Thermal output of the heating surfaces is too low| Increase setpoint
Change the control mode from 4p-c to Δp-v

10.1 Fault signals

  • The fault signal LED indicates a fault.
  • The pump switches off (depending on the fault) and attempts a cyclical restart.
LED Faults Causes 1 Remedy

Lights
up red| Blocking| Rotor blocked| Activate manual restart or contact customer service
Contacting/ winding| Winding defective
Flashes red| Under/overvoltage| Power supply too low/high on mains side| Check mains voltage and operating
conditions, and request customer service
Excessive module temperature| Module interior too warm
Short-circuit| Motor current too high
Flashesred/green| Generator operation| Water is flowing through the pump hydraulics, but there is no mains voltage at the pump| Check the mains voltage, water quantity/pressure and the ambient
conditions
Dry run| Air in the pump
Overload| Sluggish motor, pump is operated outside of its specifications (e.g. high module temperature). The speed is lower than during normal operation

Manual restart

DAA100 Wilo PARA Pump - Manual restart

  • The pump attempts an automatic restart upon detecting a blockage.
    If the pump does not restart automatically:

  • Activate manual restart via the operating button: press and hold for 5 seconds, then release.
    The restart function is initiated, and lasts max. 10 minutes.
    The LEDs flash in succession clockwise.

  • To cancel, press and hold the operating button for 5 seconds.

NOTICE
After the restart, the LED display shows the previously set values of the pump.
If the fault cannot be remedied, contact a specialist technician or Wilo customer service.

Disposal

Information on the collection of used electrical and electronic products
Proper disposal and appropriate recycling of this product prevents damage to the environment and danger to your personal health.

NOTICE
Disposal in domestic waste is forbidden!
In the European Union, this symbol can appear on the product, the packaging or the accompa nying documentation.
It means that the electrical and electronic products in question must not be disposed of along with domestic waste.
To ensure proper handling, recycling and disposal of the used products in question, please note the following points:

  • Only hand over these products at designated, certified collecting points.
  • Observe the locally applicable regulations!
    Please consult your local municipality, the nearest waste disposal site, or the dealer who sold the product to you for information on proper disposal. Further recycling information at www.wilo-recycling.com

Local contact at www.wilo.com/contact
WILO SE, Wilopark 1
D-44263 Dortmund, Germany
T +49(0)231 4102-0
F +49(0)231 4102-7363
wilo@wilo.com
www.wilo.com
Pioneering for You

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals