BEGA 50146.5 Wall Washer for Indo **or Use Instruction Manual
**
Instructions for use
Application
Wall washer · indoor luminaire for the glare free illumination of wall surfaces with the mounting surface being the reflection surface. The light emits upwards and downwards.
Product description
Die-cast aluminium and aluminium housing, finish Colour velvet black Crystal
glass, inside matt Reflector made of pure anodised aluminium 2 mounting holes
ø 4.8mm Distance apart 200 x 65mm 2 cable entries for through-wiring of mains
supply cable ø 7-10.5mm, max. 5G1.5@ Connection terminal 2.5@ Earth conductor
connection 2-pole connecting terminal for digital control LED power supply
unit 220-240 V x 0/50-60 Hz DC 176-264 V DALI-controllable
Basic insulation is provided between the mains and control cables BEGA Thermal
Switch®
Temporary thermal shutdown to protect temperature-sensitive components Safety
class I Impact strength IK07
Protection against mechanical impacts < 2 joule
Safety mark
Conformity mark
Weight: 2.0 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend
separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 24.6 W |
---|---|
Luminaire connected wattage | 28.4 W |
Rated temperature | ta=25 °C |
Ambient temperature | ta max=25 °C |
50 146.5K3
Module designation | 2x LED-0696/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI >90 |
Module luminous flux | 3620 lm |
Luminaire luminous flux | 2571 lm |
Luminaire luminous efficiency | 90,5 lm/W |
50 146.5K4
Module designation | 2x LED-0696/940 |
---|---|
Colour temperature | 4000 K |
Colour rendering index | CRI >90 |
Module luminous flux | 3770 lm |
Luminaire luminous flux | 2678 lm |
Luminaire luminous efficiency | 94,3 lm/W |
Installation
LED are high-quality electronic components! Please avoid touching the light
output opening of the LED directly during installation or relamping.
Undo screws and lift off luminaire top.
Loosen earth connection (plug connection) and
LED-connection between luminaire top and luminaire base.
Lead the mains supply cable through the cable entry of the luminaire base.
Note position of application of the luminaire “arrow down”.
Fix luminaire base with enclosed or any other suitable fixing material onto
the mounting surface.
Be sure to use the gasket rings supplied.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Make earth connection (plug connection) and LED-connection between luminaire
top and luminaire base again.
Install luminaire top part, adjust it and tighten screws evenly
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The replacement can be carried out by
a qualified person using standard tools.
Disconnect the system and open the luminaire. Uninstall the reflector.
Please follow the installation instructions for the LED module.
Install the reflector. Defective glass must be replaced. Close the luminaire.
Replacement of the glass
Undo screws and lift off luminaire top.
Loosen earth connection (plug connection) and LED-connection between luminaire
top and luminaire base.
Loosen reflector screws, separate earth connection and remove reflector.
Loosen screws of the glass retaining springs and remove glass retaining
springs from the luminaire top.
Remove damaged glass. Insert replacement glass.
Reinstall glass retaining springs and tighten screws on both sides.
Insert reflector into luminaire top part, makeearth connection to reflector
and tighten reflector screws (0,6 Nm).
Make earth connection (plug connection) and
LED-connection between luminaire top and luminaire base again.
Install luminaire top part, adjust it and tighten screws evenly
Spares
LED power supply unit DEV-0388/700
LED module 3000 K LED-0696/930
LED module 4000 K LED-0696/940
Reflector 76 001 510
BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com