autani SMT-131 Wireless Digital Thermostat Installation Guide
- June 11, 2024
- autani
Table of Contents
SMT-131 Wireless Thermostat
Quick Installation Sheet
On the provided list of device serial numbers, document the location for each Thermostat.
Opening Wall Controller
Open the SMT-131 wall controller by placing a flat blade screwdriver or coin in the slot on the bottom of the thermostat case and gently twist to release the case locking clip. Gently pry the two case halves apart at the base taking care not to twist the case as this may crack the LCD.
Mounting wall Controller
The SMT-131 should be mounted in a convenient location at approximately 1.2 to
1.5 meters from the ground. It should be located in a “typical” location where
it will sense the accurate room temperature and not be affected by direct
sunlight or drafts.
It is highly recommended that any penetrations in the wall where wiring may
pass for example be sealed to prevent drafts from entering the rear of the
thermostat and effecting the room temperature sensor accuracy. Take care to
ensure excess wiring is not trapped between the cases half’s when closing –
push excess wires into the wall cavity. Never press on the LCD when closing
the SMT-131 as it may crack. Always press on the SMT-131 plastic case only.
DIP Switch Settings
Switch | Function | ON | OFF |
---|---|---|---|
Sw1 | Indoor Fan | ||
Mode | 3 Fan | ||
Speed | 1 Fan Speed | ||
Sw2 | Equipment | Heat Pump | Heat Cool |
Sw3 | HP Mode |
(5w2= ON)
HC Mode
(Sw2=OFF)| Rev Valve
Heat (B)
HE — Fan
With Heat| Rev Valve
Cool (0)
HG — No Fan
In Heat
Sw4| 2/4 pipe
mode| 2 pipe
mode| 4 pipe Mode
Sw5| Comp
Protection
Delay| 5 Min Anti
Cycle| Immediate
Comp start
Sw6| Klixon
(Ricardo)
Mode| On| Off
Sw7| Ventilation
Mode| Permitted| Not
Permitted
Sw8| Door Station
(Optional)| Fitted| Door Station
Not Used
NOTES: The SMT-131 reads the switch settings on power up only. If you
change any DIP switch settings you must power cycle before these changes will
take effect.
It is expected that only qualified people will make adjustment to these dip
switch settings. Knowledge of the HVAC system under the control of the SMT131
is essential prior to making adjustment to these DIP switch settings.
CAUTION: Incorrect adjustment of these DIP switch settings could cause
HVAC equipment damage. This would NOT be covered by warranty.
Wiring – HVAC Control
Terminal Designations
Terminal | Function |
---|---|
C | 24V Neutral |
R | 24V Active – This voltage is switched back through the relays |
Hi | Indoor Fan High Speed (NOT Used in Single fan speed mode – Swl = OFF) |
Med | Indoor Fan Medium Speed (NOT Used in Single fan speed mode – Swl = OFF) |
Low | Indoor Fan Low Speed (Used in single & three fan speed mode) |
Y | Compressor or Cool-(Based on Sw2 setting) |
W-0/B | Reversing Valve or Heat- (Based on Sw2 setting) |
Al-Cool | 0-10V Output for Cooling (Typically used to control modulating |
valves)
A2-Heat| 0-10V Output for Heating (Typically used to control modulating
valves)
A3-Fan| 0-10V Modulating Output for Indoor DC Fan
Com – OV| OV terminal – Used for o-ny, sensor or inputs nputs ground reference
A| Modbus Data A
B| Modbus Data B
SI| Remote temperature sensor input
(Remote/average/Modbus data use)
DI| Digital (Switched input) for forced
un-occupied or initiate doorbell function
WC| Window Contact – Forces SMT-131 OFF if window open > 5 min (Adjustable)
DS| Door Switch — Monitors room door status for occupancy detection
PIR| PIR (Movement sensor) input for
occupancy detection
The SMT-131 is powered by 24VAC and requires the 24VAC active and neutral to be connected to the “R” (active) and “C” (Neutral) terminals for the SMT-131 to function. The 24VAC applied to the SMT-131 “R” terminal is switch back through the 2A relays to the equipment. Note the drawing provided here.
CAUTION – Although the SMT-131 is a robust device, wiring errors can
potentially damage the thermostat. Warranty does NOT cover this damage.
Take care when wiring 24V near sensor inputs or the Modbus communications
terminals.
NOTE : When the SMT-131 calls heating or cooling the SMT-131 will drive both
the relays and the 0-10V outputs simultaneously. This way the SMT-131 can all
a circulating water pump via the relays as it controls room temperature with
valves if needed.
Heat Cool – 1 Fan Speed
0-10 v Heat & Cool Valve – 3 Fan Speed
0-10v Outputs
To permit the control of modulating heating and cooling valves as well as
variable speed DC fan motors or variable capacity HVAC systems the SMT-131 has
been fitted with 3×0-10V outputs.
The 0-10V outputs in the SMT-131 are PI(Proportional Integral) controlled.
This control method provides the most accurate and cost effective way to
control
heating and cooling valves by ensuring set temperate are reached as quickly
and efficiently as possible while reducing temperature overshoot.
As the SMT-131 is fitted with both relays as well as 0-10V outputs to control
HVAC systems there may be some slight disparity between the thermostat display
and the 0-10V outputs actions. The SMT-131 displays the relay actions more
than the actions of the 0-10V outputs on the LCD. In most cases these are very
closely matched however as the 0-10v outputs have the capability of providing
finer control than do the ON/OFF relays the heating and cooling calls may have
started slightly before indicated on the thermostat display. This is true of
the fan also.
A1 – Cool : This output is used to control a cooling valve.
A2 – Heat : This output is used to control a heating valve.
A3 – Fan : This output is used to control a variable speed fan or a variable
capacity AC system. If the fan mode is set to Auto speed the 0-10V output will
vary between these two values based on calculated demand. If the user selects
LOW speed, the 0-10V output will be fixed at 3.3VDC, when Medium speed is
selected the 0-10V output will be fixed at 6.6VDC. High speed is set to 10VDC
The installer menu provides the following settings for the control of the
three 0-10V outputs.
Span
This is the value where the output is at maximum value.
It sets how aggressive the 0-10V will move for a given temperature change.
Range is 0-5C
Time Interval
Time interval sets the running average calculation time.
The smaller the number the faster the 0-10V output will respond to room
temperature changes. Range is 10–300 seconds.
Direction
Forward action 0V=0% open and 10V=100% open; reverse action sets 0V=100% open
and 10V=0% open.
Minimum Value
Rather than start the output at 0V, when the output is called it will
immediately jump to this value. It will then vary the output to maximum. When
approaching set point the value will drop from the minimum value to 0V in 1
step. This setting is particularly useful for fan control as it will not
permit the fan to run too slowly when close to set point.
Maximum Value (Fan A3) output only
When controlling 0-10V fans sometimes it is necessary to limit the fan speed
to reduce noise or to protect ducting. The fan output has a high voltage limit
setting so regardless of the user selected speed (High, Medium or Low) or
thermostat selected auto speed the 0-10V output will not exceed this pre-set
high limit.
These settings can be found in the installer menu.
Belimo™ 6 Way Valve
Belimo™ manufactures an actuator that is in full cooling at 2V, off at 6V and full heating at 10V. To use this type of actuator with the Smart Temp SMT-131 you must enter the installer menu and set valve type to “Belimo™ Mode”. The heating 0-10v output only is used in this mode.
As with normal valves, the 0-10V heating and cooling span settings in the
installer menu scale the heating and cooling outputs. Factory default is full
heating and full cooling 1°C from set point. The heating and cooling span can
be adjusted independently to a maximum of full heating and full cooling 3°C
from set point. The output is linear.
NOTE: When using “Belimo™” mode, both the A1 “cool” and the A2 “Heat”
0-10 output are used. Both will provide the same output to the value. (The A3
“fan” output will remain unchanged and can be used to control a DC fan or
other devices).
2 Pipe Mode
The SMT-131 can measure water temperature via a sensor strapped to the water
pipe and wired into the SMT-131 Sensor input terminals (SI and Com 0-10
input). Based on the pipe temperature, the room temperature and the set point
the SMT-131 will control either the heating or the cooling outputs to maintain
guest comfort.
When 2 pipe is mode is used, the SMT-131 will occasionally open the water
valve to allow water flow within the pipe so the SMT-131 can sample pipe
temperature to determine / confirm operation mode.
If mode selection is permitted, the SMT-131 will only permit the appropriate
mode to be selected based on the pipe temperature.
To use the SMT-131 in 2 pipe mode set DIP 2 OFF and DIP 4 to the ON position.
Set Installer menu option 26 “SI & Com 0-V” to option “3”–2 Pipe Mode.
The pipe sensor needed for 2 pipe mode is the RS-1d sensor – available as an
optional part from Smart Temp or an authorised distributor.
Serial Number Information and Tracking
The serial number or ID of a device is used to track device installation
locations and details for the commissioning process. The identification
information for each device should be tracked in a meaningful way, many
devices include duplicate ‘stickers’ with this information. Autani provides an
iOS app to assist with the process.
https://apps.apple.com/us/app/autani-commissioning/id1493796455
For help getting starting with the iOS Commissioning App please see Autani’s User Guide for the iOS Commissioning App.
https://autani.zendesk.com/hc/en-us/articles/4402408987917-Autani- Commissioning-App-User-Guide
Once commissioning details are collected, either through the iOS Commissioning
App, or by tracking identifiers on drawings/spreadsheets.
Please provide this information to
support@autani.com to begin the commissioning
process.
Autani, LLC 7090 Columbia Gateway Drive, Suite 140 Columbia, MD 21046
USA 443-320-2233
www.autani.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>