BEGA 51 012.4 Ceiling Luminaire for Indoor Use Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 51 012.4 Ceiling Luminaire for Indoor Use Instruction Manual
Instructions for use
Application
Ceiling luminaire · indoor luminaire impact resistant synthetic diffuser and
metal housing for non-glare light deflected downwards.
Product description
Ceiling luminaire »STUDIO LINE« Luminaire housing made of aluminium, surface
Colour velvet black inside hue matt brass Metal luminaire mounting plate,
finish Colour velvet black Impact resistant synthetic diffuser, white, with
bayonet closure 2 mounting holes ø 5.5mm Distance apart 180mm 2 cable entries
for through-wiring for mains cable up to ø 10.5 mm max. 3 × 1.5@ Connection
terminal 2.5@ Earth conductor connection LED power supply unit 220-240 V y
50-60 Hz BEGA Thermal Switch® Temporary thermal shutdown to protect
temperature-sensitive components Safety class I Impact strength IK10
Protection against mechanical impacts < 20 joule – Safety mark c – Conformity
mark
Weight: 1.6 kg This product contains light sources of energy efficiency
class(es) D
Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp
Module connected wattage : 11.6 W
Luminaire connected wattage: 15.5 W
Rated temperature: ta=25 °C
Ambient temperature: ta max=45 °C
51 012.4K3
Colour temperature : 3000 K
Colour rendering index: CRI >90
Module luminous flux: 1725 lm
Luminaire luminous flux : 961 lm
Luminaire luminous efficiency: 62 lm/W
Installation
LED are high-quality electronic components! Please avoid touching the light
output opening of the LED directly during installation or relamping.
Before installing onto the ceiling the luminaire mounting plate must be
inserted into the luminaire housing. Thereby pass the mains supply cable
through the grommet into luminaire mounting plate. Fix monting plate inside
the luminaire housing with enclosed or any other suitable fixing material on
to the mounting surface. Dismantle the mains supply cable approx. 60 mm. Pull
silicone sleeves over the wires and make earth and electrical connection to
the terminals.
In order to securely install the synthetic cover in the fitting, the top opening of the synthetic cover must be inserted into the luminaire housing at an angle. Make sure that at least one of the recesses in the edge of the synthetic cover matches the position of one of the lugs on the fitting – see drawing
IMPORTANT:
Turn the synthetic cover upwards into the fitting as far as it will go. Now
secure the synthetic cover in the fitting by turning it clockwise.
Only then is the synthetic cover held securely in place and resistant to
vibration.
The synthetic cover is removed by turning it anti-clockwise as far as it will go while simultaneously pushing the synthetic cover up against the luminaire fitting.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacement of the LED unit
The designation of the LED unit is noted on a label in the luminaire. The
light colour and light output of BEGA replacement units correspond to those of
the LED units originally fitted. The LED unit can be replaced by qualified
persons using standard tools. Disconnect from main supply. Unscrew synthetic
diffuser from luminaire housing by turning it counter-clockwise. Disassemble
LED unit. Assemble LED replacement unit. Note installation instructions of the
LED unit. Screw in synthetic diffuser by turning it clockwise. A damaged
synthetic diffuser must be replaced.