PPI UniLog Universal Process Data Recorder Pen-Drive User Manual
- June 11, 2024
- PPI
Table of Contents
UniLog Universal Process Data Recorder Pen-Drive
UniLog / UniLog Plus with CIM
Universal Process Data Recorder Pen-Drive Version
OPERATOR PARAMETERS
Parameters
Settings (Default Value)
Select Option for Operation on Pen Drive
Select Option>> None
None Copy (New) Re-copy (Old) Read Chan Names Recover
(Default : None)
`Start’ Command for Batch Recording (Available if Batch Recording is selected)
BATCH START>> NO
No Yes
(Default : No)
`Stop’ Command for Batch Recording (Available if Batch Recording is selected)
BATCH STOP>> NO
No Yes
(Default : No)
SUPERVISORY CONFIGURATION
Boiler Temp. 91 C
MAIN Display Mode
SELECT PAGE>> Spvr. Config
Select Supervisory Configuration
SELECT PAGE>> or Operator Page
First Available Page Header
ENTER PASSCODE>> or 0
Passcode Screen
ENTER PASSCODE>> 22
Set Passcode 22
SELECT PAGE>> or Device Config
First Supervisory Page Header
SELECT PAGE>> Alarm Config
Desired Supervisory Page Header
ALARMS / CHAN>> or 4
First Alarms Config Parameter
Note: AII the other Parameters are under SUPERVISORY CONFIGURATION
ALARM SETTING
Parameters
Settings (Default Value)
Channel Name for Alarm Settings
SELECT CHANNEL>> Channel-1
User defined or default names for channel-1 to channel-8 / 16
(Default : NA)
Select Alarm SELECT ALARM>>
AL1
Alarm Type AL1 TYPE>>
None
Alarm Setpoint AL1 SETPOINT>>
0
AL1, AL2, AL3, AL4 (The actual available options depends on the numbers of
Alarms set per channel on Alarm configuration page)
None Process Low Process High (Default : None)
Min. to Max. of selected input type range (Default : 0)
Alarm Hysteresis
AL1 HYSTERESIS>> 2
1 to 3000 or 0.1 to 3000.0 (Default : 2 or 2.0)
Alarm Inhibit
AL1 INHIBIT>> Yes
No Yes
(Default : No)
DEVICE CONFIGURATION
Parameters
Settings (Default Value)
Channel Update Time in Auto Scan Mode SCAN RATE>>
3
1 Sec. to 99 Sec. (Default : 3 Sec.)
Device Identification Number
RECORDER ID>> 2
1 to127 (Default : 1)
Select Total Numbers of Channels
TOTAL CHANNELS>> 16
8 16
(Default : 16)
Erase All Stored Records
DELETE RECORDS>> No
No Yes
(Default : No)
CHANNEL CONFIGURATION
Parameters
Settings (Default Value)
Select Channel Name
SELECT CHANNEL>> Channel-1
User defined or default names for channel-1 to channel – 8 / 16
(Default : NA)
Skip Channel for Display
SKIP>> No
No Yes
(Default : Yes)
Signal Input Type INPUT TYPE>>
Type K (Cr-Al)
Display Resolution for Measured PV RESOLUTION>>
0.1 Unit
Display Units for Measured PV UNITS>>
°C
Refer Table 2 (Default : Type K (Cr-Al))
1 Unit 0.1 Unit 0.01 Unit 0.001 Unit (Default : 0.1 Unit) (* for 4-20mA)
Refer Table 1 (Default : °C)
Range Low (for 4-20mA)
RANGE LOW>> 0
-19999 to 30000 Counts with Selected Resolution
(Default : 0.0)
Range High (for 4-20mA)
RANGE HIGH>> 1000
-19999 to 30000 Counts with Selected Resolution
(Default : 100.0)
Apply Lower Clip on Displayed PV (for 4-20mA)
LOW CLIPPING>> Disable
Disable Enable
(Default : Disable)
Preset Lower Clip Level (for 4-20mA)
LOW CLIP VAL>> 0.0
Apply Upper Clip on Displayed PV (for 4-20mA)
HIGH CLIPPING>> Disable
Preset Upper Clip Level (for 4-20mA) HIGH CLIP VAL>>
100.0
-19999 to 30000 (Default : 0)
Disable Enable (Default : Disable)
-19999 to 30000 (Default : 100.0)
Zero Offset
ZERO OFFSET>> 0
-1999 / 3000 or -1999.9 / 3000.0
(Default : 0)
User – Linearisation
LINEARISATION>> Disable
Disable Enable
(Default : Disable)
Total Break – Points
BREAK POINTS>> 2
2 to 32 (Default : 2)
Operation Manual
This brief manual is primarily meant for quick reference to wiring connections
and parameter searching. For more details on operation and application; please
log on to www.ppiindia.net
Parameters
Select Break – Point Number for Setting SELECT POINT>>
1
X Co-ordinate Value X-VALUE>>
0
Y Co-ordinate Value Y-VALUE>>
0
Settings (Default Value)
1 to Set Numbers of Break-points (Default : NA)
-19999 to 30000 (Default : 0)
-19999 to 30000 (Default : 0)
ALARM CONFIGURATION
Parameters
Settings (Default Value)
Alarms Per Channel
ALARMS / CHAN >> 4
1 to 4 (Default : 4)
Relay-1 Logic
RELAY-1 LOGIC >> Normal
Normal Reverse
(Default : Normal)
Relay-2 Logic
RELAY-2 LOGIC >> Normal
Normal Reverse
(Default : Normal)
RECORDER CONFIGURATION
Parameters
Settings (Default Value)
Normal Recording Interval
NORMAL INTERVAL>> 0:00:30
0:00:00 (H:MM:SS) to
2:30:00 (H:MM:SS)
(Default : 0:00:30)
Zoom Recording Interval
ZOOM INTERVAL>> 0:00:01
0:00:00 (H:MM:SS) to
2:30:00 (H:MM:SS)
(Default : 0:00:01)
Record Generation on Alarm Status Toggle
ALARM TOGGLE REC>> Disable
Disable Enable
(Default : Enable)
Select Recording Mode
RECORDING MODE>> Continuous
Time Interval for Batch Recording (for Batch mode only)
BATCH TIME>> 1.00
Continuous Batch
(Default : Continuous)
0:01 (HH:MM) to
250:00 (HHH:MM) (Default : 1:00)
RTC SETTING
Parameters
Settings
Set Clock Time (HH:MM)
TIME (HH:MM)>> 15:53
0.0 to 23:59
Set Calendar Date
DATE>> 23
1 to 31
Set Calendar Month
MONTH>> 11
1 to 12
Set Calendar Year
YEAR>>
2011
2000 to 2099
UTILITIES
Parameters
Settings
Master Lock Enable Disable
LOCK>>
No
No
Yes
UNLOCK>> No
UTILITIES
Parameters
Settings
UIM Default
No
UIM DEFAULT>> No
Yes
CIM Default
CIM DEFAULT>> No
No Yes
*Set Device Id
No
SET DEVICE ID>> 1
Yes
Make CIM & UIM Compatible
CPY CIM TO UIM>> No
No
Yes
CPY UIM TO CIM>>
No
- For UniLog Plus Only
Option °C °F
(none) °K EU % Pa Mpa kPa bar
mbar psi
kg/sq.cm mmH2O inH2O mmHg
Torr litre/hr litre/min %RH %O2 %CO2 %CP
V A mA mV ohm ppm rpm
mSec Sec min hrs PH %PH miles/hr mg
g kg
TABLE- 1 Description
Degree Centigrade Degree Fahrenheit No Unit (Blank) Degree Kelvin Engineering
Units Percentage Pascals Mpascals Kpascals Bar Milli bar PSI kg/cm2 mm water
gauge Inches water gauge mm mercury
Torr Litres per hour Litres per minute % Relative Humidity % Oxygen % Carbon
di-oxide % Carbon Potential Volts Amps Milli Amps
Milli Volts Ohms Parts per million Revolutions per minute Milli seconds
Seconds Minutes Hours PH %PH Miles per hour Milli grams
Grams Kilo grams
Option
TABLE- 2 Range (Min. to Max.)
Resolution
J Type T/C
0 to +960°C / +32 to +1760°F
-200 to +1376°C / -328 to +2508°F K Type T/C
T Type T/C
-200 to +385°C / -328 to +728°F
0 to +1771°C / +32.0 to +3219°F R Type T/C
0 to +1768°C / +32 to +3214°F S Type T/C
Fixed 1°C / 1°F
0 to +1826°C / +32.0 to +3218°F B Type T/C
0 to +1314.0°C / +32 to +2397.0°F N Type T/C
Reserved for customer specific Thermocouple type not listed above.
RTD Pt100
-199 to +600°C / -328 to +1112°F or
-199.9 to 600.0°C / -328.0 to 1112.0°F
User settable 1°C / 1°F or
0.1°C / 0.1°F
0 to 20mA DC
4 to 20mA DC
0 to 50mV DC
0 to 200mV DC 0 to 1.25V DC
-19999 to +30000 units
User settable 1 / 0.1 / 0.01/ 0.001 units
0 to 5.0V DC
0 to 10.0V DC
1 to 5.0V DC
Assign Channel Name
Instrument Name
File Name
Channel Name
101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401
210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E:
sales@ppiindia.net, support@ppiindia.net
ID SETTING FOR MORE THAN 1 CIM Applicable only for UNILOG PLUS
Operator Setting Alarm Setting
Supervisory Configuration Device Configuration Delete Records Scan Rate
Recorder ID Total Device
Select 2 by pressing UP arrow
Select Device (1) Total Channels (8 Or 16)
Device ID Set 1 for 1st CIM Select Device (2) Total Channels (8 Or 16)
Device ID Set 2 for 2nd CIM
Jan 2022
FRONT PANEL LAYOUT
2 X 16 LCD Display Upper Row
Pen Drive Slot PAGE Key
DOWN Key
Front Panel
PPI
UniLog
SELECT PAGE>> ALARM CONFIG
AUTO
Lower Row
LED Indicator ENTER Key UP Key
Symbol Key
Keys Operation Function
PAGE Press to enter or exit set-up mode.
Press to decrease the parameter value. Pressing once DOWN decreases the value
by one count; holding pressed
speeds up the change.
Press to increase the parameter value. Pressing once
UP
increases the value by one count; holding pressed speeds
up the change.
ENTER
Press to store the set parameter value and to scroll to the next parameter on the PAGE.
PV Error Indications
Error Message
Cause
Over Range
Process Value above Max. Range
Under Range
Process Value below Min. Range
Sensor Open
Thermocouple / RTD broken
Com. Fail
Communication Link with CIM broken
ELECTRICAL CONNECTIONS
USER INTERFACE MODULE (UIM)
Batch Start Alarm ACK
Switch
Switch
Comm Port
Device
RS485
B-
B+
123456789
UniLog / UniLog Plus
10 11 12 13 14 15 16 17 18
L
N
85~265 V
AC SUPPLY
NO
C
RLY
Alarm-1
Alarm-3
NO
C
RLY
Alarm-2
Alarm-4
JUMPER SETTINGS
INPUT-CHANNEL INTERFACE MODULE (CIM)
Old Version
Jumper Pins Channel-1
Jumper Pins Channel-8
21 4 3
Jumper Pins Channel-9
Pins
Shorting Link
Shorting Link Placed
Shorting Link Parked
Jumper Pins Channel-16
4 1
2 3
RTD Sensor
Pt100 (3-wire)
Place Shorting Link on Pins 1 & 2
321
4
Thermocouples
J, K, T, R, S, B, N Types
Place Shorting Link on Pins 2 & 4
321 4
DC Current
0-20mA, 4-20mA
Place Shorting Link on Pins 2 & 3
321
4
DC Voltage
0-50mV, 0-200mV, 0-1.25V, 0-5V, 1-5V, 0-10V
321
Park Shorting Link
4
COMMUNICATION PORT FOR INTERFACING WITH CIM(S) Applicable only for UNILOG PLUS
CIM – 2 COMM PORT 55 54 53 52
CIM – 1 COMM PORT 55 54 53 52
To Next CIM
UIM Comm Port
Device
RS485
89
ELECTRICAL CONNECTIONS
CHANNEL INTERFACE MODULE (CIM)
Old Version
COMM PORT 55 54 53 52
1A
INPUT-1 2 B
3C 4A
INPUT-2 5 B
6C 7A
INPUT-3 8 B
9C 10 A
INPUT-4 11 B
12 C 13 A
INPUT-5 14 B
15 C 16 A
INPUT-6 17 B
18 C
19 A
INPUT-7 20 B
21 C
22 A
INPUT-8 23 B
24 C
25
SUPPLY 26 L VOLTAGE 27 N
AI – X ABC A B C RTD A B C TC A B C mA/mV/V
CIM – 8 / CIM – 16
A 28 B 29 C 30 A 31 B 32 C 33 A 34 B 35 C 36 A 37 B 38 C 39 A 40 B 41 C 42 A 43 B 44 C 45 A 46 B 47 C 48 A 49 B 50 C 51
INPUT-9 INPUT-10 INPUT-11 INPUT-12 INPUT-13 INPUT-14 INPUT-15 INPUT-16
JUMPER SETTINGS
INPUT-CHANNEL INTERFACE MODULE (CIM)
New Version 1 2
Jumper Pins Channel-1
Jumper Pins Channel-9
DIP Switch for Configuration
Mode
Jumper Pins Channel-8
Mode IndicatorLED
ON 12 ON 12
Jumper Pins Channel-16
1 2
Switch Position
Right
Left
Mode Indicator LED
OFF
ON
Operation Mode Communication Parameter Values
Normal
Configuration
User Set values for Module Slave ID, Baud Rate & Parity
Module Slave ID : 1 Baud Rate : 9600 Parity : Even
Pins
Shorting Shorting Link
Link
Placed
Shorting Link Parked
RTD Sensor
Pt100 (3-wire)
Thermocouples
J, K, T, R, S, B, N Types
DC Voltage
0-50mV, 0-200mV 0-1.25V, 0-5V, 1-5V, 0-10V
21 Park Shorting Link
DC Current
0-20mA, 4-20mA
21 Place Shorting Link on Pins 1 & 2
ELECTRICAL CONNECTIONS
CHANNEL INTERFACE MODULE (CIM)
New Version
55 54 53 52 BBBB
COMM PORT
DC Lin : mV / V / mA Config
Normal Operation
Mode Configuration
Mode
UniLog 8 / 16 Channel Interface Module
Sr. No.: Comm. ID:
DC Lin T/C RTD
51 50 49 INPUT-16
DC Lin T/C RTD
48 47 46 INPUT-15
DC Lin T/C RTD
45 44 43 INPUT-14
DC Lin T/C RTD
42 41 40 INPUT-13
DC Lin T/C RTD
39 38 37 INPUT-12
DC Lin T/C RTD
36 35 34 INPUT-11
DC Lin T/C RTD
33 32 31 INPUT-10
DC Lin T/C RTD
30 29 28 INPUT-9
ON 12
CONFIG
12
12
ON
ON
DC Lin T/C RTD
123 INPUT-1
DC Lin T/C RTD
456 INPUT-2
DC Lin T/C RTD
789 INPUT-3
DC Lin T/C RTD
10 11 12 INPUT-4
DC Lin T/C RTD
13 14 15 INPUT-5
DC Lin T/C RTD
16 17 18 INPUT-6
DC Lin T/C RTD
19 20 21 INPUT-7
DC Lin T/C RTD
22 23 24 INPUT-8
84 ~ 264 VAC