PPI UniLog Universal Process Data Recorder Pen-Drive User Manual

June 11, 2024
PPI

UniLog Universal Process Data Recorder Pen-Drive

UniLog / UniLog Plus with CIM
Universal Process Data Recorder Pen-Drive Version

OPERATOR PARAMETERS

Parameters

Settings (Default Value)

Select Option for Operation on Pen Drive
Select Option>> None

None Copy (New) Re-copy (Old) Read Chan Names Recover
(Default : None)

`Start’ Command for Batch Recording (Available if Batch Recording is selected)
BATCH START>> NO

No Yes
(Default : No)

`Stop’ Command for Batch Recording (Available if Batch Recording is selected)
BATCH STOP>> NO

No Yes
(Default : No)

SUPERVISORY CONFIGURATION

Boiler Temp. 91 C
MAIN Display Mode
SELECT PAGE>> Spvr. Config
Select Supervisory Configuration

SELECT PAGE>> or Operator Page
First Available Page Header
ENTER PASSCODE>> or 0
Passcode Screen

ENTER PASSCODE>> 22
Set Passcode 22

SELECT PAGE>> or Device Config
First Supervisory Page Header

SELECT PAGE>> Alarm Config
Desired Supervisory Page Header

ALARMS / CHAN>> or 4
First Alarms Config Parameter

Note: AII the other Parameters are under SUPERVISORY CONFIGURATION

ALARM SETTING

Parameters

Settings (Default Value)

Channel Name for Alarm Settings
SELECT CHANNEL>> Channel-1

User defined or default names for channel-1 to channel-8 / 16
(Default : NA)

Select Alarm SELECT ALARM>>
AL1
Alarm Type AL1 TYPE>>
None
Alarm Setpoint AL1 SETPOINT>>
0

AL1, AL2, AL3, AL4 (The actual available options depends on the numbers of Alarms set per channel on Alarm configuration page)
None Process Low Process High (Default : None)
Min. to Max. of selected input type range (Default : 0)

Alarm Hysteresis
AL1 HYSTERESIS>> 2

1 to 3000 or 0.1 to 3000.0 (Default : 2 or 2.0)

Alarm Inhibit
AL1 INHIBIT>> Yes

No Yes
(Default : No)

DEVICE CONFIGURATION

Parameters

Settings (Default Value)

Channel Update Time in Auto Scan Mode SCAN RATE>>
3

1 Sec. to 99 Sec. (Default : 3 Sec.)

Device Identification Number
RECORDER ID>> 2

1 to127 (Default : 1)

Select Total Numbers of Channels
TOTAL CHANNELS>> 16

8 16
(Default : 16)

Erase All Stored Records
DELETE RECORDS>> No

No Yes
(Default : No)

CHANNEL CONFIGURATION

Parameters

Settings (Default Value)

Select Channel Name
SELECT CHANNEL>> Channel-1

User defined or default names for channel-1 to channel – 8 / 16
(Default : NA)

Skip Channel for Display
SKIP>> No

No Yes
(Default : Yes)

Signal Input Type INPUT TYPE>>
Type K (Cr-Al)
Display Resolution for Measured PV RESOLUTION>>
0.1 Unit
Display Units for Measured PV UNITS>>
°C

Refer Table 2 (Default : Type K (Cr-Al))
1 Unit 0.1 Unit 0.01 Unit 0.001 Unit (Default : 0.1 Unit) (* for 4-20mA)
Refer Table 1 (Default : °C)

Range Low (for 4-20mA)
RANGE LOW>> 0

-19999 to 30000 Counts with Selected Resolution
(Default : 0.0)

Range High (for 4-20mA)
RANGE HIGH>> 1000

-19999 to 30000 Counts with Selected Resolution
(Default : 100.0)

Apply Lower Clip on Displayed PV (for 4-20mA)
LOW CLIPPING>> Disable

Disable Enable
(Default : Disable)

Preset Lower Clip Level (for 4-20mA)
LOW CLIP VAL>> 0.0
Apply Upper Clip on Displayed PV (for 4-20mA)
HIGH CLIPPING>> Disable
Preset Upper Clip Level (for 4-20mA) HIGH CLIP VAL>>
100.0

-19999 to 30000 (Default : 0)
Disable Enable (Default : Disable)
-19999 to 30000 (Default : 100.0)

Zero Offset
ZERO OFFSET>> 0

-1999 / 3000 or -1999.9 / 3000.0
(Default : 0)

User – Linearisation
LINEARISATION>> Disable

Disable Enable
(Default : Disable)

Total Break – Points
BREAK POINTS>> 2

2 to 32 (Default : 2)

Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

Parameters
Select Break – Point Number for Setting SELECT POINT>>
1
X Co-ordinate Value X-VALUE>>
0
Y Co-ordinate Value Y-VALUE>>
0

Settings (Default Value)
1 to Set Numbers of Break-points (Default : NA)
-19999 to 30000 (Default : 0)
-19999 to 30000 (Default : 0)

ALARM CONFIGURATION

Parameters

Settings (Default Value)

Alarms Per Channel
ALARMS / CHAN >> 4

1 to 4 (Default : 4)

Relay-1 Logic
RELAY-1 LOGIC >> Normal

Normal Reverse
(Default : Normal)

Relay-2 Logic
RELAY-2 LOGIC >> Normal

Normal Reverse
(Default : Normal)

RECORDER CONFIGURATION

Parameters

Settings (Default Value)

Normal Recording Interval
NORMAL INTERVAL>> 0:00:30

0:00:00 (H:MM:SS) to
2:30:00 (H:MM:SS)
(Default : 0:00:30)

Zoom Recording Interval
ZOOM INTERVAL>> 0:00:01

0:00:00 (H:MM:SS) to
2:30:00 (H:MM:SS)
(Default : 0:00:01)

Record Generation on Alarm Status Toggle
ALARM TOGGLE REC>> Disable

Disable Enable
(Default : Enable)

Select Recording Mode
RECORDING MODE>> Continuous
Time Interval for Batch Recording (for Batch mode only)
BATCH TIME>> 1.00

Continuous Batch
(Default : Continuous)
0:01 (HH:MM) to
250:00 (HHH:MM) (Default : 1:00)

RTC SETTING

Parameters

Settings

Set Clock Time (HH:MM)
TIME (HH:MM)>> 15:53

0.0 to 23:59

Set Calendar Date
DATE>> 23

1 to 31

Set Calendar Month
MONTH>> 11

1 to 12

Set Calendar Year

YEAR>>

2011

2000 to 2099

UTILITIES

Parameters

Settings

Master Lock Enable Disable

LOCK>>

No

No

Yes

UNLOCK>> No

UTILITIES

Parameters

Settings

UIM Default

No

UIM DEFAULT>> No

Yes

CIM Default

CIM DEFAULT>> No

No Yes

*Set Device Id

No

SET DEVICE ID>> 1

Yes

Make CIM & UIM Compatible

CPY CIM TO UIM>> No

No

Yes

CPY UIM TO CIM>>

No

  • For UniLog Plus Only

Option °C °F
(none) °K EU % Pa Mpa kPa bar
mbar psi
kg/sq.cm mmH2O inH2O mmHg
Torr litre/hr litre/min %RH %O2 %CO2 %CP
V A mA mV ohm ppm rpm
mSec Sec min hrs PH %PH miles/hr mg
g kg

TABLE- 1 Description
Degree Centigrade Degree Fahrenheit No Unit (Blank) Degree Kelvin Engineering Units Percentage Pascals Mpascals Kpascals Bar Milli bar PSI kg/cm2 mm water gauge Inches water gauge mm mercury
Torr Litres per hour Litres per minute % Relative Humidity % Oxygen % Carbon di-oxide % Carbon Potential Volts Amps Milli Amps
Milli Volts Ohms Parts per million Revolutions per minute Milli seconds Seconds Minutes Hours PH %PH Miles per hour Milli grams
Grams Kilo grams

Option

TABLE- 2 Range (Min. to Max.)

Resolution

J Type T/C

0 to +960°C / +32 to +1760°F

-200 to +1376°C / -328 to +2508°F K Type T/C

T Type T/C

-200 to +385°C / -328 to +728°F

0 to +1771°C / +32.0 to +3219°F R Type T/C

0 to +1768°C / +32 to +3214°F S Type T/C

Fixed 1°C / 1°F

0 to +1826°C / +32.0 to +3218°F B Type T/C

0 to +1314.0°C / +32 to +2397.0°F N Type T/C

Reserved for customer specific Thermocouple type not listed above.

RTD Pt100

-199 to +600°C / -328 to +1112°F or
-199.9 to 600.0°C / -328.0 to 1112.0°F

User settable 1°C / 1°F or
0.1°C / 0.1°F

0 to 20mA DC

4 to 20mA DC

0 to 50mV DC

0 to 200mV DC 0 to 1.25V DC

-19999 to +30000 units

User settable 1 / 0.1 / 0.01/ 0.001 units

0 to 5.0V DC

0 to 10.0V DC

1 to 5.0V DC

Assign Channel Name

Instrument Name
File Name
Channel Name

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net
ID SETTING FOR MORE THAN 1 CIM Applicable only for UNILOG PLUS

Operator Setting Alarm Setting
Supervisory Configuration Device Configuration Delete Records Scan Rate Recorder ID Total Device
Select 2 by pressing UP arrow

Select Device (1) Total Channels (8 Or 16)
Device ID Set 1 for 1st CIM Select Device (2) Total Channels (8 Or 16)
Device ID Set 2 for 2nd CIM

Jan 2022

FRONT PANEL LAYOUT

2 X 16 LCD Display Upper Row
Pen Drive Slot PAGE Key
DOWN Key

Front Panel

PPI

UniLog

SELECT PAGE>> ALARM CONFIG

AUTO

Lower Row
LED Indicator ENTER Key UP Key

Symbol Key

Keys Operation Function

PAGE Press to enter or exit set-up mode.

Press to decrease the parameter value. Pressing once DOWN decreases the value by one count; holding pressed
speeds up the change.

Press to increase the parameter value. Pressing once

UP

increases the value by one count; holding pressed speeds

up the change.

ENTER

Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications

Error Message

Cause

Over Range

Process Value above Max. Range

Under Range

Process Value below Min. Range

Sensor Open

Thermocouple / RTD broken

Com. Fail

Communication Link with CIM broken

ELECTRICAL CONNECTIONS
USER INTERFACE MODULE (UIM)

Batch Start Alarm ACK

Switch

Switch

Comm Port

Device

RS485

B-

B+

123456789

UniLog / UniLog Plus

10 11 12 13 14 15 16 17 18

L

N

85~265 V

AC SUPPLY

NO

C

RLY

Alarm-1

Alarm-3

NO

C

RLY

Alarm-2

Alarm-4

JUMPER SETTINGS
INPUT-CHANNEL INTERFACE MODULE (CIM)

Old Version
Jumper Pins Channel-1
Jumper Pins Channel-8

21 4 3

Jumper Pins Channel-9

Pins

Shorting Link

Shorting Link Placed

Shorting Link Parked

Jumper Pins Channel-16
4 1
2 3

RTD Sensor
Pt100 (3-wire)

Place Shorting Link on Pins 1 & 2

321

4

Thermocouples
J, K, T, R, S, B, N Types

Place Shorting Link on Pins 2 & 4

321 4

DC Current
0-20mA, 4-20mA

Place Shorting Link on Pins 2 & 3

321

4

DC Voltage
0-50mV, 0-200mV, 0-1.25V, 0-5V, 1-5V, 0-10V
321
Park Shorting Link
4

COMMUNICATION PORT FOR INTERFACING WITH CIM(S) Applicable only for UNILOG PLUS

CIM – 2 COMM PORT 55 54 53 52

CIM – 1 COMM PORT 55 54 53 52

To Next CIM

UIM Comm Port
Device
RS485
89

ELECTRICAL CONNECTIONS
CHANNEL INTERFACE MODULE (CIM)

Old Version

COMM PORT 55 54 53 52

1A
INPUT-1 2 B
3C 4A
INPUT-2 5 B
6C 7A
INPUT-3 8 B
9C 10 A
INPUT-4 11 B
12 C 13 A
INPUT-5 14 B
15 C 16 A
INPUT-6 17 B
18 C
19 A
INPUT-7 20 B
21 C
22 A
INPUT-8 23 B
24 C
25
SUPPLY 26 L VOLTAGE 27 N

AI – X ABC A B C RTD A B C TC A B C mA/mV/V
CIM – 8 / CIM – 16

A 28 B 29 C 30 A 31 B 32 C 33 A 34 B 35 C 36 A 37 B 38 C 39 A 40 B 41 C 42 A 43 B 44 C 45 A 46 B 47 C 48 A 49 B 50 C 51

INPUT-9 INPUT-10 INPUT-11 INPUT-12 INPUT-13 INPUT-14 INPUT-15 INPUT-16

JUMPER SETTINGS
INPUT-CHANNEL INTERFACE MODULE (CIM)

New Version 1 2
Jumper Pins Channel-1

Jumper Pins Channel-9

DIP Switch for Configuration
Mode

Jumper Pins Channel-8

Mode IndicatorLED

ON 12 ON 12

Jumper Pins Channel-16
1 2

Switch Position

Right

Left

Mode Indicator LED

OFF

ON

Operation Mode Communication Parameter Values

Normal

Configuration

User Set values for Module Slave ID, Baud Rate & Parity

Module Slave ID : 1 Baud Rate : 9600 Parity : Even

Pins

Shorting Shorting Link

Link

Placed

Shorting Link Parked

RTD Sensor
Pt100 (3-wire)

Thermocouples
J, K, T, R, S, B, N Types

DC Voltage
0-50mV, 0-200mV 0-1.25V, 0-5V, 1-5V, 0-10V

21 Park Shorting Link

DC Current
0-20mA, 4-20mA
21 Place Shorting Link on Pins 1 & 2

ELECTRICAL CONNECTIONS
CHANNEL INTERFACE MODULE (CIM)
New Version

55 54 53 52 BBBB
COMM PORT
DC Lin : mV / V / mA Config
Normal Operation
Mode Configuration
Mode
UniLog 8 / 16 Channel Interface Module
Sr. No.: Comm. ID:

DC Lin T/C RTD
51 50 49 INPUT-16

DC Lin T/C RTD
48 47 46 INPUT-15

DC Lin T/C RTD
45 44 43 INPUT-14

DC Lin T/C RTD
42 41 40 INPUT-13

DC Lin T/C RTD
39 38 37 INPUT-12

DC Lin T/C RTD
36 35 34 INPUT-11

DC Lin T/C RTD
33 32 31 INPUT-10

DC Lin T/C RTD
30 29 28 INPUT-9

ON 12

CONFIG

12

12

ON

ON

DC Lin T/C RTD
123 INPUT-1

DC Lin T/C RTD
456 INPUT-2

DC Lin T/C RTD
789 INPUT-3

DC Lin T/C RTD
10 11 12 INPUT-4

DC Lin T/C RTD
13 14 15 INPUT-5

DC Lin T/C RTD
16 17 18 INPUT-6

DC Lin T/C RTD
19 20 21 INPUT-7

DC Lin T/C RTD
22 23 24 INPUT-8

84 ~ 264 VAC

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals