PPI Zenex 48X48 Universal PID Temperature Controller User Manual

June 11, 2024
PPI

Zenex 48X48 Universal PID Temperature Controller
User Manualv

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

Zenex 48X48 Universal PID Temperature Controller

I / O CONFIGURATION PARAMETERS

Parameters Settings (Default Value)
Input Type Refer Table 1 (Default : Type K)
Temperature Display Units °C

°F
(Default : °C)
Temperature Range | Min. to Max. specified for the selected Input Type (Refer Table 1)
(Default : 1375)
Control Output Type  | Refer Table 2 (Default : Relay)
Control Mode   | On-Off
PID
(Default : PID)
Control Logic  | Direct
Reverse (Default : Reverse)
Hysteresis  | 1 to 999°C or 0.1 to 99.9°C (Default : 2 or 0.2)
Setpoint Low Limit | Min. Range to Setpoint High for the selected Input Type (Default : -200)
Setpoint High  Limit | Setpoint Low to Max. Range for the selected Input Type (Default : 1375)

SUPERVISORY PARAMETERS

Parameters Settings (Default Value)
Tune / Optimize Command No

Yes
(Default : No)
Tune / Optimize Abort Command | No
Yes (Default : No)
Overshoot Inhibit | Enable
Disable (Default : Disable)
Overshoot Inhibit Factor | 1.0 to 2.0 (Default : 1.2)
Self-tune on Setpoint Change  | Enable
Disable (Default : Disable)
Offset for PV | -1999 to 9999 or
-199.9 to 999.9
(Default : 0)
PV Digital Filter for PV | 0.5 to 25.0 Seconds
in steps of 0.5 Seconds (Default : 1.0)
Permission for OP2/OP3 Setpoint Editing on Operator Page | Enable
Disable (Default : Enable)
Soak Abort Command on Operator Page | Enable
Disable (Default : Enable)
Soak Time Adjustment on Operator Page  | Enable
Disable (Default : Enable)
Parameters| Settings (Default Value)
---|---
Utility Option | None
Serial Comm.
Soak Start (Default : None)
Slave ID | 1 to 127 (Default : 1)
Baud Rate | 1200, 2400, 4800, 9600 (Default : 9600)
Communication Write Enable | No
Yes (Default : Yes)

PID CONTROL PARAMETERS

Parameters Settings (Default Value)
% Output Power Not Applicable (Default : Not Applicable)
Cycle Time 0.5 to 120.0 Seconds (in steps of 0.5 secs.) (Default : 0.5)
Proportional Band 0.1 to 999.9 (Default : 10.0)
Integral Time 0 to 1000 Seconds (Default : 100)
Derivative Time 0 to 250 Seconds (Default : 25)

OP2 FUNCTION PARAMETERS

Parameters Settings (Default Value)
Output-2 Function Selection

OP2 Function : Alarm-1

Type (Default : Process Low)
Setpoint Min. to Max. Range for the selected Input type (Default : 0)
Deviation Band -1999 to 9999 or -199.9 to 999.9 (Default : 0)
Window Band 3 to 999 or 0.3 to 99.9 (Default : 3)
Logic Normal

Reverse (Default : Normal)
Inhibit | Normal
Reverse (Default : Normal)
Alarm Timer | 5 to 250 Seconds (Default : 10)

OP2 Function : Auxiliary Control

Parameters Settings (Default Value)
Offset Value (Min. Range – SP) to (Max. Range – SP) specified for the

selected Input Type (Default : 0)
Hysteresis | 1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2)
Control Logic | Normal
Reverse (Default : Normal)

OP2 Function : Blower / Compressor Control

Offset Value 0 to 250 or 0.0 to 25.0 (Default : 0)
Hysteresis 1 to 250 or 0.1 to 25.0 (Default : 2 or 0.2)
Time Delay 00.00 to 10.00 Min. Sec (in steps of 5 Seconds) (Default : 00.00)

OP3 FUNCTION PARAMETERS

Parameters Settings (Default Value)
Output-3 Function Selection

OP3 Function : Alarm-2

Type (Default : Process Low)
Setpoint Min. to Max. Range for the selected Input type (Default : 0)
Deviation Band -1999 to 9999 or -199.9 to 999.9 (Default : 0)
Window Band 3 to 999 or 0.3 to 99.9 (Default : 3)
Logic Normal

Reverse (Default : Normal)
Inhibit | Yes
No (Default : Yes)
Alarm Timer | 5 to 250 Seconds (Default : 10)

OP3 Function : Auxiliary Control

Offset Value | (Min. Range – SP) to (Max. Range – SP) specified for the selected Input Type
(Default : 0)
---|---
Hysteresis | 1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2)
Control Logic | Normal
Reverse (Default : Normal)

SOAK TIMER PARAMETERS

Parameters Settings (Default Value)
Timer Enable No

Yes (Default : No)
Time Units | (Default : Min: Sec)
Time Duration | 00.05 to 60:00 Min: Sec 00.05 to 99:55 Hrs: Min 1 to 999 Hours (Default : 00.10 Min: Sec)
Timer-Start Band | 0 to 9999 or
0.0 to 999.9 (Default : 5 or 0.5)
Holdback Strategy | (Default : None)
Hold Band| 1 to 9999 or  0.1 to 999.9 (Default : 5 or 0.5)
Switch-Off Control Output at Timer End | No
Yes (Default : No)
Power-fail Recovery Method | (Default : Continue)

OPERATOR PAGE AND PARAMETERS

Parameters Settings
Timer Start Command No

Yes
Timer Abort Command | No
Yes
Time Duration | 00.05 to 60.00 M:S or 00.05 to 99.55 H:M or 1 to 999 Hours

OP2 Function : Alarm-1

Alarm-1 Setpoint  Min. to Max. Range for the Input Type
Alarm-1 Deviation Band  -1999 to 9999 or -199.9 to 999.9
Alarm-1 Window Band 3 to 999 or 0.3 to 99.9

OP2 Function : Auxiliary Control

Auxiliary Control Setpoint | (Min. Range – SP) to (Max. Range – SP) for selected Input
---|---
OP2 Function : Blower / Compressor Control
Blower / Compressor Setpoint | 0 to 250 or 0.0 to 25.0

OP3 Function : Alarm-2

Parameters Settings
Alarm-2 Setpoint Min. to Max. Range for the Input Type
Alarm-2 Deviation Band -1999 to 9999 or -199.9 to 999.9
Alarm-2 Window Band 3 to 999 or 0.3 to 99.9

OP3 Function : Auxiliary Control

Auxiliary Control Setpoint | (Min. Range SP) to
(Max. Range SP) for selected Input
Control Setpoint (SP) Locking
Setpoint Locking | No
Yes

TABLE- 1

Option Range (Min. to Max.) Resolution
J Type T/C 0 to +960°C / +32 to +1760°F Fixed 1°C / 1°F
K Type T/C -200 to +1375°C / -328 to +2508°F
T Type T/C -200 to +385°C / -328 to +725°F
R Type T/C 0 to +1770°C / +32 to +3218°F
S Type T/C  0 to +1765°C / +32 to +3209°F
B Type T/C 0 to +1825°C / +32 to +3092°F
N Type T/C 0 to +1300°C / +32 to +2372°F
3-wire, RTD Pt100 -199 to +600°C / -328 to +1112°F
3-wire, RTD Pt100  -199.9 to 600.0°C / -199.9 to 999.9°F 0.1°C / 0.1°F

TABLE- 2

Option What it means Remarks
Relay SSR (Solid State Relay) Applicable for OP1 as Relay / SSR

NOTE : Applicable Only For Zenex DC Linear Version

Option What it means Remarks
0 to 20mA current 4 to 20mA current Applicable for OP1 as DC Linear

Current
| 0 to 5 Volts 0 to 10 Volts| Applicable for OP1 as DC Linear Voltage

FRONT PANEL LAYOUT Keys Operation

Symbol Key Function
PAGE Press to enter or exit set-up mode.
DOWN Press to decrease the parameter value. Pressing once decreases the

value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
| ENTER| Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications

Message PV Error Type
Over-range (PV above Max. Range)
Under-range (PV below Min. Range)
Open (Sensor open / broken)

ELECTRICAL CONNECTIONS

ENCLOSURE ASSEMBLY MOUNTING DETAILS OUTPUT-2 MODULE JUMPER SETTINGS OUTPUT-2 & OUTPUT-3

Output Type Jumper Setting – A Jumper Setting – B
Relay
SSR

MOUNTING DETAILS SERIAL COMM. MODULE ELECTRICAL CONNECTIONS

OUTPUT-2 & OUTPUT-3 : HARDWARE JUMPER SETTINGS SERIAL COMMUNICATION MODULE

101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

PPI User Manuals

Related Manuals