PPI Neuro 105 48X48 Programmable Profile Controller User Manual
- June 11, 2024
- PPI
Table of Contents
Neuro 105 48X48 Programmable Profile Controller
neuro 105 48X48
Programmable Profile Controller
INPUT / OUTPUT PARAMETERS : PAGE 12
Parameters
Settings (Default Value)
Hand (manual) made Enable/ Disable
Enable
Disable (Default : Disable)
Quick Adjustment of Setpoint Enable/Disable
Enable Disable
(Default : Enable)
Control Output Type
Relay
Sensor Input Type
SSR 0-20mA 4-20mA (Default : Relay)
Type J Type K Type T Type R
Type S Type B Type N
Reserved RTD Pt100
0-20mA 4-20mA 0 to 50mV
0 to 200mV
0 to 1.25mV
Resolution For PV Range Low For PV
0 to 5.0mV
0 to 10.0mV (Default : Type K)
Refer Table 1 for the available max / min Ranges & Resolution for
each input type. (Default : 1)
Same as above (Default : 0)
Range High For PV Setpoint Low
Same as above (Default : 1000)
Same as above (Default : -200)
Setpoint High
Same as above (Default : 1300)
Offset for PV Digital Filter For PV
-1999 to 9999 (Default : 0)
0.5 to 25.0 (Default : 1.0)
CONTROL PARAMETERS : PAGE 10
Parameters
Settings (Default Value)
Control Setpoint
Setpoint Low to Setpoint High
(Default : 0)
Proportional Band
0 to 999 Units (Default : 50 units)
Hysteresis
1 to 250 (Default : 2)
Integral Time
0 to 1000 Seconds (Default : 100 Sec.)
Derivative Time
0 to 250 Seconds (Default : 25 Sec.)
Cycle Time
0.5 to 120.0 (Default : 20.0)
Relative cool Gain
0.1 to 10.0 (Default : 1.0)
Cool Cycle Time
0.5 to 120.0 (Default : 20.0)
Power Low Limit
0 to less than Power High (Default : 0)
Power High Limit
Greater than Power Low to 100
(Default : 100)
OP2 & OP3 FUNCTION PARAMETERS : PAGE 14
Parameters
Settings (Default Value)
Output-2 Function Selection
Alarm
Cool control
Output-2 Type
Profile Event (Default : Alarm)
Relay
SSR
0-20mA
Output-3 Function Selection
4-20mA (Default : Relay)
Alarm Recorder
Recorder Output Type
Profile Event (Default : Alarm)
0-20mA
Recorder Low
4-20mA (Default : 0-20mA)
Range Low to Range High (Default : 0)
Recorder High
Range Low to Range High (Default : 0)
Operation Manual
This brief manual is primarily meant for quick reference to wiring connections
and parameter searching. For more details on operation and application; please
log on to www.ppiindia.net
ALARM PARAMETERS : PAGE 11
Parameters
Settings (Default Value)
Alarm-1 Type
None
Process Low Process High
Deviation Band
Window Band
Alarm-1 Setpoint Alarm-1 Deviation Band
End of Profile (Default : None) Throughout the range for the selected input
type
(Default : 0)
-999 to 999 (Default : 0)
Alarm-1 Window Band Alarm-1 Hysteresis
3 to 999 (Default : 3)
1 to 999 (Default : 2)
Alarm-1 Logic
Direct
Alarm-1 Inhibit
Reverse (Default : Direct)
No
Alarm-2 Type
Yes (Default : No)
None
Process low
Process high
Deviation Band
Window Band
Alarm-2 Setpoint Alarm-2 Deviation Band
End of Profile (Default : None) Throughout the range for the selected input
type
(Default : 0)
-999 to 999 (Default : 0)
Alarm-2 Window Band Alarm-2 Hysteresis Alarm-2 Logic
Alarm-2 Inhibit
3 to 999 (Default : 3)
1 to 999 (Default : 2)
Direct
Reverse (Default : Direct)
No
Yes (Default : No)
PROFILE : SEGMENT PARAMETERS : PAGE 15
Parameters
Settings (Default Value)
Select Profile Number
1 to Max. configured
Select Set Number Ramp Rate Target Setpoint Soak Time
1 to Max. configured
0.00 to 99.99 (Default : 0.00)
Range Low to Range High (Default : 0)
0 to 9999 (Default : 0)
PROFILE : CONFIGURATION PARAMETERS : PAGE 18
Parameters
Settings (Default Value)
Profile Enable/Disable
Enable
Output(S) Off
Disable (Default : Enable)
No
Numbers of Profile
Yes (Default : No)
1 to 2
Select Profile Number Numbers of Sets for the Selected Profile
1 to Max. configured
1 to 8
Number of Programs Reset Programs Set-UP
1 to 16
No Yes (Default : No)
PROFILE : BAND / EVENT PARAMETERS : PAGE 16
Parameters
Settings (Default Value)
Select Profile Number
1 to Max. configured
Ramp Hold Band Soak Hold Band
0 to 250 (Default : 0)
0 to 250 (Default : 0)
Select Segment Number
1 to twice the Max. configured Sets
Output-2 Event Time
0 to 9999 (Default : 0)
Output-2 Event Status
ON, OFF (Default : ON)
Output-3 Event Time Output-3 Event Status
0 to 9999 (Default : 0)
ON, OFF (Default : ON)
UTILITY PARAMETERS : PAGE 13
Parameters
Settings (Default Value)
Self Tune Commands
No
Overshoot Inhibit
Yes (Default : No)
Enable
Baud Rate Controller ID Number
Disable (Default : Disable)
1200, 2400, 4800, 9600 (Default : 9600)
1 to 31 (Default : 1)
Communication Write Enable
No
Yes (Default : No)
Option J Type T/C
TABLE- 1 Range (Min. to Max.)
Resolution
0 to +760°C / +32 to +1400°F
K Type T/C T Type T/C
-200 to +1300°C / -328 to +2372°F -200 to +350°C / -328 to +662°F
R Type T/C S Type T/C
0 to +1770°C / +32 to +3092°F 0 to +1700°C / +32 to +3092°F
Fixed 1°C / 1°F
B Type T/C
+200 to +1700°C / +392 to +3092°F
N Type T/C RTD Pt100
0 to +1300°C / +32 to +2372°F
Reserved for customer specific Thermocouple type not listed above.
-199 to +600°C / -328 to +1112°F or
-199.9 to 600.0°C / -199.9 to 999.9°F
User settable 1°C / 1°F or
0.1°C / 0.1°F
0 to 20mA DC
4 to 20mA DC
0 to 50mV DC 0 to 200mV DC
-1999 to +9999 units
User settable 1 / 0.1 / 0.01/ 0.001 units
0 to 1.25V DC
0 to 5.0V DC 0 to 10.0V DC
101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net
Upper Readout
FRONT PANEL LAYOUT
Front Panel
PPI
neuro 105
Lower Readout Output-2 Indicator Output-1 Indicator
PAGE Key
DOWN Key
R S OP1 OP2 OP3
Ramp Indicator Soak Indicator Output-3 Indicator
ENTER Key UP Key
Symbol Key
Keys Operation Function
PAGE Press to enter or exit set-up mode.
DOWN
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Press to increase the parameter value. Pressing once UP increases the value by
one count; keeping pressed
speeds up the change.
ENTER
Press to store the set parameter value and to scroll to the next parameter on the PAGE.
PV Error Indications
Message
PV Error Type
Over-range (PV above Max. Range)
Under-range (PV below Min. Range)
Open (Sensor open / broken)
NOTE : For Page 17 Kindly Refer the Detailed Manual on www.ppiindia.net
Jan 2022
ELECTRICAL CONNECTIONS
85~264 Exct (*) VAC 5V/12V
RS485 (*) B+ B- N L + –
+TC
++V/mmAV–
RTD
– V/mA + – SSR +
RLY C NO
OUTPUT1
PV INPUT (*) Optional Modules
OUTPUT2 (*)
–
V/mA SSR RLY
+ +
NC C NO
6 7 8 9 10
5
11
4
12
3 48X48 13
2
14
1 18 17 16 15
NO C NC RLY
–
–
SSR
V/mA OUTPUT3 (*)
Aux SP (*)
JUMPER SETTINGS
OUTPUT-2 & OUTPUT-3
A
B
1 23
B A
1 23
MOUNTING DETAILS
OUTPUT-2 MODULE
MOUNTING DETAILS
OUTPUT-3 MODULE
Plug & Socket Connector
Output Module
Projected Parts
Plug & Socket Connector
Output Module
Projected Parts
Relay/SSR Module
Output Type Jumper Setting – A
Jumper Setting – B
Relay
123
123
SSR
123
123
Power Supply Board
PPI
neuro 105
Front Label Upright
Slots
CPU Board
Front Label Upside-down
neuro 105
PPI
Slots
mV, V, mA T/C
Pt100 + SERIAL SUPPLY SAEULXIELICATIROYNSP
}
}
ENCLOSURE ASSEMBLY
`UP’ inscribed on topside
Removal
UP UP
OUTPUT 1 SSR / DC Linear RELAY
+ NO C
INPUT
6 5 4 3 2 1
NC C NO 7
8 9
nePu48rPXo481I05 18 17 16 NO C NC
ROS11ESU10LRTAP/GYDUNCTDL2inear
12
13
L N
14
15
A B
AC DC
RSOSEURLTA/PYDUCT
Linear 3
Placing Back
Power Supply PCB
CPU PCB
Display PCB
neuro 105
R
PPI
S
OP3 OP2 OP1
Pullout Grip
JUMPER SETTINGS
INPUT & OUTPUT-1
B
C
Input Jumper Settings 1 2 3
C AB
1 234
CPU PCB
Output 1 Jumper Settings
neuro 105
P P I
Input
A
Pins Shorted DC Linear Current (mA)
A
Link Parked All Other Input Types
Output – 1
Output Type Jumper Setting – B Jumper Setting – C
3
Relay
2
1
1234
3
SSR Drive
2
1
1234
DC Linear
3
Current
2
(or Voltage)
1
1234
MOUNTING DETAILS
Power Supply Board
Serial Communication/ Auxiliary SP Selection Module
Plug & Socket Connectors
PPI
105 neuro
Front Label Upside-down
neuro 105 96X96
Programmable Profile Controller
INPUT / OUTPUT PARAMETERS : PAGE 12
Parameters
Settings (Default Value)
Hand (manual) made Enable/ Disable
Enable
Disable (Default : Disable)
Quick Adjustment of Setpoint Enable/Disable
Enable Disable
(Default : Enable)
Control Output Type
Relay
SSR
0-20mA
Sensor Input Type
4-20mA (Default : Relay)
Type J
Type K
Type T
Type R
Type S
Type B
Type N
Reserved
RTD Pt100
0-20mA
4-20mA
0 to 50mV
0 to 200mV
0 to 1.25mV
0 to 5.0mV
Resolution For PV Range Low For PV
0 to 10.0mV
(Default : Type K)
Refer Table 1 for the available max / min Ranges & Resolution for
each input type. (Default : 1)
Same as above (Default : 0)
Range High For PV
Same as above (Default : 1000)
Setpoint Low
Same as above (Default : -200)
Setpoint High
Same as above (Default : 1300)
Offset for PV
-1999 to 9999 (Default : 0)
Digital Filter For PV
0.5 to 25.0 (Default : 1.0)
CONTROL PARAMETERS : PAGE 10
Parameters
Settings (Default Value)
Control Setpoint
Setpoint Low to Setpoint High
(Default : 0)
Proportional Band
0 to 999 Units (Default : 50 units)
Hysteresis
1 to 250 (Default : 2)
Integral Time
0 to 1000 Seconds (Default : 100 Sec.)
Derivative Time
0 to 250 Seconds (Default : 25 Sec.)
Cycle Time
0.5 to 120.0 (Default : 20.0)
Relative cool Gain
0.1 to 10.0 (Default : 1.0)
Cool Cycle Time
0.5 to 120.0 (Default : 20.0)
Power Low Limit
0 to less than Power High (Default : 0)
Power High Limit
Greater than Power Low to 100
(Default : 100)
OP2 & OP3 FUNCTION PARAMETERS : PAGE 14
Parameters
Settings (Default Value)
Output-2 Function Selection
Alarm
Cool control
Output-2 Type
Profile Event (Default : Alarm)
Relay
SSR
0-20mA
Output-3 Function Selection
4-20mA (Default : Relay)
Alarm Recorder
Recorder Output Type
Profile Event (Default : Alarm)
0-20mA
Recorder Low
4-20mA (Default : 0-20mA)
Range Low to Range High (Default : 0)
Recorder High
Range Low to Range High (Default : 0)
Operation Manual
This brief manual is primarily meant for quick reference to wiring connections
and parameter searching. For more details on operation and application; please
log on to www.ppiindia.net
ALARM PARAMETERS : PAGE 11
Parameters
Settings (Default Value)
Alarm-1 Type
None
Process Low Process High
Deviation Band
Window Band
Alarm-1 Setpoint Alarm-1 Deviation Band
End of Profile (Default : None) Throughout the range for the selected input
type
(Default : 0)
-999 to 999 (Default : 0)
Alarm-1 Window Band Alarm-1 Hysteresis Alarm-1 Logic
Alarm-1 Inhibit Alarm-2 Type
3 to 999 (Default : 3)
1 to 999 (Default : 2)
Direct
Reverse (Default : Direct)
No
Yes (Default : No)
None
Process low Process high
Alarm-2 Setpoint Alarm-2 Deviation Band
Deviation Band
Window Band
End of Profile (Default : None) Throughout the range for the selected input
type
(Default : 0)
-999 to 999 (Default : 0)
Alarm-2 Window Band Alarm-2 Hysteresis Alarm-2 Logic
Alarm-2 Inhibit
3 to 999 (Default : 3)
1 to 999 (Default : 2)
Direct
Reverse (Default : Direct)
No
Yes (Default : No)
PROFILE : SEGMENT PARAMETERS : PAGE 15
Parameters
Settings (Default Value)
Select Profile Number
1 to Max. configured
Select Set Number Ramp Rate Target Setpoint Soak Time
1 to Max. configured
0.00 to 99.99 (Default : 0.00)
Range Low to Range High (Default : 0)
0 to 9999 (Default : 0)
PROFILE : CONFIGURATION PARAMETERS : PAGE 18
Parameters
Settings (Default Value)
Profile Enable/Disable
Enable
Output(S) Off
Disable (Default : Enable)
No
Numbers of Profile
Yes (Default : No)
1 to 2
Select Profile Number Numbers of Sets for the Selected Profile
1 to Max. configured
1 to 8
Number of Programs Reset Programs Set-UP
1 to 16
No Yes (Default : No)
PROFILE : BAND / EVENT PARAMETERS : PAGE 16
Parameters
Settings (Default Value)
Select Profile Number
1 to Max. configured
Ramp Hold Band Soak Hold Band
0 to 250 (Default : 0)
0 to 250 (Default : 0)
Select Segment Number
1 to twice the Max. configured Sets
Output-2 Event Time
0 to 9999 (Default : 0)
Output-2 Event Status
ON, OFF (Default : ON)
Output-3 Event Time
0 to 9999 (Default : 0)
Output-3 Event Status
ON, OFF (Default : ON)
UTILITY PARAMETERS : PAGE 13
Parameters
Settings (Default Value)
Self Tune Commands
No
Overshoot Inhibit
Yes (Default : No)
Enable
Baud Rate Controller ID Number
Disable (Default : Disable)
1200, 2400, 4800, 9600 (Default : 9600)
1 to 31 (Default : 1)
Communication Write Enable
No
Yes (Default : No)
Option J Type T/C K Type T/C T Type T/C
TABLE- 1 Range (Min. to Max.)
Resolution
0 to +760°C / +32 to +1400°F
-200 to +1300°C / -328 to +2372°F
-200 to +350°C / -328 to +662°F
R Type T/C S Type T/C
0 to +1770°C / +32 to +3092°F 0 to +1700°C / +32 to +3092°F
Fixed 1°C / 1°F
B Type T/C
+200 to +1700°C / +392 to +3092°F
N Type T/C RTD Pt100
0 to +1300°C / +32 to +2372°F
Reserved for customer specific Thermocouple type not listed above.
-199 to +600°C / -328 to +1112°F or
-199.9 to 600.0°C / -199.9 to 999.9°F
User settable 1°C / 1°F or
0.1°C / 0.1°F
0 to 20mA DC
4 to 20mA DC
0 to 50mV DC 0 to 200mV DC
-1999 to +9999 units
User settable 1 / 0.1 / 0.01/ 0.001 units
0 to 1.25V DC
0 to 5.0V DC 0 to 10.0V DC
101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net
FRONT PANEL LAYOUT
Front Panel
PPI
neuro 105
Upper Readout
Lower Readout
Ramp Indicator Output-1 Indicator
PAGE Key
R OP1
OP2
S OP3
Output-2 Indicator Soak Indicator Output-3 Indicator
ENTER Key
DOWN Key
UP Key
Symbol Key
Keys Operation Function
PAGE Press to enter or exit set-up mode.
DOWN
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Press to increase the parameter value. Pressing once UP increases the value by
one count; keeping pressed
speeds up the change.
ENTER
Press to store the set parameter value and to scroll to the next parameter on the PAGE.
PV Error Indications
Message
PV Error Type
Over-range (PV above Max. Range)
Under-range (PV below Min. Range)
Open (Sensor open / broken)
NOTE : For Page 17 Kindly Refer the Detailed Manual on www.ppiindia.net
Jan 2022
ELECTRICAL CONNECTIONS
NO C NC
RELAY SSR/ DC Linear
OUTPUT-3
NC C NO NC C NO
RELAY
SSR/DC Linear SSR/DC Linear
OUTPUT-2
LN
85 ~ 265 V RS485 AC SUPPLY
RELAY
OUTPUT-1
9
18
8
17
7
16
6
15
5 96 X 96 14
4
13
3
12
2
11
1
10
INPUT
SERIAL COMMUNICATION MODULE
Output 3 Jumper Setting
8 Pin Female Socket
Serial Communication Module
8 Pin Male Plug
PPI
A
1 23
B
1 23
CN4 CN3
neuro 105
Power-Supply PCB
mV, V, mA
T/C Pt100
Input
Input Type Jumper `A’ Setting
Thermocouple, RTD Pt100, mV & V
12 3
DC Linear Current (mA)
12 3
Output Type Relay
Output-1
Jumper Setting – B
Jumper Setting – C
1
2
3
4
123
1 2 SSR Drive 3 4
123
1
DC Linear
2
Current
(or Voltage)
3
4
123
INPUT & OUTPUT HARDWARE JUMPER SETTINGS
Output Type
Output-2
Jumper Setting – D
Jumper Setting – E
Relay
123
123
SSR
123
123
Output Type
Output-3
Jumper Setting – A
Jumper Setting – B
Relay SSR
123 123
123 123
Output 2 Jumper Setting
D
E
B
1 23
1 23
Output 1 B & C Jumper Settings 1234
C
123
A
Input
Jumper Setting
123
Display
} Keys
CPU Board
References
Read User Manual Online (PDF format)