LabCon Map PC Recording 4 Channel Mapping PC Software User Manual

June 11, 2024
PPI

LabCon Map PC Recording 4 Channel Mapping PC Software

LabCon-Map-PC-Recording-4-Channel-Mapping-PC-Software-
PRODUCT

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

OPERATOR PAGE PARAMETERS

Parameters Settings (Default Value)

Time Start Command > >

Time Abort Command > >

| Yes No

(Default : No)

Time Interval (H:M) >>| 0.00 to 500.00 (HH:MM)

(Default : 0.10)

Ctrl Set Value >>| Setpoint LO limit to Setpoint HI limit (Resolution 0.1°C for RTD /

DC Linear & 1°C for Thermocouple)

(Default : 25.0)

Ctrl Lo Deviation >>| For RTD & DC Linear : 0.2 to 99.9 For Thermocouple : 2 to 99

(Default : 2.0)

Ctrl Hi Deviation >>| For RTD & DC Linear : 0.2 to 99.9 For Thermocouple : 2 to 99

(Default : 2.0)

Change Password >>| 1 to 100

(Default : 0)

SUPERVISORY

SUPERVISORY > SENSOR INPUT

Parameters Settings (Default Value)
Ctrl Zero Offset >> -50 to 50

(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)

(Default : 0.0)

Map-1 Zero Offset >> Map-2 Zero Offset >> Map-3 Zero Offset >> Map-4 Zero Offset >>| -50 to 50

(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)

(Default : 0.0)

SUPERVISORY > RECORDING

Parameters Settings (Default Value)

Rec.

Interval (min) >>

| 0 to 250 Min (Default : 5 Min)
Alarm

Toggle Record >>

| Enable Disable

(Default : Enable)

Del PC Records >>| Yes No

(Default : No)

Del

Display Record >>

| Yes No

(Default : No)

GSM Machine ID >>

(refer note)

| 1 to 128

(Default : 1)

RTC Time >>| 0 to 23 for Hour

0 to 59 for Min

(Default : NA)

RTC Date >>| 1 to 31 (Default : NA)
RTC Month >>| 1 to 12 (Default : NA)
RTC Year >>| 2000 to 2099

(Default : NA)

Device Id >>| 1 to 127

(Default : 1)

SUPERVISORY > CONTROL

Parameters Settings (Default Value)
Tune > > Yes No

(Default : No)

Setpoint LO Limit >>| Min Range for the Selected Input Type to Setpoint HI Limit (Resolution 0.1°C for RTD /

DC Linear & 1°C for Thermocouple)

(Default : 0.0)

Setpoint| Setpoint LO Limit to
HI Limit >>| Max Range for the Selected

Input Type

| (Resolution 0.1°C for RTD /
| DC Linear & 1°C for Thermocouple)
| (Default : 600.0)
Compressor| 0 to 100
Setpoint| (Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
| (Default : 45.0)
Compressor Hyst > >| 0.1 to 99.9

(Default : 2.0)

Heat **Ctrl Action >>**| ON-OFF PID

(Default : PID)

Heat Hyst >>| 0.1 to 99.9

(Default : 0.2)

Heat Only Control| Heat + Cool Control Zone : Single| Heat + Cool Control Zone : Dual
---|---|---
Proportional Band >>

0.1 to 999.9

(Default : 50.0)

| Proportional Band >>

0.1 to 999.9

(Default : 50.0)

| Cz Prop Band >> Proportional Band for Cool Pre-dominant zone 0.1 to 999.9

(Default : 50.0)

Integral Time >> 0 to 3600 sec (Default : 100 sec)| Integral Time >> 0 to 3600 sec (Default : 100 sec)| Cz Integral Time >>

Integral Time for Cool Pre-dominant zone

0 to 3600 sec

(Default : 100 sec)

Derivative Time >>

0 to 600 sec (Default : 16 sec)

| Derivative Time >>

0 to 600 sec (Default : 16 sec)

| Cz Derivative Time >> Derivative Time for Cool Pre-dominant zone

0 to 600 sec (Default : 16 sec)


Cycle Time >>

0.5 to 100.0 sec (Default : 10.0 sec)

| ****

Cycle Time >>

0.5 to 100.0 sec (Default : 10.0 sec)

| Hz Prop Band >> Proportional Band for Heat Pre-dominant zone 0.1 to 999.9

(Default : 50.0)

Overshoot Inhibit > > Enable Disable

(Default : Disable)

| Overshoot Inhibit > > Enable Disable

(Default : Disable)

| Hz Integral Time >>

Integral Time for Heat Pre-dominant zone

0 to 3600 sec

(Default : 100 sec)

Cutoff Factor >>

1.0 to 2.0 sec (Default : 1.2 sec)

| Cutoff Factor >>

1.0 to 2.0 sec (Default : 1.2 sec)

| Hz Derivative Time >> Derivative Time for Heat Pre-dominant zone

0 to 600 sec (Default : 16 sec)

Cycle Time >>

0.5 to 100.0 sec (Default : 10.0 sec)

Overshoot Inhibit > > Enable Disable

(Default : Disable)

Cutoff Factor >>

1.0 to 2.0 sec (Default : 1.2 sec)

SUPERVISORY > PASSWORD

Parameters Settings (Default Value)
Change Password >> 1000 to 1999

(Default : 123)

SUPERVISORY > EXI

Parameters Settings (Default Value)
Exit Setup Mode >> Yes No

(Default : No)

FACTORY

FACTORY > CONTROL SENSOR INPUT

Parameters Settings (Default Value)
Input Type >> Refer Table 1 (Default : RTD Pt100)
Signal LO >>
Signal HI >>
Range LO >> -199.9 to RANGE HI

(Default : 0.0)

Range HI >>| RANGE LO to 999.9

(Default : 100.0)

FACTORY > MAPPING PARAMETERS

Parameters Settings (Default Value)
Mapping Points >> 0 to 4

(Default : 0)

Input Type >>| Refer Table 1 (Default : RTD Pt100)
Signal LO >>| | Input Type| Settings| Default
---|---|---
0 to 20mA| 0.00 to Signal High| 0.00
4 to 20mA| 4.00 to Signal High| 4.00
0 to 5V| 0.000 to Signal High| 0.000
0 to 10V| 0.00 to Signal High| 0.00
1 to 5V| 1.000 to Signal High| 1.000
Signal HI >>| | Input Type| Settings| Default
---|---|---
0 to 20mA| Signal Low to 20.00| 20.00
4 to 20mA| Signal Low to 20.00| 20.00
0 to 5V| Signal Low to 5.000| 5.000
0 to 10V| Signal Low to 10.00| 10.00
1 to 5V| Signal Low to 5.000| 5.000
Range LO >>| -199.9 to RANGE HI

(Default : 0.0)

Range HI >>| RANGE LO to 999.9

(Default : 100.0)

FACTORY > ALARM PARAMETERS

Parameters Settings (Default Value)
Hysteresis >> 0.1 to 99.9

(Default : 0.2)

Inhibit >>| Yes No

(Default : Yes)

FACTORY > HEAT COOL SELECT

Parameters Settings (Default Value)
Control Strategy >> Heat Only Cool Only Heat + Cool

(Default : Heat + Cool)

Control Strategy : Cool Only
Time Delay (sec) >>| 0 to 1000 Sec (Default : 200 Sec)
Control Strategy : Heat + Cool
Compressor Strategy >>| CONT. OFF CONT. ON SP BASED PV BASED

(Default : CONT. ON)

CONT. ON SP BASED PV BASED

Time

Delay (sec) >>

0 to 1000 Sec (Default : 200 Sec)

| Boundary Set Value >>

0 to 100 (Resolution 0.1°C for RTD / DC Linear

& 1°C for Thermocouple)

| Control Zones >> Single  Dual

(Default : Single)


Time Delay (sec) >>

0 to 1000 Sec (Default : 200 Sec)

Time Delay (sec) >> 0 to 1000 Sec (Default : 200 Sec)

FACTORY > SOAK TIMER PARAMETERS

Parameters Settings (Default Value)
Enable >> No Yes

(Default : No)

Start Band >>| 0 to 999.9

(Default : 0.5)

Holdback Strategy >>| None Up Down Both

(Default : None)

Hold Band >>| 0.1 to 999.9

(Default : 0.5)

Heat Off >>| No Yes

(Default : No)

Cool Off >>| No Yes

(Default : No)

Power Recovery >>| Abort Restart Continuous

(Default : Restart)

FACTORY > DOOR OPEN

Parameters Settings (Default Value)
Enable >> No Yes

(Default : No)

Start Band >>| 0 to 999.9

(Default : 0.5)

Holdback Strategy >>| None Up Down Both

(Default : None)

Hold Band >>| 0.1 to 999.9

(Default : 0.5)

Heat Off >>| No Yes

(Default : No)

Cool Off >>| No Yes

(Default : No)

Power Recovery >>| Abort Restart Continuous

(Default : Restart)

FACTORY > MAINS FAILURE

Parameters Settings (Default Value)
Enable >> No Yes

(Default : No)

Start Band >>| 0 to 999.9

(Default : 0.5)

Holdback Strategy >>| None Up Down Both

(Default : None)

Hold Band >>| 0.1 to 999.9

(Default : 0.5)

Heat Off >>| No Yes

(Default : No)

Cool Off >>| No Yes

(Default : No)

Power Recovery >>| Abort Restart Continuous

(Default : Restart)

FACTORY > SMS ALERT

Parameters Settings (Default Value)
Enable >> No Yes

(Default : No)

Start Band >>| 0 to 999.9

(Default : 0.5)

Holdback Strategy >>| None Up Down Both

(Default : None)

Hold Band >>| 0.1 to 999.9

(Default : 0.5)

Heat Off >>| No Yes

(Default : No)

Cool Off >>| No Yes

(Default : No)

Power Recovery >>| Abort Restart Continuous

(Default : Restart)

FACTORY > FACTORY DEFAULT

Parameters Settings (Default Value)
Set To Default >> Yes No

(Default : No)

FACTORY > PASSWORD

Parameters Settings (Default Value)
Set To Default >> Yes No

(Default : No)

FACTORY > EXIT

Parameters Settings (Default Value)
Exit Setup Mode >> Yes No

(Default : No)

TABLE 1

TABLE 1

What it means| Range (Min. to Max.)| Resolution
Type J Thermocouple| 0 to +960°C| ****




Fixed 1°C

Type K Thermocouple| -200 to +1376°C
Type T Thermocouple| -200 to +385°C
Type R Thermocouple| 0 to +1770°C
Type S Thermocouple| 0 to +1765°C
Type B Thermocouple| 0 to +1825°C
Type N Thermocouple| 0 to +1300°C


Reserve

| Reserved for customer specific Thermocouple type not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.
3-wire, RTD Pt100| -199.9 to 600.0°C| Fixed 0.1°C
0 to 20mA DC current| ****



-199.9 to 999.9 units

| ****



Fixed

0.1 unit

4 to 20mA DC current
0 to 5.0V DC voltage
0 to 10.0V DC voltage
1 to 5.0V DC voltage

FRONT PANEL KEYS

Symbol Key Function
****

Scroll

| Press to scroll through various Process Information Screens in Normal Operation Mode.
| Alarm Acknowledge| ****

Press to acknowledge and mute (if active) alarm output.

| ****

DOWN

| Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
| ****

UP

| Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
| ****

SET-UP

| ****

Press to enter or exit set-up mode.

| ****

ENTER

| Press to store the set parameter value and to scroll to the next parameter.

PV ERROR INDICATIONS

Message Error Type Cause
OPEN Sensor Open Sensor (RTD Pt100) Broken / Open
OVR Over-range Temperature above Max. Specified Range
UNR Under-range Temperature below Min. Specified Range

ELECTRICAL CONNECTIONS

4 Mapping Channels

LabCon-Map-PC-Recording-4-Channel-Mapping-PC-Software-
FIG-7

CONTACT

Address: 101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210.
Sales: 8208199048 / 8208141446
Support: 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals