PPI LabCon Recording + Printer Interface User Manual
- June 11, 2024
- PPI
Table of Contents
LabCon (Printer)
Recording + Printer Interface
Operation Manual
LabCon Recording + Printer Interface
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
OPERATOR PAGE PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Select Print Option>> | None Print (New) |
Re-Print (Old) Print Info Page
(Default : None)
Time Start Command >>
Time Abort Command >>| Yes No
(Default: No)
Time Interval (H:M) >>| 0.00 to 500.00 (HH:MM)
(Default: 0.10)
Ctrl Set Value >>| Setpoint LO limit to Setpoint HI limit (Resolution
0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default : 25.0)
Ctrl Lo Deviation >>| For RTD & DC Linear : 0.2 to 99.9 For Thermocouple: 2 to
99
(Default: 2.0)
Ctrl Hi Deviation >>| For RTD & DC Linear: 0.2 to 99.9 For Thermocouple: 2 to
99
(Default: 2.0)
Change Password >>| 1 to 100
(Default: 0)
SUPERVISORY > SENSOR INPUT
Parameters | Settings (Default Value) |
---|---|
Ctrl Zero Offset >> | -50 to 50 |
(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default: 0.0)
SUPERVISORY > RECORDING
Parameters | Settings (Default Value) |
---|
Rec.
Interval (min) >>| 0 to 250 Min (Default : 5 Min)
Alarm
Toggle Record >>| Enable Disable
(Default: Enable)
Del
Print Records >>| Yes No
(Default: No)
Del
Display Record >>| Yes No
(Default: No)
RTC Time >>| 0 to 23 for Hour
0 to 59 for Min (Default : NA)
RTC Date >>| 1 to 31
(Default: NA)
RTC Month >>| 1 to 12 (Default: NA)
RTC Year >>| 2000 to 2099
(Default: NA)
SUPERVISORY > CONTROL
Parameters | Settings (Default Value) |
---|---|
Tune >> | Yes No |
(Default: No)
Setpoint LO Limit >>| Min Range for the Selected Input Type to Setpoint HI
Limit (Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default : 0.0)
Setpoint HI Limit >>| Setpoint LO Limit to Max Range for the Selected
Input Type
(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default: 600.0)
Compressor Setpoint >>| 0 to 100
(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default: 45.0)
Compressor Hyst >>| 0.1 to 99.9
(Default: 2.0)
Heat
Ctrl Action >>| ON-OFF PID
(Default: PID)
Heat Hyst >>| 0.1 to 99.9
(Default: 0.2)
Heat Only Control| Heat + Cool Control Zone: Single| Heat + Cool
Control Zone: Dual
---|---|---
Proportional Band >>
0.1 to 999.9
(Default: 50.0)| Proportional Band >>
0.1 to 999.9
(Default: 50.0)| Cz Prop Band >> Proportional Band for Cool Pre-dominant zone
0.1 to 999.9
(Default: 50.0)
Integral Time >> 0 to 3600 sec (Default: 100 sec)| Integral Time >> 0 to 3600
sec (Default: 100 sec)| Cz Integral Time >>
Integral Time for Cool Pre-dominant zone
0 to 3600 sec
(Default: 100 sec)
Derivative Time >>
0 to 600 sec (Default: 16 sec)| Derivative Time >>
0 to 600 sec (Default : 16 sec)| Cz Derivative Time >> Derivative Time for
Cool Pre-dominant zone
0 to 600 sec (Default : 16 sec)
Cycle Time >>
0.5 to 100.0 sec (Default: 10.0 sec)| Cycle Time >>
0.5 to 100.0 sec (Default: 10.0 sec)| Hz Prop Band >> Proportional Band for
Heat Pre-dominant zone 0.1 to 999.9
(Default: 50.0)
Overshoot Inhibit >> Enable Disable
(Default: Disable)| Overshoot Inhibit >> Enable Disable
(Default: Disable)| Hz Integral Time >>
Integral Time for Heat Pre-dominant zone
0 to 3600 sec
(Default: 100 sec)
Cutoff Factor >>
1.0 to 2.0 sec (Default: 1.2 sec)| Cutoff Factor >>
1.0 to 2.0 sec (Default: 1.2 sec)| Hz Derivative Time >> Derivative Time for
Heat Pre-dominant zone
0 to 600 sec (Default: 16 sec)
Cycle Time >>
0.5 to 100.0 sec (Default: 10.0 sec)
Overshoot Inhibit >> Enable Disable
(Default: Disable)
Cutoff Factor >>
1.0 to 2.0 sec (Default: 1.2 sec)
SUPERVISORY > PRINTER SETTING
Parameters | Settings (Default Value) |
---|---|
Line Per Page >> | 25 to 100 |
(Default: 65)
Top Margine >>| 1 to 5
(Default: 2)
Bottom Margine >>| 1 to 5
(Default: 2)
Header & Footer >>| No
On First Page Every Page
(Default: No)
Enable >>| Yes No
(Default: No)
SUPERVISORY > PRINT EVENT
Parameters| Settings
(Default Value)
---|---
Alarm Toggle >>
RTC Modify >>
Interval Modify >>
Power Up >>
Door Open >>
Mains Fail >>
Setpoint Modify >>| Yes
No
(Default : Yes)
SUPERVISORY > PASSWORD
Parameters| Settings
(Default Value)
---|---
Change
Password >>| 1000 to 1999
(Default: 123)
SUPERVISORY > EXIT
Parameters| Settings
(Default Value)
---|---
Exit Setup Mode >>| Yes
No
(Default: )No
FACTORY > CONTROL SENSOR INPUT
Parameters | Settings (Default Value) |
---|---|
Input Type >> | Refer Table 1 (Default : RTD Pt100) |
Signal LO >> | |
--- | --- |
0 to 20mA | 0.00 to Signal High |
4 to 20mA | 4.00 to Signal High |
0 to 5V | 0.000 to Signal High |
0 to 10V | 0.00 to Signal High |
1 to 5V | 1.000 to Signal High |
Signal HI >> | |
--- | --- |
0 to 20mA | Signal Low to 20.00 |
4 to 20mA | Signal Low to 20.00 |
0 to 5V | Signal Low to 5.000 |
0 to 10V | Signal Low to 10.00 |
1 to 5V | Signal Low to 5.000 |
Range LO >> | -199.9 to RANGE HI |
(Default : 0.0)
Range HI >>| RANGE LO to 999.9
(Default : 100.0)
FACTORY > ALARM PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Hysteresis >> | 0.1 to 99.9 |
(Default : 0.2)
Inhibit >>| Yes No
(Default : Yes)
FACTORY > HEAT COOL SELECT
Parameters | Settings (Default Value) |
---|---|
Control Strategy >> | Heat Only Cool Only Heat + Cool |
(Default : Heat + Cool)
Control Strategy: Cool Only
Time Delay (sec) >>| 0 to 1000 Sec (Default : 200 Sec)
Control Strategy: Heat + Cool
Compressor Strategy >>| CONT. OFF CONT. ON SP BASED PV BASED
(Default: CONT. ON)
CONT. ON| SP BASED| PV BASED
---|---|---
Time Delay (sec) >>
0 to 1000 Sec
(Default: 200 Sec)| Boundary Set Value >>
0 to 100
(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default : 45.0)| Time Delay (sec) >>
0 to 1000 Sec
(Default: 200 Sec)
Control Zones >>
Single
Dual
(Default: Single)
Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
FACTORY > SOAK TIMER PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Enable >> | No Yes |
(Default: No)
Start Band >>| 0 to 999.9
(Default: 0.5)
Holdback Strategy >>| None Up Down Both
(Default : None)
Hold Band >>| 0.1 to 999.9
(Default : 0.5)
Heat Off >>| No Yes
(Default : No)
Cool Off >>| No Yes
(Default: No)
Power Recovery >>| Abort Restart Continuous
(Default: Restart)
FACTORY > DOOR OPEN
Parameters | Settings (Default Value) |
---|---|
Enable >> | Yes No |
(Default : No)
Switch Logic >>| Close: Door Open Open: Door Open
(Default: Close: Door Open)
Door
Alrm Dly (sec) >>| 0 to 1000 Sec
(Default : 60 Sec)
FACTORY > MAINS FAILURE
Parameters | Settings (Default Value) |
---|---|
Enable >> | Yes No |
(Default: No)
Switch Logic >>| Close: Mains Fail Open: Mains Fail
(Default: Close: Mains Fail)
FACTORY > PASSWORD
Parameters | Settings (Default Value) |
---|---|
Change Password >> | 2000 to 2999 |
(Default: 321)
FACTORY > FACTORY DEFAULT
Parameters | Settings (Default Value) |
---|---|
Set To Default >> | Yes No |
(Default: No)
FACTORY > EXIT
Parameters | Settings (Default Value) |
---|---|
Exit Setup Mode >> | Yes No |
(Default: No)
TABLE 1
What it means| Range (Min. to Max.)| Resolution
Type J Thermocouple| 0 to +960°C| Fixed 1°C
Type K Thermocouple| -200 to +1376°C
Type T Thermocouple| -200 to +385°C
Type R Thermocouple| 0 to +1770°C
Type S Thermocouple| 0 to +1765°C
Type B Thermocouple| 0 to +1825°C
Type N Thermocouple| 0 to +1300°C
Reserve| Reserved for customer specific Thermocouple type not listed above.
The type shall be specified in accordance with the ordered (optional on
request) Thermocouple type.
3-wire, RTD Pt100| -199.9 to 600.0°C| Fixed
0.1°C
0 to 20mA DC current| -199.9 to 999.9 units| Fixed
0.1 unit
4 to 20mA DC current
0 to 5.0V DC voltage
0 to 10.0V DC voltage
1 to 5.0V DC voltage
ELECTRICAL CONNECTIONS
PV ERROR INDICATIONS
Message | Error Type | Cause |
---|
|
Sensor Open| Sensor (RTD Pt100) Broken / Open
| Over-range| Temperature above Max. Specified Range
| Under-range| Temperature below Min. Specified Range
FRONT PANEL KEYS
Symbol | Key | Function |
---|---|---|
**** | Scroll | Press to scroll through various Process Information Screens in |
Normal Operation Mode.
| Alarm Acknowledge| Press to acknowledge and mute (if active) alarm
output.
| DOWN| Press to decrease the parameter value. Pressing once decreases
the value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the
value by one count; keeping pressed speeds up the change.
| SET-UP| Press to enter or exit set-up mode.
****| ENTER| Press to store the set parameter value and to scroll to the
next parameter.