PPI HumiTherm Plus Recording + PC Software User Manual
- June 11, 2024
- PPI
Table of Contents
HumiTherm Plus Recording + PC Software
User Manual
HumiTherm Plus Recording + PC Software
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
OPERATOR PARAMETERS
Parameters| Settings (Default Value)
Temp. Set Value >>| SP Low Limit to SP High Limit
(Default: 25.0)
%RH Set Value >>| SP Low Limit to SP High Limit
(Default: 60.0)
Temp. Lo Deviation >>| 0.2 to 99.9
(Default: 2.0)
Temp. Hi Deviation >>| 0.2 to 99.9
(Default: 2.0)
%RH Lo Deviation >>| 0.2 to 99.9
(Default: 2.0)
%RH Hi Deviation >>| 0.2 to 99.9
(Default: 2.0)
Change Password >>| 1 to 100
(Default: 0)
RECORDING PARAMETERS
Parameters| Settings (Default Value)
Recording Interval (min) >>| 0 to 250 Min
(Default: 5 Min)
Alarm Toggle Records >>| Enable Disable
(Default: Enable)
Delete PC Records >>| Yes No
(Default: No)
Temp. Zero Offset >>| -50.0 to 50.0
(Default: 0.0)
%RH Zero Offset >>| -50.0 to 50.0
(Default: 0.0)
GSM Machine ID >> (refer note)| 1 to 128
(Default: 1)
RTC Time >>| 0 to 23 for Hour
0 to 59 for Min
(Default: NA)
RTC Date >>| 1 to 31
(Default: NA)
RTC Month >>| 1 to 12
(Default: NA)
RTC Year >>| 2000 to 2099
(Default: NA)
Device Id >>| 1 to 127
(Default: 1)
Change Password >>| 1000 to 1999
(Default: 123)
FACTORY > TEMPERATURE > ALARM FACTORY > HUMIDITY (%RH) > ALARM
Parameters| Settings (Default Value)
Hysteresis >>| 0.1 to 99.9
(Default: 0.2)
Inhibit >>| Yes No
(Default: Yes)
FACTORY > TEMPERATURE > CONTROL FACTORY > HUMIDITY (%RH) > CONTROL
Parameters| Settings (Default Value)
Tune >>| Yes No
(Default: No)
Setpoint LO Limit >>| -99.9 to SETPOINT HI LIMIT
(Default: 10.0)
Setpoint HI Limit >>| For RTD: Setpoint Lo Limit to 600.0
For mA/V: Setpoint Lo Limit to 999.9
(Default: 60.0)
FACTORY > TEMPERATURE > CONTROL FACTORY > HUMIDITY (%RH) > CONTROL
CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9
(Default: 50.0)
CZ Integral Time >>| 0 to 3600 Sec
(Default: 100 Sec)
CZ Derivative Time >>| 0 to 600 Sec
(Default: 16 Sec)
HZ Prop Band >>| 0.1 to 999.9
(Default: 50.0)
HZ Integral Time >>| 0 to 3600 Sec
(Default: 100 Sec)
HZ Derivative Time >>| 0 to 600 Sec
(Default: 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec
(Default: 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9
(Default: 50.0)
Integral Time >>| 0 to 3600 Sec
(Default: 100 Sec)
Derivative Time >>| 0 to 600 Sec
(Default: 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec
(Default: 10.0 Sec)
FACTORY > TEMPERATURE > SENSOR INPUT FACTORY > HUMIDITY (%RH) > SENSOR
INPUT
Parameters| Settings (Default Value)
Input Type >>| RTD Pt100 0-20mA
4-20mA
0-5V
0-10V
1-5V
(Default:
For Temp. Input: RTD Pt100
For %RH Input: 0-5V)
Available for Temp. Input only
Signal LO >>|
Signal HI >>|
Range LO >>| -199.9 to RANGE HI
(Default: 0.0)
Range HI >>| RANGE LO to 999.9
(Default: 100.0)
FACTORY > **COMPRESSOR**
Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED
(Default: CONT. ON)
CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>
0 to 1000 Sec (Default : 200 Sec)| Boundary Set Value >>
0.0 to 100.0
(Default : 45.0)| Compressor SP >>
0.0 to 100.0
(Default: 45.0)
| Control Zones >>
SINGLE DUAL
(Default : SINGLE)| Hysteresis >>
0.1 to 99.9
(Default: 2.0)
Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)| Time Delay (sec) >>
0 to 1000 Sec
(Default: 200 Sec)
FACTORY > BOILER WATER LEVEL
Parameters| Settings (Default Value)
Enable >>| Yes No
(Default: No)
Water Level Startegy >>| Single Switch
Dual Switch Lo-hi
Dual Switch Lo-vlo
(Default: Single Switch)
Switch-1 Logic >>| Close: Water Lo
Open: Water Lo
(Default: Close: Water Lo)
Switch-2 Logic >>| Close: Water HI
Open: Water HI
(Default: Close : Water HI)
OR
Close: Water VLO
Open: Water VLO
(Default: Close: Water VLO)
FACTORY > DOOR OPEN
Parameters| Settings (Default Value)
Enable >>| Yes No
(Default: No)
Switch Logic >>| Close: Door Open
Open: Door Open
(Default: Close: Door Open)
Door Alrm Dly (sec) >>| 0 to 1000 Sec
(Default : 60 Sec)
FACTORY > MAINS FAILURE
Parameters| Settings (Default Value)
Enable >>| Yes No
(Default: No)
Switch Logic >>| Close: Mains Fail
Open: Mains Fail
(Default: Close : Mains Fail)
FACTORY > SMS ALERT
Parameters| Settings (Default Value)
Enable >> (refer note)| Yes No
(Default: No)
Reset GSM Module >> (refer note)| Yes No
(Default: No)
Note : These parameters are available only if the controller supplied with GSM module version.
FACTORY > FACTORY DEFAULT
Parameters| Settings (Default Value)
Set To Default >>| Yes No
(Default: No)
FACTORY > PASSWORD
Parameters| Settings (Default Value)
Change Password >>| 2000 to 2999
(Default: 321)
FACTORY > EXIT
Parameters| Settings (Default Value)
Exit Setup Mode >>| Yes No
(Default: No)
FRONT PANEL KEYS
Symbol | Key | Function |
---|---|---|
Scroll | Press to scroll through various Process Information Screens in |
Normal Operation Mode.
| Alarm Acknowledge| Press to acknowledge and mute (if active) alarm output.
| DOWN| Press to decrease the parameter value. Pressing once decreases the
value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value
by one count; keeping pressed speeds up the change.
| SET-UP| Press to enter or exit set-up mode.
| ENTER| Press to store the set parameter value and to scroll to the next
parameter.
PV ERROR INDICATIONS
Message | Error Type | Cause |
---|---|---|
Sensor Open | Sensor (RTD Pt100) Broken/Open | |
Over-range | Temperature above Max. Specified Range | |
Under-range | Temperature below Min. Specified Range |
ELECTRICAL CONNECTIONS
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales: 8208199048/8208141446
Support: 07498799226/08767395333
E: sales@ppiindia.net
support@ppiindia.net
Jan 2022
Documents / Resources
| PPI
HumiTherm Plus Recording + PC
Software
[pdf] User Manual
HumiTherm Plus Recording PC Software, HumiTherm Plus, Recording PC Software,
PC Software, Software
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>