SuperLightingLED DALI/DMX 4 Channel Switch Owner’s Manual
- September 24, 2024
- SuperLightingLED
Table of Contents
DALI/DMX 4 Channel Switch
“`html
Product Specifications
-
Product Name: DH4 DALI/DMX 4-Channel Switch
-
Channels: 4 DALI address, 4-channel 16A dry contact mains rated
relay switch output -
Work Modes: DALI mode, DMX mode
-
Input Voltage: 100-240VAC
-
Input Signal: DALI+DMX512
-
Relay Contacts: High inrush (120 A at 20ms), single-pole,
single-throw (SPST) relay -
Max Relay Load Current:
- 16A resistive load (incandescent lamp)
- 8A Capacitive load (LED dimming driver)
- 8A inductive load (fluorescent lamp)
-
Environment: Ta: -20°C ~ +50°C, Tc: +60°C, IP20
-
Warranty: 5 years
Product Usage Instructions
System Setting
1. System Setting:
WorkMode: DALI Channel Num: 4 Manual Switch: Yes
Long press M button for 2s to enter system setting state. Short
press the M button to switch between setting items.
DALI Mode Setup
- Short press or button to select DALI working mode.
- DALI Address Assignment:
- Manually assign DALI address and view on digital display.
- Automatically assign by DALI master.
- Two groups of DALI signal input with no need to distinguish
polarity.
DMX Mode Setup
- Short press or button to select DMX working mode.
- RDM Function:
- Enables intercommunication between DMX master and decoder.
- Supports manual switching of individual channels.
Mechanical Installation
Mount the DH4 on a DIN Rail using TS-35/7.5 or TS-35/15 mounting
size.
Frequently Asked Questions (FAQ)
Q: Can the DH4 switch between DALI and DMX working modes?
A: Yes, you can switch between DALI and DMX modes by short
pressing the appropriate button.
Q: What is the warranty period for the DH4 switch?
A: The DH4 comes with a 5-year warranty.
“`
DH4
DALI/DMX 4-Channel Switch
4 DALI address, 4 channel 16Adry contact mains rated relay switch output.
OLEDdisplayscreen, via button settingtwoworkmode: DALImode, DMXmode. DALI
address can be manually assigned and shown in digital display or
automatically assigned by DALI master. In accordance with DALI standard
protocol IEC 62386-101,102, 208
and in compliance with DALI products from other international incorporation.
Comply with the DMX512 standard protocols. RDM function can realize
intercommunication between DMX master and decoder. Supports manual switching
of individual channels. High-inrush specification relays (single pole,
normally open). Zero cross switching function. Can operate as:
4 individual channels (4 × 1) 2 sets of 2 channels (2 × 2) 1 sets of 4
channels (1 × 4)
DALI Switch
4CH/ dry contact output / 4 DALI address/ DMX-RDM / OLEDdisplay / Din Rail
Technical Parameters
InputandOutput
Input voltage
100-240VAC
Input current
0.1A
Input signal
DALI+DMX512
No-load standby power consumption
0.5W@100V,
1.5W@240V
Full load loss power 4W@100V, 4.5W@240V
Relay contacts
High inrush (120 A at 20ms), single-pole, single-throw (SPST) relay.
Max relay load current
16A resistive load (incandescent lamp) 8A Capacitive load (LED dimming driver) 8A inductive load ( uorescent lamp)
Safety and EMC EMC standard (EMC)
ETSI EN 301 489-1 V2.2.3 ETSI EN 301 489-17 V3.2.4
Safety standard(LVD)
EN 62368-1:2020+A11:2020
Certi cation
CE,EMC,LVD
Warranty and Protection
Warranty
5 years
Environment Operation temperature Case temperature (Max.) IP rating Package Size Gross weight
Ta: -20 OC ~ +50 OC Tc: +60 OC IP20
W118 x L102 x H71mm 0.345kg
Mechanical Structures and Installations
2CH drycontactoutput 1CH drycontactoutput
3CH drycontactoutput 4CH drycontactoutput
AC N Input AC L Input
OLEDdispay screen Settingkey
Two groups of DALI signal input DALI bus no need distinguish plus-minus
polarity
DALIcom LEDindicator
115.00mm
L
N
100-240VAC IN
K1A 1 K1B K2A 2 K2B K3A 3 K3B K4A 4 K4B
DH4 DALI/DMX 4-Channel Switch
4 ChannelON/OFFLEDindicator
DALI IN DALI OUT DA1 DA2 DA1 DA2
DALI COM
K1
K2
K3
Uin = 100-240VAC Iin = 0.1A Out = 4×16A Temp Range: -20~+55
DMX IN
DMX OUT
GND D- D+ GND D- D+
K4
DMX Signal RJ45 Pin1: D+ Pin2: DPin7: GND Pin8: GND
4 Channel manual switch RJ45 DMX signal input
DMX COM
DMXinput
DMX output
DMX comLEDindicator
88.00mm
88.00mm 65.00mm
User Manual Ver 1.0.0 2023.7
DIN Rail Mounting Size: TS-35/7.5 or TS-35/15
Page1
Wiring Diagram
LN AC100-240V
L
N
100-240VAC IN
K1A 1 K1B K2A 2 K2B K3A 3 K3B K4A 4 K4B
DALI IN DALI OUT DA1 DA2 DA1 DA2
DALI COM
K1
K2
K3
DMX IN
DMX OUT
GND D- D+ GND D- D+
K4
DMX Signal RJ45 Pin1: D+ Pin2: DPin7: GND Pin8: GND
DMX COM
Note: The maximum surge current of the AC output is120A, the sum of surge
current of multiple resistivel load or inductive
load (LED drivers )should not exceed its maximum value. Otherwise, the product
will be overloaded and damaged.
DALI Master
DMX Master
DMX signal
WorkMode
1.Systemsetting
System Setting WorkMode:DALI Channe1Num:4 ManualSwitch:Yes
Long press M button for 2s, enter system setting state, prepare to set the
working mode, channel number and manual switch enable. Short press the M
button to switch three setting items.
Working mode: Short press or button, switch between DALI and DMX working mode.
Channel number: Short press or button, switch the number of 4/2/1 channels,
i.e. 4 independent channels (4×1), 2 groups of 2 channels (2×2) or 1 group of
4 channels (1×4).
Manual switch enable: Short press or button, setting to allow (Yes) or
disallow (No) the manual switching function, i.e. setting whether the four-
channel manual switching buttons are active or not.
Long press M button for 2s, or timeout 15s, quit system setting.
2.DALI mode
DALI Mode CH1:01 CH2:02 CH3:03 CH4:04
In DALI mode, the DALI address can be set by buttons or DALI master control:
(1) Set DALI Address via buttons
Short press M button, prepare for set the start DALI address. The four
channels can be addressed separately, and the address setting of the four
channels can be switched sequentially by short pressing the M button.
Short press or button, change the address value of the current channel
(00-63-FF), FF means unassigned DALI address. long press for fast adjustment.
Long press M button for 2s, or timeout 15s, quit DALI address setting.
(2) DALI address assigned by DALI masters DALI address can also be assigned by DALI Master controller automatically. Please refer to user manuals of compatible DALI Masters for speci c operations.
3.DMX mode
DMX Mode CH1:001 CH2:002 CH3:003 CH4:004
In DMX mode, the DMX address can be set by buttons or DMX RDM master:
Short press M button, prepare for set the start DMX address. Only the address
of the rst channel needs to be set, and the addresses of the other channels
will be automatically added 1 in sequence.
Short press or button, change the DMX address value (001-512), long press for fast adjustment.
Long press M button for 2s, or timeout 15s, quit DMX address setting.
DMX control: When DMX data value is <50, the relay output is off.
When DMX data value is >200, the relay output is on.
When DMX data value is between 50 and 200, keep the previous on/off status.
4.Restore factory settings
Reset
Long press and buttons at the same time for 2 seconds to restore factory settings. Factory default parameter: DALI mode, number of channels is 4, manual switch enable.
5.Overheat protection
Temp Faults
110°C triggers temperature protection and shuts off the relay output. Normal switching control is resumed at 90°C.