EUROLAMP 300-28212_1 Air Conditioner Dc Inverter Instruction Manual

July 25, 2024
EUROLAMP

EUROLAMP 300-28212_1 Air Conditioner Dc Inverter

Product Information

Specifications

  • Product: Air Conditioner DC Inverter
  • Refrigerant: R32
  • Temperature Range:
    • Cooling: 0°C to 30°C
    • Heating: 17°C to 32°C
    • Operation: -15°C to 30°C
    • Storage: 15°C to 50°C

Product Usage Instructions

Safety Precautions

Follow all safety precautions mentioned in the manual before using the air conditioner.

Installation

  1. Read and follow the installation precautions for R32 refrigerant.
  2. Ensure proper indoor unit installation.
  3. Install the outdoor unit as per the instructions.
  4. Perform a test operation after installation.

Maintenance

Regular maintenance is crucial for optimal performance. Refer to the maintenance section for detailed instructions.

Troubleshooting

Refer to the troubleshooting guide in case of any issues with the air conditioner.

FAQs

  • What type of refrigerant does the air conditioner use?
    • The air conditioner uses R32 refrigerant.
  • What is the recommended temperature range for operation?
    • The recommended temperature range for operation is between 0°C to 30°C for cooling and 17°C to 32°C for heating.

SAFETY PRECAUTIONS

SAFETY RULES AND RECOMMENDATIONS FOR THE INSTALLER
Read this guide before installing and using the appliance. During the installation of the indoor and outdoor units the access to the working area should be forbidden to children. Unforeseeable accidents could happen. Make sure that the base of the outdoor unit is firmly fixed. Check that air cannot enter the refrigerant system and check for refrigerant leaks when moving the air conditioner. Carry out a test cycle after installing the air conditioner and record the operating data. The ratings of the fuse installed in the built in control unit are 4A / 250V. Protect the indoor unit with a fuse of suitable capacity for the maximum input current or with another overload protection device. Ensure that the mains voltage corresponds to that stamped on the rating plate. Keep the switch or power plug clean. Insert the power plug correctly and firmly into the socket, thereby avoiding the risk of electric shock or fire due to insufficient contact. Check that the socket is suitable for the plug, otherwise have the socket changed. The appliance must be fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules. The air conditioner must be installed by professional or qualified persons. Do not install the appliance at a distance of less than 50 cm from inflammable substances (alcohol, etc.) or from pressurised containers (e.g. spray cans). If the appliance is used in areas without the possibility of ventilation, precautions must be taken to prevent any leaks of refrigerant gas from remaining in the environment and creating a danger of fire The packaging materials are recyclable and should be disposed of in the separate waste bins. Take the air conditioner at the end of its useful life to a special waste collection centre for disposal. Only use the air conditioner as instructed in this booklet. These instructions are not intended to cover every possible condition and situation. As with any electrical household appliance, common sense and caution are therefore always recommended for installation, operation and maintenance. The appliance must be installed in accordance with applicable national regulations. Before accessing the terminals, all the power circuits must be disconnected from the power supply. The appliance shall be installed in accordance with national wiring regulations. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by The air conditioner must be installed by children without supervision.
-46-

ENG
SAFETY PRECAUTIONS
SAFETY RULES AND RECOMMENDATIONS FOR THE INSTALLER
Do not try to install the conditioner alone; always contact specialized technical personnel. Cleaning and maintenance must be carried out by specialized technical personnel. In any case disconnect the appliance from the mains electricity supply before carrying out any cleaning or maintenance. Ensure that the mains voltage corresponds to that stamped on the rating plate. Keep the switch or power plug clean. Insert the power plug correctly and firmly into the socket, thereby avoiding the risk of electric shock or fire due to insufficient contact. Do not pull out the plug to switch off the appliance when it is in operation, since this could create a spark and cause a fire, etc. This appliance has been made for air conditioning domestic environments and must not be used for any other purpose, such as for drying clothes, cooling food, etc. The packaging materials are recyclable and should be disposed of in the separate waste bins. Take the air conditioner at the end of its useful life to a special waste collection center for disposal. Always use the appliance with the air filter mounted. The use of the conditioner without air filter could cause an excessive accumulation of dust or waste on the inner parts of the device with possible subsequent failures. The user is responsible for having the appliance installed by a qualified technician, who must check that it is earthed in accordance with current legislation and insert a thermomagnetic circuit breaker. The batteries in remote controller must be recycled or disposed of properly. Disposal of Scrap Batteries. Please discard the batteries as sorted municipal waste at the accessible collection point. Never remain directly exposed to the flow of cold air for a long time. The direct and prolonged exposition to cold air could be dangerous for your health .Particular care should be taken in the rooms where there are children, old or sick people. If the appliance gives off smoke or there is a smell of burning, immediately cut off the pow er supply and contact the Service Centre. The prolonged use of the device in such conditions could cause fire or electrocution.Have repairs carried out only by an authorised Service Centre of the manufacturer. Incorrect repair could expose the user to the risk of electric shock, etc. Unhook the automatic switch if you foresee not to use the device for a long time. The airflow direction must be properly adjusted. The flaps must be directed downwards in the heating mode and upwards in the cooling mode. Only use the air conditioner as instructed in this booklet. These instructions are not intended to cover every possible condition and situation. As with any electrical household appliance, common sense and caution are therefore always recommended for installation, operation and maintenance. Ensure that the appliance is disconnected from the power supply when it will remain inoperative for a long period and before carrying out any cleaning or maintenance. Selecting the most suitable temperature can prevent damage to the appliance.
-47-

ENG
SAFETY PRECAUTIONS
SAFETY RULES AND PROHIBITIONS
Do not bend, tug or compress the power cord since this could damage it. Electrical shocks or fire are probably due to a damaged power cord. Specialized technical personnel only must replace a damaged power cord. Do not use extensions or gang modules. Do not touch the appliance when barefoot or parts of the body are wet or damp. Do not obstruct the air inlet or outlet of the indoor or the outdoor unit. The obstruction of these openings causes a reduction in the operative efficiency of the conditioner with possible consequent failures or damages. In no way alter the characteristics of the appliance. Do not install the appliance in environments where the air could contain gas, oil or sulphur or near sources of heat. This appliance is not intended for use by persons (including children ) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Do not climb onto or place any heavy or hot objects on top of the appliance. Do not leave windows or doors open for long when the air conditioner is operating.. Do not direct the airflow onto plants or animals. A long direct exposition to the flow of cold air of the conditioner could have negative effects on plants and animals. Do not put the conditioner in contact with water. The electrical insulation could be damaged and thus causing electrocution. Do not climb onto or place any objects on the outdoor unit Never insert a stick or similar object into the appliance. It could cause injury. Children should be supervised to ensure that they do not play with the appliance. If the supply cord is damaged, it must be replaced by the manufacturer,its service agent or similarly qualified persons in order to avoid a hazard.
-48-

ENG
NAME OF PARTS INDOOR UNIT

Mounting plate

Air Outlet

Front Panel Emergency button

Air Filter

Air Outlet

Air Deflector and Flap

Refrigerant connecting pipe

OUTDOOR UNIT
Air Outlet

with the protective cover removed

Air Inlet Wiring Cover
Drainage Pipe Connection Wiring Valve protective cover Gas Valve (low pressure valve) Gas Valve (high pressure valve)

Note: This figure shown may be different from the actual object. Please take the latter as the standard. -49-

NAME OF PARTS INDOOR DISPLAY AND CONTROL PANEL
1

ENG
2 3

. LED indication Function

1

Indicator for Timer, temperature and Error codes.

2

Lights up during Timer operation.

3

SLEEP mode

The shape and position of switches and indicators may be different according to the model, but their function is the same.

-50-

ENG

INDOOR UNIT DISPLAY

(!) Attempt to use the air conditioner under the temperature beyond the specified range may cause the air conditioner protection device to start and the air conditioner may fail to operate. Therefore, try to use the air conditioner in the following temperature conditions.

Inverter Air Conditioner: Mode
Temperature
Room Temperature
Outdoor Temperature

Heating 0oC~30oC -15oC~30oC

Cooling

Dry

17oC~32oC

15oC~50oC

With the power supply connected, restart the air conditioner after shutdown, or switch it to other mode during operation, and the air conditioner protection device will start. The compressor will resume operation after 3 minutes.

(!) Characteristics of heating operation (applicable to Heating pump) Preheating: When the heating function is enabled, the indoor unit will take 2~5 minutes for preheating, after that the air conditioner will start heating and blows warm air. Defrosting: During heating, when the outdoor unit frosted, the air conditioner will enable the automatic defrosting function to improve the heating effect. During defrosting, the indoor and outdoor fans stop running. The air conditioner will resume heating automatically after defrosting finish.

(!) Emergency button: Open the panel and find the emergency button on the electronic control box when the remote controller fails . (Always press the emergency button with insulation material.)

Current status Standby
Standby (Only for heating
pump) Running

Operation
Press the emergency button once
Press the emergency button
twice in 3 seconds
Press the emergency button once

Respond It beeps briefly once. It beeps briefly twice.
It keeps beeping for a while

Enter mode Cooling mode Heating mode
Off mode

control-box cover

(open the panel of indoor unit)
-51-

ENG

INSTRUCTION FOR SERVICING

1. Check the information in this manual to find out the dimensions of space needed for proper installation of the device, including the minimum distances allowed compared to adjacent structures. 2. Appliance shall be installed, operated and stored in a room with a floor area larger than 4m . 3. The installation of pipe-work shall be kept to a minimum. 4. The pipe-work shall be protected from physical damage, and shall not be installed in an 2 unventilated space if the space is smaller than 4m . 5. The compliance with national gas regulations shall be observed. 6. The mechanical connections shall be accessible for maintenance purposes. 7. Follow the instructions given in this manual for handling, installing, cleaning, maintaining and disposing of the refrigerant. 8. Make sure ventilation openings clear of obstruction. 9. Notice: The servicing shall be performed only as recommended by the manufacturer. 10. Warning: The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. 11. Warning: The appliance shall be stored in a room without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example an operating electric heater). 12. The appliance shall be stored so as to prevent mechanical damage from occurring. 13. It is appropriate that anyone who is called upon to work on a refrigerant circuit should hold a valid and up-to-date certificate from an assessment authority accredited by the industry and recognizing their competence to handle refrigerants, in accordance with the assessment specification recognized in the industrial sector concerned. Service operations should only be carried out in accordance with the recommendations of the equipment manufacturer. Maintenance and repair operations that require the assistance of other qualified persons must be conducted under the supervision of the person competent for the use of flammable refrigerants. 14. Every working procedure that affects safety means shall only be carried out by competent persons. 15. Warning: Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater. Do not pierce or burn. Be aware that refrigerants may not contain an odor.
Caution: Risk of fire Operating Instructions Read technical manual
-52-

ENG
INSTRUCTION FOR SERVICING (R32)
16. Information on servicing: 1) Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. 2) Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed. 3) General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material 4) Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. 5) Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO 2 fire extinguisher adjacent to the charging area. 6) No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed. 7) Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. 8) Checks to the refrigeration equipment Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance.
-53-

ENG
INSTRUCTION FOR SERVICING (R32)
The following checks shall be applied to installations using flammable refrigerants: — The charge size is in accordance with the room size within which the refrigerant containing parts are installed; — The ventilation machinery and outlets are operating adequately and are not obstructed; — If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; — Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; — Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded. 9) Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include: — That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; — That there no live electrical components and wiring are exposed while charging, recovering or purging the system; — That there is continuity of earth bonding. 17. Repairs to sealed components 1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation. 2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications. NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them. 18. Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
-54-

ENG
INSTRUCTION FOR SERVICING (R32)
19. Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. 20. Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. 21. Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process. 22. Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, it is important that best practice is followed since inflammability is a consideration. The following procedure shall be adhered to: — Remove refrigerant; — Purge the circuit with inert gas; — Evacuate; — Purge again with inert gas; — Open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. 23. Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
-55-

ENG
INSTRUCTION FOR SERVICING (R32)
a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure, ensure that: . mechanical handling equipment is available, if required, for handling refrigerant cylinders; . all personal protective equipment is available and being used correctly; . the recovery process is supervised at all times by a competent person; . recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. F) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer’s instructions. h) Do not overfill cylinders. (No more than 80 % volume liquid charge). i) Do not exceed the maximum working pressure of the cylinder, even temporarily. J) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. K) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. 24. Labeling Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. 25. Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. Special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure- relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recover cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
-56-

ENG

INSTALLATION PRECAUTIONS (R32)

IMPORTANT CONSIDERATIONS 1. The air conditioner must be installed by professional personnel and the Installation manual is used
only for the professional installation personnel! The installation specifications should be subject to our after-sale service regulations. 2. When filling the combustible refrigerant, any of your rude operations may cause serious injury or injuries to human body and objects. 3. A leak test must be done after the installation completed. 4. It is a must to do the safety inspection before maintaining or repairing an air conditioner using combustible refrigerant in order to ensure that the fire risk is reduced to minimum. 5. It is necessary to operate the machine under a controlled procedure in order to ensure that any risk arising from the combustible gas or vapor during the operation is reduced to minimum. 6. Requirements for the total weight of filled refrigerant and the area of a room to be equipped with an air conditioner (are shown as in the following Tables GG.1 and GG.2) The maximum charge and the required minimum floor area m l = (4 m3) x LFL, m2 = (26 m3)) x LFL, m3 = (130 m3) x LFL Where LFL is the lower flammable limit in kg3 , R32 LFL is 0,038 kg/ m3 . For the appliances with a charge amount m1 < M = m2 : The maximum charge in a room shall be in accordance with the following: m max = 2,5 x (LFL) (5/4) x h0 x (A) 1/2 The required minimum floor area Amin to install an appliance with refrigerant charge M (kg) shall be in accordance with following A min = (M/ (2,5 x (LFL) (5/4) x h0 )) 2

Category LFL (kg/m)

R32

0,306

GG.1 – Maximum Charge (kg)

hO (m) 1

Floor Area (m)

4

7 10 15 20

1,14 1,51 1,8 2,2 2,54

1,8

2,05 2,71 3,24 3,97 4,58

2,2

2,5 3,31 3,96 4,85 5,6

30 50 3,12 4,02 5,61 7,254 6,86 8,85

GG.2 – Minimum Room Area (m2)

Category R32

LFL (kg/m3) hO (m)

Charge Amount () (kg) Minimum Room Area (m2)

1.224kg 1.836kg 2.448kg 3.672kg 4.896kg 6.12kg 7.956kg

0,6

29

51 116 206 321 543

1

0,306

1,8

10

19

42

74 116 196

3

6

13

23 36 60

2,2

2

4

9

15 24 40

-57-

ENG

INSTALLATION PRECAUTIONS

(R32)
INSTALLATION SAFETY PRINCIPLES 1. Site Safety

Open Flames Prohibited 2. Operation Safety

Ventillation Necessary

Mind Static Electricity
2. Installation Safety · Refrigerant Leak Detector · Appropriate Installation Location

Must wear protective clothing and anti-static gloves

Don’t use mobile phone

The left picture is the schematic diagram of a refrigerant leak detector
Please note that: 1. The installation site should be well-ventilated. 2. The sites for installing and maintaining an air conditioner using Refrigerant R32 should be free from open fire or welding, smoking, drying oven or any other heat source higher than 548 which easily produces open fire. 3. When installing an air conditioner, it is necessary to take appropriate anti-static measures such as wear anti-static clothing and/or gloves. 4. It is necessary to choose the site convenient for installation or maintenance wherein the air inlets and outlets of the indoor and outdoor units should be not surrounded by obstacles or close to any heat source or combustible and/or explosive environment. 5. If the indoor unit suffers refrigerant leak during the installation, it is necessary to immediately turn off the valve of the outdoor unit and all the personnel should go out till the refrigerant leaks completely for 15 minutes. If the product is damaged, it is a must to carry such damaged product back to the maintenance station and it is prohibited to weld the refrigerant pipe or conduct other operations on the user’s site. 6. It is necessary to choose the place where the inlet and outlet air of the indoor unit is even. 7. It is necessary to avoid the places where there are other electrical products, power switch plugs and sockets, kitchen cabinet, bed, sofa and other valuables right under the lines on two sides of the indoor unit.

-58-

ENG

INSTALLATION PRECAUTIONS (R32)

Tool
Standard Wrench
Adjustable/ Crescent Wrench
Torque Wrench
Hex Keys or Allen
Wrenches Drill & Drill
Bits
Hole Saw

Picture

Tool Pipe Cutter

Picture

Tool Vacuum Pump

Picture

Screw drivers (Phillips & Flat blade)
Manifold and Gauges
Level
Flaring tool

Safety Glasses Work Gloves
Refrigerant Scale
Micron Gauge

Clamp on Amp Meter

Pipe Length and Additional Refrigerant
Inverter Models Capacity (Btu/h)
Lenght of pipe with standard charge
Maximum distance between indoor and outdoor unit Additional refrigerant charge
Max. diff. in level between indoor and outdoor unit Type of refrigerant

9-12K 5 m 15 m
15 g/m 10 m
R32

18K 5 m 15 m
20 g/m 10 m
R32

Torque Parameters Pipe Size Newton meter [N x m]

1/4” ( 6,35) 3/8” ( 9,52)
1/2” (12) 5,8” (15,88)

18-20 30-35 45-50 60-65

Pound-force foot (1bf-ft) 24,4-27,1 40,6-47,4
61,0-67,7 81,3-88,1

Kilogram-force meter (kgf-m) 2,4-2,7 4,1-4,8
6,2-6,9 8,2-8,9

-59-

ENG

INSTALLATION PRECAUTIONS
Dedicated Distribution Device and Wire for Air Conditioner

INVERTER TYPE MODEL capacity (Btu/h)

9k Indoor

12k Indoor

18k Indoor
Sectional area

18k Outdoor

27k/32k/42k Outdoor

N

Power supply

cable

L

(on outdoor)

1,5 mm2 1,5 mm2 1,5 mm2

2,5 mm2 2,5 mm2 2,5 mm2

Connection cable

N

0,75 mm2

L or (L) 0,75 mm2

1

0,75 mm2

0,75 mm2 0,75 mm2 0,75 mm2

0,75 mm2 0,75 mm2 0,75 mm2

0,75 mm2 0,75 mm2 0,75 mm2

Note: This table is only for reference, the installation shall meet the requirements of local laws and regulations.

INSTALLATION

ENG
INDOOR UNIT INSTALLATION
STEP 1: SELECT INSTALLATION LOCATION 1.1 Ensure the installation complies with the installation minimum dimensions (defined below) and meets the minimum and maximum connecting piping length and maximum change in elevation as defined in the System Requirements section. 1.2 Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room. 1.3 Condensate can be easily and safely drained. 1.4 All connections can be easily made to outdoor unit. 1.5 Indoor unit is out of reach of children. 1.6 A mounting wall strong enough to withstand four times the full weight and vibration of the unit. 1.7 Filter can be easily accessed for cleaning. 1.8 Leave enough free space to allow access for routine maintenance. 1.9 Install at least 10 ft. (3 m) away from the antenna of TV set or radio. Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device. 1.10 Do not install in a laundry room or by a swimming pool due to the corrosive environment.
Minimum Indoor Clearances

13cm

Ceiling

20cm

13cm

Floor

250c m

-61-

ENG
INDOOR UNIT INSTALLATION
STEP 2: INSTALL MOUNTING PLATE 2.1 Take the mounting plate from the back of indoor unit. 2.2 Ensure to meet the minimum installation dimension requirements as step 1, according to the size of mounting plate, determine the position and stick the mounting plate close to the wall. 2.3 Adjust the mounting plate to a horizontal state with a spirit level, then mark out the screw hole positions on the wall. 2.4 Put down the mounting plate and drill holes in the marked positions with drill. 2.5 Insert expansion rubber plugs into the holes, then hang the mounting plate and fix it with screws.
Reference screw positions

2.8 (70mm)
Note: (I) Make sure the mounting plate is firm enough and flat against the wall after installation. (II) This figure shown may be different from the actual object, please take the latter as the standard.

STEP 3: DRILL WALL HOLE A hole in the wall should be drilled for refrigerant piping ,the drainage pipe, and connecting cables. 3.1 Determine the location of wall hole base on the position of mounting plate. 3.2 The hole should be have a 70mm diameter at least and a small oblique angle to facilitate drainage. 3.3 Drill the wall hole with 70mm core drill and with small oblique angle lower than the indoor end about 5mm to 10mm. 3.4 Place the wall sleeve and wall sleeve cover(both are optional parts) to protect the connection parts.
Caution: When drill the wall hole, maker sure to avoid wires, plumbing and other sensitive components.

VOfi fi

Wall sleeve Cover Indoor

Wall sleeve
Outdoor 5-10mm Small bolique angle

-62-

ENG

INDOOR UNIT INSTALLATION

STEP 4: CONNECTING REFRIGERANT PIPE 4.1 According to the wall hole position, select the appropriate piping mode. There are three optional piping modes for indoor units as shown in the figure below: In Piping Mode 1 or Piping Mode 3, a notch should be made by using scissors to cut the plastic sheet of piping outlet and cable outlet on the corresponding side of the indoor unit. Note: When cutting off the plastic sheet at the outlet, the cut should be trimmed to smooth.

1

23

Piping Outlet Cable Outlet

4.2 Bending the connecting pipes with the port facing up as shown in the figure.

YES

NO

4.3 Take off the plastic cover in the pipe ports and take off the protective cover on the end of piping connectors. 4.4 Check whether there is any sundry on the port of the connecting pipe and make ensure the port is clean. 4.5 After align the center, rotate the nut of the connecting pipe to tighten the nut as tightly as possible by hand. 4.6 Use a torque wrench to tighten it according to the torque values in the torque requirements table; (Refer to the torque requirements table on section INSTALLATION PRECAUTIONS) 4.7 Wrap the joint with the insulation pipe.

Note: For R32 refrigerant, the connector should be placed outdoors.

Indoor

Outdoor

The connector should be outdoor

-63-

ENG
INDOOR UNIT INSTALLATION
STEP 5: CONNECT DRAINAGE HOSE 5.1 Adjust the drainage hose(if applicable) In some model, both sides of the indoor unit are provided with drainage ports, you can choose one of them to attache the drainage hose. And plug the unused drain port with the rubber attached in one of the ports.
Drainage ports
5.2 Connect the drainage hose to the drainage port, ensure the joint is firm and the sealing effect is good. 5.3 Wrap the joint firmly with teflon tape to ensure no leaks. Note: Make sure there is no twists or dents, and the pipes should be placed obliquely downward to avoid blockage, to ensure proper drainage.
STEP 6: CONNECT WIRING 6.1 Choose the right cables size determined by the maximum operating current on the nameplate. (Check the cables size refer to section INSTALLATION PRECAUTIONS) 6.2 Open the front panel of indoor unit. 6.3 Use a screwdriver, open the electric control box cover, to reveal the terminal block. 6.4 Unscrew the cable clamp. 6.5 Insert one end of the cable into the position of control box from the back of the right end of the indoor unit. 6.6 Connect the wires to corresponding terminal according to the wiring diagram on the electric control box cover. And make sure that they are well connected. 6.7 Screw the cable clamp to fasten the cables. 6.8 Reinstall the electric control box cover and front panel.
Front Panel
Wiring Diagram
Control box Cover
-64-

ENG

INDOOR UNIT INSTALLATION
STEP 7: WRAP PIPNG AND CABLE After the refrigerant pipes, connecting wires and drainage hose are all installed, in order to save space, protect and insulate them, it must be bundle with insulating tape before passing them through the wall hole. 7.1 Arrange the pipes ,cables and drainage hose well as the following picture.
Refrigerant piping

Note:

Drainage hose
(I) Make sure the drainage hose is at the bottom. (II) Avoid crossing and bending of parts.

7.2 Using the insulating tape wrap the refrigerant pipes, connecting wires and drainage hose together tightly.

STEP 8: MOUNT INDOOR UNIT 8.1 Slowly pass the refrigerant pipes, connecting wires and drainage hose wrapped bundle through the wall hole. 8.2 Hook the top of indoor unit on the mounting plate. 8.3 Apply slight pressure to the left and right sides of the indoor unit, make sure the indoor unit is hooked firmly. 8.4 Push down the bottom of indoor unit to let the snaps onto the hooks of the mounting plate, and make sure it is hooked firmly.
Sometimes, if the refrigerant pipes were already embedded in the wall, or if you want to connecting the pipes and wires on the wall, do as below: (I) Hook the top of the indoor unit on the mounting plate without piping and wiring. (II) Lift the indoor unit opposite the wall, unfold the bracket on the mounting plate, and use this bracket to prop up the indoor unit, there will be a big space for operation. (III) Do the refrigerant piping, wiring, connect drainage hose, and wrap them as Step 4 to 7.

-65-

ENG
OUTDOOR UNIT INSTALLATION
STEP 1: SELECT INSTALLATION LOCATION Select a site that allows for the following: 1.1 Do not install the outdoor unit near sources of heat, steam or flammable gas. 1.2 Do not install the unit in too windy or dusty places. 1.3 Do not install the unit where people often pass. Select a place where the air discharge and operating sound will not disturb the neighbors. 1.4 Avoid installing the unit where it will be exposed to direct sunlight ( other wise use a protection, if necessary, that should not interfere with the air flow). 1.5 Reserve the spaces as shown in the picture for the air to circulate freely. 1.6 Install the outdoor unit in a safe and solid place. 1.7 If the outdoor unit is subject to vibration, place rubber blankets onto the feet of the unit.
Over 30cm

Over 50cm

Over 30cm

Over 200cm

Over 50cm

STEP 2: INSTALL DRAINAGE HOSE 2.1 This step only for heating pump models. 2.2 Insert the drainage joint to the hole at the bottom of the outdoor unit. 2.3 Connect the drainage hose to the joint and make the connection well enough.

Drainage joint Drainage hose

STEP 3: FIX OUTDOOR UNIT 3.1 According to the Outdoor Unit installation dimension to mark the installation position for expansion bolts. 3.2 Drill holes and clean the concrete dust and place the bolts. 3.3 If applicable install 4 rubber blankets on the hole before place the outdoor unit (Optional). This will reduce vibrations and noise. 3.4 Place the outdoor unit base on the bolts and pre-drilled holes. 3.5 Use wrench to fix the outdoor unit firmly with bolts.

Note: The outdoor unit can be fixed on a wall-mounting bracket. Follow the instruction of the wall-mounting bracket to fix the wall-mounting bracket on the wall, and then fasten the outdoor unit on it and keep it horizontal. The wall-mounting bracket must be able to support at least 4 times of the weight of outdoor unit

Install 4 rubber blankets (Optional)

-66-

ENG

OUTDOOR UNIT INSTALLATION
STEP 4: INSTALL WIRING 4.1 Use a phillips screwdriver to unscrew wiring cover, grasp and press it down gently to take it down. 4.2 Unscrew the cable clamp and take it down. 4.3 According to the wiring diagram pasted inside the wiring cover, connect the connecting wires to the corresponding terminals, and ensure all connections are firmly and securely. 4.4 Reinstall the cable clamp and wiring cover. Note: When connecting the wires of indoor and outdoor units, the power should be cut off.
Terminal block
Cable clamp Wiring cover
Wiring diagram

FOR MULTI MODELS

NL
POWE R SUPPLY

1A NA LA

1B NB LB

Ou td oo r 1C NC LC

1D ND LD

1 NL In do or A

1 NL In do or B

1 NL In do or C

1 NL In do or D

A and B: 2 indoor units A, B and C: 3 indoor units A, B, C and D: 4indoor units A, B, C, D and E: 5 indoor units

1E NE LE
1 NL In do or E

-67-

ENG
OUTDOOR UNIT INSTALLATION
STEP 5: CONNECTING REFRIGERANT PIPE 5.1 Unscrews the valve cover, grasp and press it down gently to take it down(if the valve cover is applicable). 5.2 Remove the protective caps from the end of valves. 5.3 Take off the plastic cover in the pipe ports and check whether there is any sundry on the port of the connecting pipe and make ensure the port is clean. 5.4 After align the center, rotate the flare nut of the connecting pipe to tighten the nut as tightly as possible by hand. 5.5 Use a spanner hold the body of the valve and use a torque wrench to tighten the flare nut according to the torque values in the torque requirements table. (Refer to the torque requirements table on section INSTALLATION PRECAUTIONS)
Take down the valve cover connection pipes
flare nuts
-68-

ENG

OUTDOOR UNIT INSTALLATION

STEP 6: VACUUM PUMPING 6.1 Use a spanner to take down the protective caps from the service port, low pressure valve and high pressure valve of the outdoor unit. 6.2 Connect the pressure hose of manifold gauge to the service port on the outdoor unit low pressure valve. 6.3 Connect the charge hose from the manifold gauge to the vacuum pump. 6.4 Open the low pressure valve of the manifold gauge and close the high pressure valve. 6.5 Turn on the vacuum pump to vacuum the system. 6.6 The vacuum time should not be less than 15 minutes, or make sure the compound gauge indicates -0.1 MPa (-76 cmHg) 6.7 Close the low pressure valve of the manifold gauge and turn off the vacuum. 6.8 Hold the pressure for 5 minutes, make sure that the rebound of compound gauge pointer does not exceed 0.005 MPa. 6.9 Open the low pressure valve counterclockwise for 1/4 turn with hexagonal wrench to let a little refrigerant fill in the system, and close the low pressure valve after 5 seconds and quickly remove the pressure hose. 6.10 Check all indoor and outdoor joints for leakage with soapy water or leak detector. 6.11 Fully open the low pressure valve and high pressure valve of the outdoor unit with hexagonal wrench. 6.12 Reinstall the protective caps of the service port, low pressure valve and high pressure valve of the outdoor unit. 6.13 Reinstall the valve cover.
Manifold gauge
compound gauge

Low pressure valve Service port
High pressure valve Valve protec ve caps
Pressure hose

Pressure gauge High pressure valve Low pressure valve
Charge hose

Vacuum pump

-69-

ENG

TEST OPERATION

INSPECTIONS BEFORE TEST RUN Do the following checks before test run.
Description

Inspection Method

· Check whether the power supply voltage complies with specification.
Electrical · Check whether there is any wrong or missing connection besafety inspection tween the power lines, signal line and earth wires.
· Check whether the earth resistance and insulation resistance comply with requirements.

· Confirm the direction and smoothness of drainage pipe.

· Confirm that the joint of refrigerant pipe is installed completely.

· Confirm the safety of outdoor unit, mounting plate and indoor

Installation

unit installation.

safety inspection · Confirm that the valves are fully open.

· Confirm that there are no foreign objects or tools left inside the

unit.

· Complete installation of indoor unit air inlet grille and panel.

· The piping joint, the connector of the two valves of the outdoor unit, the valve spool, the welding port, etc., where leakage may occur.
· Foam detection method: Apply soapy water or foam evenly on the parts where leakage may occur, and observe whether bubbles appear or not, if not, it indicates that the leakage detection result is safe. Refrigerant · Leak detector method: leakage detection Use a professional leak detector and read the instruction of operation, detect at the position where leakage may occur. · The duration of leak detection for each position should last for
3 minutes or more; If the test result shows that there is leakage, the nut should be tightened and tested again until there is no leakage; After the leak detection is completed, wrap the exposed pip connector of indoor unit with thermal insulation material and wrap with insulation tape.

-70-

ENG
TEST OPERATION
TEST RUN INSTRUCTION 1. Turn on the power supply. 2. Press the ON/OFF button on the remote controller to turn on the air conditioner. 3. Press the Mode button to switch the mode COOL and HEAT.
In each mode set as below: COOL-Set the lowest temperature HEAT-Set the highest temperature 4. Run about 8 minutes in each mode and check all functions are properly run and respond the remote controller. Functions check as recommended: 4.1 If the outlet air temperature respond the cool and heat mode 4.2 If the water drains properly from the drainage hose 4.3 If the Louver and deflectors(optional) rotate properly 5. Observe the test run state of the air conditioner at least 30 minutes. 6. After the successfully test run, return the normal setting and press ON/OFF button on the remote controller to turn off the unit. 7. Inform the user to read this manual carefully before use, and demonstrate to the user how to use the air conditioner, the necessary knowledge for service and maintenance, and the reminder for storage of accessories. Note: If the ambient temperature is excess the range refer to section OPERATION INSTRUCTIONS, and it can not run COOL or HEAT mode, lift the front panel and refer to the emergency button operation to run the COOL and HEAT mode.
-71-

ENG

MAINTENANCE

WARNING

When cleaning, you must shut down the machine and cut off the power supply for more than 5 minutes. Under no circumstances should the air conditioner be flushed with water. Volatile liquid (e.g. thinner or gasoline) will damage the air conditioner, so only use soft dry cloth or wet cloth dipped with neutral detergent to clean the air conditioner. Pay attention to cleaning the filter screen regularly to avoid dust covering which will affect the filter screen effect. When the operating environment is dusty, the cleaning frequency should be increased appropriately. After removing the filter screen, do not touch the fins of the indoor unit to avoid scratching.

Clean the unit

<40
Wring it dry Gentle wipe the unit surface Tip: Wipe frequently to keep air conditioner clean and good appearance

Clean the filter

Take out the filter from the unit

<40
Clean the filter with soapy water and air
dry it

Opposi te to the
Replace the filter

Service and Maintenance

Tip: When you find accumulated dust in the filter, please clean the filter
in time to ensure the clean, healthy and efficient operation inside the air
conditioner.
When the air conditioner is not in use for a long time, do the following work: Take out the batteries of the remote controller and disconnect the power supply of the air conditioner. When starting to use after long-term shutdown:

  1. Clean the unit and filter screen; 2. Check whether there are obstacles at the air inlet and outlet of indoor and outdoor units; 3. Check whether the drain pipe is unobstructed; Install the batteries of the remote controller and check whether the power is on.

-72-

ENG

TROUBLESHOOTING

MALFUNCTION

POSSIBLE CAUSES

Power failure/plug pulled out

Damaged indoor/outdoor unit fan motor.

Faulty compressor thermomagnetic circuit breaker.

The appliance does
not operate

Faulty protective device or fuses. Loose connections or plug pulled out. It sometimes stops operating to protect the appliance. Voltage higher or lower than the voltage range.

Active TIMER-ON function.

Damaged electronic control board.

Strange odor Dirty air filter.

Noise of running Back flow of liquid in the refrigerant circulation. water

A fine mist comes from the air outlet

This occurs when the air in the room becomes very cold, for example in the ”COOLING” or ”DEHUMIDIFYING/DRY” modes.

A strange noise This noise is made by the expansion or contraction of the front panel due to can be heard variations in temperature and does not indicate a problem.

Unsuitable temperature setting.

Obstructed air conditioner intakes and outlets.

Insufficient Dirty air filter.

airflow, either hot or cold

Fan speed set at minimum.

Other sources of heat in the room

No refrigerant.

The appliance does not
respond to commands

Remote control is not close enough to indoor unit. The batteries of remote control need to be replaced. Obstacles between remote control and signal receiver in indoor unit.

The display is off Active DISPLAY function.

Power failure.

Strange noises during operation.

Switch off the air conditioner

Faulty electronic control board.

immediately Faulty fuses or switches.

and cut off the power supply in

Spraying water or objects inside the appliance.

the event of: Overheated cables or plugs.

Very strong smells coming from the appliance.

-73-

ENG

TROUBLESHOOTING

ERROR CODE ON THE DISPLAY In case of error, the display on the indoor unit shown the following error codes:

Display 0 1 2 3 4 5 6 7 8 9 EA EC EE EH EF EP EU Ed En Ey PA P0 P1 P2 P4 P5 P6 P7 P8 P9

Description of the trouble Indoor and outdoor Communication fault
Indoor room temperature sensor fault Indoor pipe temperature sensor fault Outdoor pipe temperature sensor fault
System unnormal Model allocation error Indoor fan motor fault Outdoor environment temperature sensor fault Exhaust temperature sensor fault Frequency conversion module fault Current sensor fault Outdoor Communication fault Outdoor or Indoor EEPROM fault Outdoor suction temperature sensor fault Outdoor fan motor fault Compressor top temperature switch fault Voltage sensor fault Indoor EEPROM fault Outdoor gas pipe temperature sensor fault Outdoor liquid pipe temperature sensor fault Indoor run mode conflict
Module protection Lower voltage protection High current protection Discharge over temperature protection Exhaust low temperature protection when cooling Exhaust high temperature protection when cooling Exhaust high temperature protection when heating Too high or too low protection for outdoor temperature Driver board protection

-74-

ENG
DISPOSAL GUIDELINE (EUROPE)
This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance,the law requires special collection and treatment. DO NOT dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the following options: · Dispose of the appliance at designated municipal electronic waste collection facility. · When buying a new appliance, the retailer will take back the old appliance free of charge. · The manufacturer will also take back the old appliance free of charge. · Sell the appliance to certifid scrap metal dealers. · Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.
REMOTE CONTROLLER
Thank you very much for purchasing our air conditioner. Please read this operation manual carefully before using your air conditioner. Make sure to save this manual for future reference
-75-

ENG

REMOTE CONTROLLER

Button Function

1

To turn on or off the air conditioner.

2

To activate or deactivate optional function (Check below table).

3

To decrease temperature, time setting or choose the function.

4

To increase temperature, time setting or choose the function.

5

To activate / deactivate the ECO function which enables the unit automatically to sets the operation to achieve energy savings.

6

Press this button to activate/deactivate the Superfunction which enables the unit to reach the preset temperature in the shortest time.

7

To select the mode of operation (AUTO COOL DRY FAN HEAT)

To select the fan speed:

8

flashing

auto

mute

very low

low

mid

high

very high

turbo

9

To activate/deactivate the swing of horizontal flap (up/down).

10

To activate/deactivate the swing of vertical flap (left/right).

ON OFF

Mode AUTO COOL DRY FAN HEAT AUTO COOL DRY FAN HEAT

Options TIMER DISPLAY HEALTH I FEEL 8°C H TIMER DISPLAY HEALTH SLEEP MILDEW I FEEL 8°C H TIMER DISPLAY HEALTH MILDEW I FEEL 8°C H TIMER DISPLAY HEALTH I FEEL 8°C H TIMER DISPLAY HEALTH SLEEP I FEEL 8°C H CLEAN TIMER DISPLAY HEALTH I FEEL 8°C H CLEAN TIMER DISPLAY HEALTH SLEEP MILDEW I FEEL 8°C H CLEAN TIMER DISPLAY HEALTH MILDEW I FEEL 8°C H CLEAN TIMER DISPLAY HEALTH I FEEL 8°C H CLEAN TIMER DISPLAY HEALTH SLEEP I FEEL 8°C H

You will hear a beep when you press the following buttons or select the optional functions below. *** Some of these options may not be available on your model HEALTH (Optional Function: generate the ionizer)
-76-

ENG
REMOTE CONTROLLER
Hold and together over 3 seconds to activate of deactivate the Lock function
You will hear a beep when you press the following buttons or select the optional functions below. *** Some of these options may not be available on your model HEALTH (Optional Function: generate the ionizer)
-77-

ENG

REMOTE CONTROLLER

Remote controller DISPLAY Meaning of symbols on the liquid crystal display

Button

Function

1

Single indicator

2

Lock function indicator

3

Battery indicator

4

AUTO

Mode Auto function indicator

5

COOL

Mode Cooling indicator

6

DRY

Mode Dry indicator

7

FAN

Mode Fan indicator

8

HEAT

Mode Heating indicator

9

ECO

ECO function indicator

10

23.5h [ TIMER ]

11

28.50C

12 flashing
13

Timer indicator
Temperature indicator Fan speed indicator: Auto, very low, low, mid, high, TURBO Mute indicator

14

TURBO function indicator

15

Flap swing angle indicator

16

Deflector swing angle indicator

[ SLEEP ] [ TIMER ] [ I FEEL ]

Optional functions indicator

19

[ HEALTH ] [ MILDEW ]

Note: HEALTH/WIND FREE/GEN MODE functions are not available

[ CLEAN ] [ DISPLAY ] [ 8ºCH ]

at this time.

You will hear a beep when you press the following buttons or select the optional functions below. *** Some of these options may not be available on your model HEALTH (Optional Function: generate the ionizer) / CLEAN
-78-

ENG
REMOTE CONTROLLER
Replacement of Batteries Remove the battery cover plate from the rear of the remote controller, by sliding it in the direction of the arrow. Install the batteries according the direction (+and -) shown on the Remote Controller. Reinstall the battery cover by sliding it into place.
Note Child-lock: Press and together to activate Display ON/OFF: Long press ECO button Please remove batteries To avoid leakage damage when not using for a long time.
Use 2 LRO 3 AAA (1.5V) batteries . Do not use rechargeable batteries . Replace the old batteries with new ones of the same type when the display is no longer legible. Do not dispose batteries as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.
1. Direct the remote controller toward the Air conditioner. 2. Check that there are no objects between the remote control and the Signal receptor in the indoor unit. 3. Never leave the remote controller exposed to the rays of the sun. 4. Keep the remote controller at a distance of at least 1m from the television or other electrical appliances.
-79-

ENG
OPERATING INSTRUCTIONS “SWING” CONTROL OF THE AIR FLOW
· The air outlet flow is uniformly distributed in the room. · It is possible to position the direction of the air in the optimal. The key activates the “FLAP”, the air flow is directed alternatively from up to down. In order to guarantee an even diffusion of the air in the room. The key activates the motorized “deflectors”, the air flow is directed alternatively from left to right. (Optional function, depends on the models) · In cooling mode, orient the flaps in horizontal direction; · In heating mode, orient the flaps downward as the warm air
tends to rise. The deflectors are positioned manually and placed under the flaps. They allow to direct the air flow rightward or leftward.
This adjustment must be done while the appliance is switched off. Never position Flaps manually, the delicate mechanism might seriously damaged! Never poke fingers, sticks or other objects in the air inlet or outlet vents. Such accidental contact with live pants might cause unforeseeable damage or hurt.
-80-

ENG

OPERATING INSTRUCTIONS

COOLING MODE
The cooling function allows the air conditioner to cool the room and at the same time reduces Air humidity. To activate the cooling function (COOL), press the MODE button until the symbol COOL appears on the display. The cooling function is activated by setting the button or at a temperature lower than that of the room. To optimize the function of the Air conditioner, adjust the temperature (1) , the speed (2) and the direction of the air flow (3) by pressing the button indicated.
HEATING MODE
The heating function allows the air conditioner to heat the room. To activate the heating function (HEAT), press the MODE button until the symbol HEAT appears on the display. With the button or set a temperature higher than that of the room. To optimize the function of the Air conditioner adjust the temperature (1), the speed (2) and the direction of the air flow (3) by pressing the button indicated.
In HEATING operation, the appliance can automatically activate a defrost cycle, which is essential to clean the frost on the condenser so as to recover its heat exchange function.This procedure usually lasts for 2-10 minutes during defrosting,indoor unit fan stop operation. After defrosting, it resumes to HEATING mode automatically.
DRY MODE
This function reduces the humid- ity of the air to make the room more comfortable. To set the DRY mode, press MODE until DRY appears in the display. An automatic function of alternating cooling cycles and air fan is activated.
-81-

ENG
OPERATING INSTRUCTIONS FAN MODE (Not FAN button)
The air conditioner works in only ventilation. To set the FAN mode, Press MODE until FAN appears on the display.
AUTO MODE
To activate the AUTO mode of operation, press the MODE button on the remote controller until the symbol AUTO appears on the display. In AUTO mode, the air conditioner will run automatically according to the room temperature.
DISPLAY function (Indoor display)
Switch on/off the LED display on panel. Press OPTION at the fist time, select the DISPLAY by pressing the button or until symbol DISPLAY is flashing; Press OPTION again to switch off the LED display on the panel, and DISPLAY appears on the remote controller display. Do it again to switch on the LED display.
SLEEP function
Press OPTION at the fist time, select the SLEEP by pressing the button or until symbol SLEEP is flashing; Press OPTION again to activate the SLEEP function, and SLEEP appears on the display. Do it again to deactivate this function. After 10 hours running in sleep mode, the air conditioner will return to the previous setting mode.
-82-

ENG
OPERATING INSTRUCTIONS ECO function
Only in Heating or Cooling model, press ECO button and symbol ECO will appear on the display, the air conditioner will work in energy saving process. To cancel this function, pressing the MODE to switch other mode or pressing the ECO button again.
WiFi reset (Optional)
If there is Wi-Fi function, reset the Wi-Fi as below method: Press ECO button 6 times in 8 seconds , then you will hear 3 beeps and CF or AP will be showed on the indoor display.
TURBO function
To activate turbo function,pressing the button TURBO or pressing the button FAN until symbol appears on the display. To cancel this function, pressing the FAN to switch other fan speed or pressing the TURBO button again. In AUTO/HEAT/COOL/FAN mode, when you select TURBO feature, it will use the highest fan setting to blow strong airflow.
-83-

ENG
OPERATING INSTRUCTIONS
I FEEL function
Press OPTION at the fist time , select the I FEEL by pressing the button or until symbol I FEEL is flashing; Press OPTION again to activate the I FEEL function, and I FEEL appears on the display. Do it again to deactivate this function. This function enable the remote control to measure the temperature at its current location and send this signal 7 times in 2 hours to the air conditioner to enable the air conditioner to optimize the temperature around you and ensure maximum comfort. It will automatically deactivate 2 hours later, or indoor temperature exceed the range between 0°C to 50°C.
MILDEW function
Press OPTION at the first time , select the MILDEW by pressing the button or until symbol MILDEW is flashing; Press OPTION again to activate the MILDEW function, and MILDEW appears on the display. Do it again to deactivate this function. This function enable the air conditioner still blow airflow about 15 minutes to dry the indoor inner parts to avoid mildew, when the air conditioner is off. Note: MILDEW function only available in DRY/COOLING mode
Heating function 8°C
1. Press OPTION at the fist time , select the 8°C H by pressing the button or until symbol 8°C H is flashing; Press OPTION again to activate the 8°C heating function, and 8°C H appears on the display. Do it again or change the mode to deactivate this function.
2. If the air conditioner is standby, this function enable the air conditioner automatically start heating when the indoor temperature is equal or lower than 8°C, it will return standby if the temperature is equal or higher than 18°C.
-84-

ENG
OPERATING INSTRUCTIONS
TIMER function
To set the automatic switch-on /off of the air conditioner For timer on, before proceeding with the time: Switch the conditioner off (with the key ). Program the working mode with the button MODE and the fan speed with the button FAN. Timer setting/change/cancel: 1. Press OPTION at the fist time , select the Timer by pressing the
button or until symbol TIMER is flashing; 2. Press OPTION again, the data symbol like h and TIMER will
be flashing; 3. To set the timer or change the timer:
(1) Press the button or to set the expected timer (Increase or decrease at half-hour intervals) the symbols h and TIMER both are flashing.
(2) Press OPTION or waiting for 5 seconds without any operation to confirm the timer, the pre-setting timer like 6.0h and symbol TIMER will be on the display.
To cancel the timer (if TIMER is on) Press OPTION or waiting for 5 seconds without any operation to cancel the timer.
A sample for the Timer-on as Figure 1, Timer-off as Figure 2
Note: All processing should be operated in 5 seconds, otherwise the processing will be cancelled.

Timer-on when switch off

Timer-off when switch on

-85-

.. EUROLAMP : 3o x. , 57013 · T: 2310 574802 IMPORTED IN U BY EUROLAMP SA: 3rd km SIMMAHIKI RD OREOKASTRO, 57013 THESSALONIKI, GREECE · T: +30 2310 574802 · MADE IN CHINA info@eurolamp.gr www.eurolampglobal.com
-86-

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals