BEGA 85 074 Bug Save light Building Element Head Instruction Manual
- June 1, 2024
- BEGA
Table of Contents
- BEGA 85 074 Bug Save light Building Element Head Instruction Manual
- Light building element
- Application
- Product description
- Safety
- Overvoltage protection
- Installation
- Cleaning · Maintenance
- Accessories
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEGA 85 074 Bug Save light Building Element Head Instruction Manual
Light building element
Instructions for use
Application
System light building element with shielded light for illuminating and
designing squares, driveways and entrance areas.
Light exit 360°. The light is deflected by means of a conical reflector onto
the surface to be illuminated.
A light building element tube is required for the installation of the light
building element head, which must be ordered separately (see accessories).
Product description
Luminaire made of cast aluminium, aluminium and stainless steel
BEGA Unidure® coating technology
Clear synthetic cover with optical structure
Silicone gasket
Reflector surface made of pure aluminium
Connecting cable X05BQ-F 5 G 1 mm²
Cable length 3,1 m
BEGA Ultimate Driver ®LED power supply unit 220-240 V x 0/50-60 Hz DC 176-276
V
DALI controllable
Number of DALI addresses: 1
A basic isolation exists between power cable and control line
BEGA Thermal Control® Temporary thermal regulation to protect temperature-
sensitive components without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK04
Protection against mechanical impacts < 0.5 joule
– Conformity mark
Horizontal wind catching area: 0.032 m²
Weight: 4.0 kg
This product contains light sources of energy efficiency class(es) C, D
Dark Sky
The light of this luminaire is directed evenly and highly efficiently onto the
surface to be illuminated. No light is emitted into the upper half-space of
the luminaire.
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Installation
Thread the connection cable into the light building element tube. Align the
light building element head and secure it in place.
Tighten the lateral hexagon socket screws (wrench size 4 mm).
Torque = 12 Nm.
Open the connection box.
Lead the luminaire wiring and mains supply cable through the cable entry into
the connection box.
Make the electrical connection.
Observe the correct configuration of the connecting cable. Make the mains
connection to the brown (L), blue (N) and green-yellow wires ( ****).
The control cables are connected via the two DALI-labelled wires white-red
(wh-rd) and white-black (wh-bl). If these wires are not assigned, the
luminaire will work with full light output.
Close the connection box.
Lamp
Module connected wattage| 20 W
Luminaire connected wattage| 22.5 W
Rated temperature| ta= 25 °C
Ambient temperature| ta max = 50 °C
85 024 K3
Module designation| 4x LED-1305/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 3300 lm
Luminaire luminous flux| 2574 lm
Luminaire luminous efficiency| 114,4 lm / W
85 024 K4
Module designation| 4x LED-1305/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 3480 lm
Luminaire luminous flux| 2714 lm
Luminaire luminous efficiency| 120,6 lm / W
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits. Do not use high pressure cleaners.
Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective synthetic diffuser must be replaced.
Close the luminaire.
Accessories
The light building element head can be combined with the following light
building element tubes:
Cylindrical aluminium poles, lacquered with access door and connection box 71
084
84 708 Pole with anch.section H 3500 mm
84 709 Pole with baseplate H 3500 mm
Cylindrical poles made of laminated wood in accordance with DIN EN 14080 and
aluminium, with access door and connection box 71 084
84 710 Pole with anch.section H 3500 mm
84 711 Pole with baseplate H 3500 mm
70 899 Anchorage unit for light building element tube with base plate
For the accessories a separate instructions for use can be provided upon
request.
Spares
Synthetic cover | 15 000 766 |
---|---|
LED power supply unit | DEV-0312/700 |
LED module 3000 K | LED-1305/830 |
LED module 4000 K | LED-1305/840 |
Reflector | 76 002 093 |
Gasket glass bottom | 83 001 027 |
Gasket glass top | 83 001 953 |
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com