signify GTD10DIM Emergency Lighting Generator Instruction Manual

June 14, 2024
signify

signify LOGO

signify GTD10DIM Emergency Lighting Generator

signify-GTD10DIM-Emergency-Lighting-Generator-PRODUCT

Product Information

Specifications

  • Electrical Specifications (GTD10DIM, BLCD16DIM):

    • Normal Power Supply Voltage: 120-277VAC

    • Normal Power Current Draw: 24MA MAX

    • Normal Power Operating Frequency: 50/60HZ

    • Emergency Power Supply Voltage: 120-277VAC

    • Emergency Power Current Draw: 118MA MAX

    • Emergency Power Operating Frequency: 50/60HZ

    • Feedback/Dimmer Contact Switching Capability (Dry Contact
      Output): 130MA @ 250V MAX

    • Relay Contact (BLCD16DIM): SPST

    • Relay Contact (GTD10DIM): SPST

    • 20A Magnetic Ballast @ 277V

    • 16A Electronic Ballast @ 277V

    • 10A Tungsten @ 120V

    • 10A Magnetic Ballast @ 277V

    • 10A Electronic Ballast @ 277V

    • 10A Tungsten @ 120V

  • Mechanical Specifications:

    • Housing: UL Accepted for use in plenum, NEMA 1
    • Wire: 16, 600V rated
    • Weight: 0.675 lbs. (BLCD16DIM), 0.40 lbs. (GTD10DIM)
    • Humidity Range: 5 to 95% (noncondensing)
    • Rated for dry and damp locations only
    • Approvals: UL 924 listed for the US and Canada

Product Usage Instructions

GTD10DIM Installation

  1. Disconnect all sources of power.
  2. Remove the ballast channel cover.
  3. Mount GTD10DIM as shown in Figures A and B.
  4. Wire the GTD10DIM using an illustration from the Typical Applications section on page 4 or similar setups for different applications.
  5. Before applying power, review the Important Safeguards at the beginning of this document.
  6. Finish installation as required by the NEC, NFPA, state, local, and other codes.
  7. Test the GTD10DIM using the Test Procedure on page 6.

BLCD16DIM Installation

  1. Disconnect all sources of power.
  2. Remove the ballast channel cover.
  3. Mount BLCD16DIM as shown in Figures C and D.
  4. Wire the BLCD16DIM using an illustration from the Typical Applications section on page 4 or similar setups for different applications.
  5. Before applying power, review the Important Safeguards at the beginning of this document.
  6. Finish installation as required by the NEC, NFPA, state, local, and other codes.
  7. Test the BLCD16DIM using the Test Procedure on page 6.

Operation and Maintenance

  • No routine maintenance is required for the GTD10DIM or BLCD16DIM. However, either should be checked periodically to ensure that it is working properly.
  • Note: Make sure to disconnect both the normal and emergency panel circuit breakers before servicing.

FAQ

Q: Is routine maintenance required for GTD10DIM or BLCD16DIM?

  • A : No, routine maintenance is not required. However, they should be checked periodically to ensure proper functionality.

Q: What precautions should I take during installation?

  • A : Before servicing, disconnect all sources of power. Mount the device in locations and at heights where it will not be readily accessible for tampering.
  • Make sure the necessary branch circuit wiring is available and a separate connection to a generator-supplied (or central inverter system-supplied) circuit is provided.

Q: Can I install GTD10DIM or BLCD16DIM in damp locations?

  • A : No, they are rated for dry and damp locations only.

IMPORTANT SAFEGUARDS

  • WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  • ALL SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL
  • This product is intended for use with lighting fixtures controlled by an emergency panel. Any switching between backup power and utility power must be done upstream of this device.
  • All wiring connections and mounting styles must be in accordance with the National Electrical Code (NEC), National Fire Protection Association (NFPA), National Electrical Safety Code, state and local codes, and any other regulations set forth by the local Authority Having Jurisdiction (AHJ).
  • Per NFPA 70E, the use of Personal Protective Equipment (PPE) may be required. Check state and local codes.
  • The load’s operating voltage must be the same as the emergency power input voltage.
  • To reduce the risk of electrical shock, fire, and injury to persons:
  1. Disconnect all sources of power before servicing,
  2. Mount this device in locations and at heights where it will not be readily accessible to tampering by unauthorized personnel,
  3. Do not mount near gas or electric heaters,
  4. Do not let any wires touch hot surfaces, and
  5. Do not use outdoors (NEMA 1 rating only).
  • The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
  • Do not use this device for other than intended use. A generator or inverter-supplied emergency panel is required (120 – 277 VAC, 50/60 Hz).

SAVE THESE INSTRUCTIONS

  • CAUTION: THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE THE RISK OF ELECTRIC SHOCK, DISCONNECT ALL POWER SOURCES BEFORE INSTALLING OR SERVICING THIS UNIT.
    SERVICE BY QUALIFIED PERSONNEL ONLY

  • NOTE: BEFORE INSTALLING THIS DEVICE, MAKE SURE THAT THE NECESSARY BRANCH CIRCUIT WIRING IS AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE CONNECTION TO A GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO BE PROVIDED.

SPECIFICATIONS

ELECTRICAL SPECIFICATIONS (GTD10DIM, BLCD16DIM)

NORMAL POWER SUPPLY VOLTAGE NORMAL POWER CURRENT DRAW NORMAL POWER OPERATING FREQUENCY| 120-277VAC

24MA MAX

50/60HZ

---|---
EMERGENCY POWER SUPPLY VOLTAGE EMERGENCY POWER CURRENT DRAW EMERGENCY POWER OPERATING FREQUENCY| 120-277VAC

118MA MAX

50/60HZ

FEEDBACK/DIMMER CONTACT SWITCHING CAPABILITY (DRY CONTACT OUTPUT)| 130MA @ 250V MAX
RELAY CONTACT (BLCD16DIM) SPST| 20A MAGNETIC BALLAST @ 277V

16A ELECTRONIC BALLAST @ 277V

10A TUNGSTEN @ 120V

RELAY CONTACT (GTD10DIM) SPST| 10A MAGNETIC BALLAST @ 277V

10A ELECTRONIC BALLAST @ 277V

10A TUNGSTEN @ 120V

MECHANICAL SPECIFICATIONS

  • HOUSING: UL ACCEPTED FOR USE IN PLENUM, NEMA 1
  • WIRE: 16″, 600V RATED
  • WEIGHT: 0.675 LBS. (BLCD16DIM) 0.40 LBS (GTD10DIM)
  • OPERATING TEMPERATURE: 35° TO 60°C (-30° TO 140° F)
  • HUMIDITY RANGE: 5 TO 95% (NONCONDENSING) RATED FOR DRY AND DAMP LOCATIONS ONLY
  • APPROVALS: UL 924 LISTED FOR THE US AND CANADA

INSTALLATION

ALL SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL GTD10DIM

Steps

  1. Remove all sources of power.
  2. Remove the ballast channel cover.
  3. Mount GTD10DIM as shown in Figures A and B.
  4. Wire the GTD10DIM using an illustration from the “Typical Applications” section on page 4 or similar setups for different applications.
  5. Before applying power, review the Important Safeguards at the beginning of this document.
  6. Finish installation as required by the NEC, NFPA, state, local, and other codes. Test the GTD10DIM using the “Test Procedure.

BLCD16DIM Steps

  1. Remove all sources of power.
  2. Remove the ballast channel cover.
  3. Mount BLCD16DIM (a couple of mounting options are shown in Figures C and D ).
  4. Wire the BLCD16DIM using an illustration from the “Typical Applications” section on page 4 or similar setups for different applications.
  5. Before applying power, review the Important Safeguards at the beginning of this document.
  6. Finish installation as required by the NEC, NFPA, state, local, and other codes. Test the BLCD16DIM using the Test Procedure” on.

OPERATION

  • The GTD10DIM and the BLCD16DIM will activate an emergency lighting load automatically upon the loss of normal power. If normal power is absent, the status of the load cannot be overridden.
  • However, if the normal power is present, the emergency lighting load can be controlled by other means in order to use it as a normal lighting load, depending on the wiring setup.
  • When used as normal lighting, a two-second delay will keep the load on, even after the wall switch is turned off, to perform a self-test on the unit. When normal power is present, a status contact will automatically close.
  • Therefore, when normal power is absent, the status contact will open (perfect for 0-10V dimming controls).
  • A red LED indicates that emergency power is available. A green LED indicates that normal power is present. A yellow LED copies the status of the load; if the LED is on, the load is on.

MAINTENANCE

  • No routine maintenance is required for the GTD10DIM or BLCD16DIM. However, either should be checked periodically to ensure that it is working properly.
  • Note: Make sure to disconnect both the normal and emergency panel circuit breakers before servicing.

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

  • TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.

WIRING DIAGRAMS

FIG 1 Using Emergency Lighting as Normal Lightingsignify-GTD10DIM-
Emergency-Lighting-Generator-FIG-3

FIG 2 Overriding a 0-10Vdc Dimmersignify-GTD10DIM-Emergency-Lighting-
Generator-FIG-4signify-GTD10DIM-Emergency-
Lighting-Generator-FIG-5

WIRING DESCRIPTIONS

WIRE COLOR DESCRIPTION NOTES
BLACK NORMAL HOT N/A
WHITE/BLACK WALL SWITCH INPUT (SELF-TEST INPUT) MUST BE FROM THE SAME BRANCH

CIRCUIT AS BLACK AND RED. WHEN SWITCHED OFF, A TWO-SECOND DELAY KEEPS THE LOAD ON TO TEST EMERGENCY POWER. DOES NOT TEST FEEDBACK/DIMMER OUTPUT.
RED| NORMAL NEUTRAL OR OTHER PHASE| N/A
BROWN| EMERGENCY HOT| N/A
BLUE| EMERGENCY HOT SWITCHED TO LOAD| SWITCHES OUT THE VOLTAGE PUT IN ON BROWN
YELLOW| EMERGENCY NEUTRAL OR OTHER PHASE| N/A
WHITE/BLUE (GTD10DIM) TERMINAL SCREW 4 (BLCD16DIM)| REMOTE TEST INPUT

(CLASS 2, DRY CONTACT INPUT)

| WHEN WIRING MULTIPLE UNITS TOGETHER, WHITE/BLUE OR TERMINAL SCREW 4 MUST BE A SHARED COMMON.

TEST IS PERFORMED WHEN INPUT IS CLOSED.

WHITE/RED (GTD10DIM) TERMINAL SCREW 3 (BLCD16DIM)
VIOLETS (GTD10DIM) TERMINAL SCREWS 1,2 (BLCD16DIM)| FEEDBACK/DIMMER CONTACT (DRY CONTACT OUTPUT)| OPEN WHEN NORMAL POWER IS ABSENT OR REMOTE TEST INPUT IS CLOSED.

CLOSED WHEN NORMAL POWER IS PRESENT OR REMOTE TEST INPUT IS OPEN.

WALL SWITCH INPUT DOES NOT TEST THIS OUTPUT.

TROUBLESHOOTING GUIDE

TESTING AND TROUBLESHOOTING

  • TEST PROCEDURE: FOUR OPTIONS TO TEST THE GTD10DIM AND BLCD16DIM AFTER INSTALLATION:

INITIAL TEST FOR CORRECT WIRING

  • APPLY EMERGENCY POWER TO THE EMERGENCY POWER INPUT AND NORMAL POWER TO THE NORMAL POWER INPUT.
  • (IF USING THE WALL SWITCH INPUT, APPLY NORMAL POWER TO THE SWITCH ALSO, BUT KEEP THE SWITCH OFF/OPEN.)
  • A. THE RED LED (EMERGENCY POWER AVAILABLE) SHOULD BE ON.
  • B. THE GREEN LED (NORMAL POWER AVAILABLE) SHOULD BE ON.
  • C. THE YELLOW LED (LOAD STATUS) SHOULD BE OFF.
  • D. THE LOAD SHOULD BE OFF.
  • E. THE FEEDBACK/DIMMER CONTACT SHOULD BE CLOSED.

LOCAL TEST BUTTON

  • APPLY EMERGENCY POWER TO THE EMERGENCY POWER INPUT AND NORMAL POWER TO THE NORMAL POWER INPUT.
  • (IF USING THE WALL SWITCH INPUT, APPLY NORMAL POWER TO THE SWITCH ALSO, BUT KEEP THE SWITCH OFF/OPEN.)
  • A. THE RED LED (EMERGENCY POWER AVAILABLE) SHOULD BE ON.
  • B. THE GREEN LED (NORMAL POWER AVAILABLE) SHOULD BE ON.
  • C. THE YELLOW LED (LOAD STATUS) SHOULD BE OFF.
  • D. THE LOAD SHOULD BE OFF.
  • E. THE FEEDBACK/DIMMER CONTACT SHOULD BE CLOSED.

ELECTRICAL SPECIFICATIONS (GTD10DIM, BLCD16DIM)

CONDITION ACTION
RED LED IS OFF • CHECK EMERGENCY POWER INPUT WIRING (BROWN AND YELLOW WIRES)

AND VOLTAGE.
GREEN LED IS OFF| • CHECK NORMAL POWER INPUT WIRING (BLACK AND RED WIRES) AND VOLTAGE.
YELLOW LED IS ON BUT THE LOAD IS OFF| • CHECK BULBS AND BALLAST.

• CHECK LOAD WIRING (BLUE WIRE AND LOAD’S NEUTRAL).

• VERIFY LOAD’S OPERATING VOLTAGE IS THE SAME AS THE EMERGENCY POWER INPUT VOLTAGE.

• REPLACE UNIT.

THE LOAD IS ON BUT THE YELLOW LED IS OFF| • REPLACE UNIT.
YELLOW LED AND LOAD DO NOT TURN

ON WHEN BEING TESTED.

| • CHECK BULBS AND BALLAST.

• CHECK WIRING CONNECTIONS IF USING A REMOTE TEST OPTION.

• PRESS THE LOCAL TEST BUTTON ON THE UNIT.

• REPLACE UNIT.

YELLOW LED AND LOAD.| • VERIFY STATUS OF NORMAL POWER INPUT.

• OPEN WALL SWITCH INPUT.

• VERIFY THAT NO TEST INPUTS ARE STUCK CLOSED. (I.E. REMOTE TEST INPUT IS NOT CLOSED).

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals