INTERMATIC T1471BR Dial Time Switch With Skipper Four Pole Single Throw Instruction Manual

June 16, 2024
Intermatic

INTERMATIC T1471BR Dial Time Switch With Skipper Four Pole Single Throw

Product Information

Specifications

  • Model: T1471BR

  • Type: Four Pole Single Throw

  • Enclosure: Type 3R Rainproof

  • Suitable for Pool Equipment Control if installed 5 ft. or more from edge of pool

  • Resistive Load: 40 A per pole, 120 – 480 VAC

  • Inductive Load: 40 A per pole, Tungsten or 1000 VA Pilot Duty, 120-277 VAC

  • Motor Load: 2 HP (24 FLA) – 120 VAC, 5 HP (28 FLA) – 240 VAC
    Single Phase, 7 1/2 HP (28 FLA) – 208 VAC, 10 HP (28 FLA) – 240 VAC
    Three Phase

  • Electronic Ballast Load: 16 A, 277 VAC

  • UL Hologram Label

  • Independent Wired Clock Motor: 120 VAC, 60 Hz

Product Usage Instructions

Wiring Instructions

  1. Remove 1/2 inch of insulation from wire ends.
  2. Tighten terminal screws firmly (2-18 in-lbs).
  3. Use solid or stranded COPPER conductors only.
  4. May use two wires of the same size and type.

Minimum Copper Wire Size (AWG)

Load Type 120 V 240 V 208 V 240 V
Resistive 14 12 10 8
Inductive 15 20 30 40
Motor (Single Phase) 2 HP 5 HP 7 1/2 HP 10 HP
Electronic Ballast 16 A

Note: Make sure wire insulation clears pressure plate and tighten terminal screws firmly.

Programming Instructions

  1. To set ON and OFF times: Hold trippers against the edge of the CLOCK-DIAL, pointing to the desired time (AM or PM) for ON and OFF operations. Tighten tripper screws firmly.
  2. To set the time-of-day: Pull CLOCK-DIAL outward, turn in either direction to align the exact time-of-day on the CLOCK-DIAL (the current time when the switch is being put into operation) to the time pointer. Do not move the pointer.
  3. To skip operation(s) on selected day(s): Insert SKIPPING SCREW(S) in the SKIPPER WHEEL for the day(s) automatic operation(s) is/are not required. Tighten screws firmly. Move MANUAL LEVER to OFF and rotate SKIPPER WHEEL to locate the correct day-of-week opposite DAY ARROW – YESTERDAY if ON/CUTOUT TRIPPER has not yet advanced wheel, TODAY if it has.

Note: In case of power failure, reset CLOCK-DIAL to the proper time-of- day. See programming instructions.

Operating Instructions

To turn the switch ON or OFF manually, move the MANUAL LEVER to the desired position.

To override the current operation(s), move the SKIPPER WHEEL to the desired day-of-week. This will not affect the next operation.

If there is a power failure, reset the CLOCK-DIAL to the proper time-of-day.

FAQ (Frequently Asked Questions)
Q: Can I control pool equipment with this timer?
A: Yes, the timer is suitable for pool equipment control if installed 5 ft. or more from the edge of the pool.
Q: What is the maximum load for resistive and inductive loads?
A: The maximum load for resistive load is 40 A per pole, 120 – 480 VAC. The maximum load for inductive load is 40 A per pole, Tungsten or 1000 VA Pilot Duty, 120-277 VAC.
Q: How do I set the ON and OFF times?
A: Hold the trippers against the edge of the CLOCK-DIAL, pointing to the desired time (AM or PM) for ON and OFF operations, and tighten the tripper screws firmly.
Q: What should I do in case of a power failure?
A: In case of a power failure, reset the CLOCK-DIAL to the proper time-of-day. See programming instructions for more details.
http://waterheatertimer.org/Intermatic-timers-and-manuals.html#T1400

MODEL: T1471BR
24 HOUR DIAL TIME SWITCH WITH “SKIPPER ®’’ FOUR POLE SINGLE THROW

TYPE 3R RAINPROOF ENCLOSURE
SUITABLE FOR POOL EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL. 40 A RESISTIVE, EACH POLE 120 –
480 VAC, 40 A INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY EACH POLE – 120-277 VAC; 2 HP (24 FLA) – 120 VAC; 5 HP (28 FLA)
240 VAC SINGLE PHASE, 7 1/2 HP (28 FLA) – 208 VAC; 10 HP (28 FLA) – 240 VAC; THREE PHASE,
16 A ELECTRONIC BALLAST, 277 VAC

WARNING
Risk of Fire or Electric Shock

  • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
  • Installation and/or wiring must be in accordance with national and local electrical code requirements.
  • Use wires rated at least 90°C – COPPER conductors ONLY.
  • For outdoor locations, raintight, or wet location, conduit hubs that comply with requirements of UL514B (standard for fittings for conduit and outlet boxes) are to be used.
  • Replace plastic insulator covering terminals before powering ON.
  • KEEP DOOR CLOSED AT ALL TIMES when not servicing.

AVERTISSEMENT

NOTICE

  • Rotate timer dial clockwise only.
  • Do not move the clock hands on the timer. Moving the clock hands can damage the timer.

INDEPENDENTLY WIRED CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG–) ON MOTOR COVER.

WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly (2-18 in-lbs). Use solid or stranded COPPER conductors only. May use two wires of the same size and type.

MINIMUM COPPER| MAX. LOAD (AMP)| MIN. INSUL- ATION TEMP(°C)| 75°C INSULATION MAX. MOTOR LOAD (HP)| PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE|
---|---|---|---|---|---
WIRE SIZE| |
SINGLE PHASE| 3 PHASE|
(AWG)|
120 V.| 240 V.| 208 V.| 240 V.|
14| 15| 90| 1/2| 2| | |
12

10

| 20

30

| 90

90

| 1

2

| 2 1/2

3

| N/A| N/A|
8| 40| 90| | 5| | |

  1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. See caution below. For additional tripper pairs on CLOCK-DIAL order 156T1948A.
  2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) TO TIME POINTER. DO NOT MOVE THE POINTER.
  3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week opposite DAY ARROW–”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.

OPERATING INSTRUCTIONS

  • TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
  • CAUTION: TO AVOID SLOW TRIPPER ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/OFF CUTOUT TRIPPER SWITCHING.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698