BEGA 12 147 Ceiling and Wall Luminaire Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
12 147 Ceiling and Wall Luminaire
Instruction Manual 12 147
Technical amendments reserved
IP 44
12 147 Ceiling and Wall Luminaire
Ceiling and wall luminaire for indoor use
Instructions for use
Application
Ceiling and wall luminaire · indoor luminaire made of hand-blown opal glass,
satin matt and aluminium alloy housing, for all lighting tasks.
They are ideal for places where a soft and uniform lighting distribution is
required.
Luminaire with a high protection class.
Product description
Luminaire made of aluminium alloy
Finish Colour white
Hand-blown opal glass, satin matt 2 mounting holes ø 5.5 mm
Distance apart 110 mm 2 cable entries for through-wiring for mains cable up to
ø 11 mm max. 5 x 1.5@
Connection terminal 2.5@
Earth conductor connection
LED power supply unit 220-240 V x 0/50-60 Hz
DC 176-276 V
DALI-controllable
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Protection class IP 44
Protected against granular foreign bodies ≥ 1 mm and splash water
Impact strength IK04
Protection against mechanical impacts < 0.5 joule
– Safety mark
****– Conformity mark
Weight: 1.9 kg
This product contains light sources of energy efficiency classes D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 7.6 W |
---|---|
Luminaire connected wattage | 9.5 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 55 °C |
12 147 K27
Module designation | 2x LED-0343/927 |
---|---|
Colour temperature | 2700 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1240 lm |
Luminaire luminous flux | 991 lm |
Luminaire luminous efficiency | 104,3 lm / W |
12 147 K3
Module designation | 2x LED-0343/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1260 lm |
Luminaire luminous flux | 1007 lm |
Luminaire luminous efficiency | 106 lm / W |
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Lead the mains supply cable through the cable entry into the luminaire back
housing.
Fix luminaire back housing with enclosed or any other suitable fixing material
onto the mounting surface.
It is imperative to use the enclosed gaskets.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Insert the opal glass into the lower spring clips, centre and push it into the
upper spring clips.
Replacement of the LED module · Maintenance
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the electrical installation.
Pull glass out of the spring clips and remove from the luminaire back housing.
Clean glass and luminaire regularly with solvent-free cleansers from dirt.
Please follow the installation instructions for the LED module.
Snap the glass into the lower spring clips, centralise and push into the upper
spring clips.
A broken glass must be replaced.
Spares
Spare glass | 11 002 057 .0R G |
---|---|
LED power supply unit | DEV-0332/350 |
LED module 2700 K | LED-0343/927 |
LED module 3000 K | LED-0343/930 |
****BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>