Application
Recessed ceiling downlight · Interior luminaire with asymmetrical light distribution for connection to an external LED power supply unit. For surface- mounted installation in indoor suspended ceilings of 5-25mm thickness.

Product description
Recessed luminaire without power supply unit Luminaire housing made of cast aluminium Installation housing is made of glass-fibre reinforced polyamide with 2 fastening springs Reflector surface made of pure aluminium Optical silicone lens · BEGA Constant Optics® Ceiling trim ring made of metal, Colour white Safety glass Recessed opening ø 130mm Required installation depth 95mm 1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI Safety class III 3 c – Conformity mark Weight: 0.34 kg This product contains light sources of energy efficiency class(es) E

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 8.1 W
  • Luminaire connected wattage 9.5 W
  • Rated temperature ta=25 °C
  • Ambient temperature ta max=50 °C
  • When installed in heat-insulating
  • material ta max=30 °C

50 395.1K3

  • Module designation LED-0800/930
  • Color temperature 3000 K
  • Color rendering index CRI > 90
  • Module luminous flux 1255 lm
  • Luminaire luminous flux 953 lm
  • Luminaire luminous efficiency 100,3 lm/W

Lighting technology

  • Half beam angle 64/68°

Installation
A separate power supply unit is required to operate the luminaire. For connection to the external LED-power supply unit – accessory 13 143 or 13 168 – the luminaire is equipped with a 2-pin connector. Note operating instructions of the LED-power supply units. LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping. The recessed opening is covered by the frame of the luminaire housing. Fixing of the installation housing in the recessed opening is achieved by using two adjustable springs.

Installation into inserted ceilings:
A recessed opening of 130 mm is necessary to accept the installation housing. Recessed depth min. 95 mm. Compress the fastening springs of the installation housing against their spring pressure on both sides towards the housing and slide the installation housing into the recessed opening. The fastening springs catch the ceiling panel from the backside. The minimum thickness of the ceiling panel is 5 mm. If the minimum thickness of the panel is less than 5 mm it must be reinforced from the reverse side. The maximum thickness of the ceiling panel must be no more than 25 mm.

Connect to the LED power supply unit. Route the LED power supply unit through the installation housing and place it in the suspended ceiling. Connect the 2-pin plug connector between the luminaire and the external LED power supply unit.BEGA-50-395.1-Recessed-Ceiling-Downlight-for-Indoor-Use-
fig-2

Press together the two internal fixing sliders inside the luminaire housing. Push the luminaire housing to the end of the installation housing and then release the fixing sliders. This mechanism ensures that the luminaire housing sits securely inside the installation housing. Ensure correct directionality towards the area to be illuminated. Installation housing and external LED power supply unit must not be installed in heat-insulating material.BEGA-50-395.1-Recessed-Ceiling-Downlight-for-Indoor-Use-
fig-3

Please use the protective gloves provided for the installation to prevent finger prints on the reflector. Insert the reflector complete with the silicone lens into the three recessed rims of the luminaire housing. Make sure that the positioning bar of the reflector is placed inside the correct recessed rim. That will ensure that the reflector is positioned correctly in relation to the LED. Carefully insert the locking bars of the ceiling trim ring into the 3 remaining openings in the luminaire housing and fix the ceiling trim ring with a twist to the right.

Cleaning · Maintenance

Clean the luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire. The light color and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Close the luminaire.

Accessories

Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.

  • 13 143 Power supply unit on/off
  • 13 168 Power supply unit DALI

The power supply units are only suitable for the operation of one LED luminaire. For the accessories separate instructions for use can be provided upon request.

Spares

  • LED module 3000 K LED-0800/930
  • Trim ring 75 002 945
  • Reflector 76 001 636M
  • BEGA Gantenbrink-Leuchten KG • Postfach 31 60 • 58689 Menden • [email protected]www.bega.com