Danfoss PR-SC4K Direct Telemetry Kit Installation Guide
- June 4, 2024
- Danfoss
Table of Contents
Danfoss PR-SC4K Direct Telemetry Kit
Hardware installation
Antenna
PR-ANTGLASS LTE 30 2J5024P Antenna
Optional Antenna PR-ANTGLASS LTE 200 – 300B0131
Optional: 2 m long antenna in case of poor signal
Note : do not install antenna on metallic surface
Optyma™ Control (AK-RC 101/111/103/113) MODBUS connection
Note:
- Variable bdr Set to 7 (default in 101/103)
- Variable Ad Set to 1
- Variable AU Set to 7 (only for 101/103)
Only for 101/103
Move JP2 in position 3-2 for MODBUS communication
AK-CC 210 MODBUS connection
AK-CC 250 MODBUS connection
**Protection box
**
Use cable glands to maintain the IP65
Note:
Remember to use twisted pair cable and terminate via resistor in case of long Modbus connection. If in doubt, please look at the Design Guide for Data Communication between ADAP-KOOL® Refrigeration Controls
Power cable and status LED
Red LED
- On : Power ON
- Off : Power Off (No power)
- Blinking: No communication with controller (or temporary condition during firmware update)
- Fast blinking : Lost communication with controller
- Green LED (after few seconds from power ON)
- On : Signal OK
- Off : no or poor signal
- Blinking: attempting signal connection
ProsaLink App
App download
Android V5.0 or later ****
iOS 11 or later
Installation
Follow automatic steps to
Register yourself and activate the device by scanning QR code as seen to the right. Configurate your installation. For more information www.prosa.danfoss.com
Scan the QR code on the label
Hand over to end user
- In case you did the configuration for somebody else and captured his email address, he will receive an email with instructions on how to download, register in and use ProsaLink App.
- First month of subscription is free of charge. Installers benefit from free access to ProsaLink and web server.
- Be sure you have activated your alarms (refer to My account \ notifications).
Notifications are sent to your own credentials & E mails to your registered Email address.
WARNINGS
- Installation of PR- SC4 mode:
- embedded into the equipment or installed in a protected enclosure (secure, no risk of electric shock)
- while the equipment is unplugged
- with double insulated cable
- by qualified and skilled technicians only
- Operating temperature: Min. 0 °C, Max. 70 °C
- Ensure use of the Services is legal in the country where you reside, including specific usage and place of usage (mobile communication might be subject to certain restrictions)
© Danfoss
DCS (vt)
2021.06
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>