COOPER Lighting Solutions ONW-D-1001 Wall Switch Sensor Owner’s Manual
- August 20, 2024
- COOPER Lighting Solutions
Table of Contents
Greengate
ONW-D-1001 Wall Switch Sensor with Neutral Required
ONW-D-1001 Wall Switch Sensor
Project| | Catalog #| | Type|
---|---|---|---|---|---
Prepared b| | Notes| | Date|
Dual Tech Single Pole 120/277 VAC Wall
Switch Occupancy Sensor
(Neutral Required)
Typical Applications
Private Offices • Small Conference Rooms • Lunch/Break Rooms • Small
Classrooms • Small Restrooms (1-2 stalls) • Small Lounges • Small Waiting
Rooms • Small Closets • Small Storage Areas
Interactive Menu
- Order Information page 2
- Additional Resources page 2
- Wiring Diagrams page 3
- Product Warranty
Product Features Product Certification
Overview
The Dual Technology Single Level Occupancy Sensing Wall Switch is a motion
sensing lighting control and conventional wall switch all-in-one that is used
for energy savings and convenience.
The ONW-D-1001-MV-N combines Ultrasonic and Passive Infrared (PIR) sensor
technologies to monitor a room for occupancy to deliver maximum energy savings
and ensure the greatest sensitivity and coverage for tough applications
without the threat of false triggers. PIR is used to turn the lights ON and
then either or both technologies are used to keep the lights ON. In Automatic
On Mode, the lights turn ON when a person enters the room. In Manual On Mode,
the lights are turned ON by pressing the universally recognized light icon
pushbutton. The sensor includes self-adaptive technology that continuously
self-adjusts sensitivity and time delay in real-time, maximizing the potential
energy savings that are available in the particular application. The EcoMeter
provides a visual indicator of energy usage, increasing end user awareness and
reminding individuals to take control of their lighting to maximize energy
savings.
Top Product Features
- Air-gap switch ensures no leakage current to load
- Selectable built-in light level sensor
- NEMA WD7 Guide robotic method utilized to verify coverage patterns
Order Information
SAMPLE ORDER NUMBER: ONW-D-1001-MV-N-W One single gang wallplate included.
Catalog Number
Catalog Number | Ratings | Coverage | Voltage | Color |
---|---|---|---|---|
ONW-D-1001-MV-N- (-W, V, LA, G, B, R) | Incandescent: 0-800W @ 120V |
Fluorescent: 0-1200W @ 120V
Fluorescent: 0-2700W @ 277V
Max Load/Relay| 180°; 1000 sq. ft.| 120/277 VAC, 50/60 Hz| W=White, V=Ivory,
LA=Light Almond, G=Gray, B=Black, R=Red
| | | | Notes Not all colors are available in stock and some color options may
have extended lead times.
Product Specifications
Technology
• Passive Infrared (PIR) and Ultrasonic (US) technology
Mechanical
Mounting Plate/Strap Dimensions: 4.195” H x 1.732” W (106.55mm x 44mm)
Mounting Plate/Strap Dimensions: ONW-D-1001-347: 4.35” H x 1.732” W (110.49mm
x 44mm)
Product Housing Dimensions: 2.618” H x 1.752” W x 1.9” D (66.5mm x 44.5mm x
48.26mm)
Environment:
- Operating temperature: 32°F to 104°F (0°C to 40°C)
- Relative humidity operating: 20% to 90% non-condensing
- For indoor use only
Housing: Durable, injection molded housing. ABS resin complies with UL 94V-0
Mounting: Fits in a standard 3.5” deep back box Can be mounted in multiple
gang back box. Refer to NEC box calculation for properly sized mounting box
Electrical
Electrical ratings (per relay):
- 120 VAC
- Incandescent / Tungsten max load: 6.7 amps, 800W, 50/60 Hz
- Fluorescent / Ballast max load: 10 amps, 1200W, 50/60 Hz
- Motor Load: 1/4 HP @ 125 VAC
- 230/277VAC
- Fluorescent / Ballast max load: 9.8 amps, 2700W, 50/60 Hz
Ballast compatibilty:
- Magnetic and Electronic ballasts
Hardware Specifications
LED Indicators:
- Red LED = PIR detection
- LED = Ultrasonic detection
- Green LED = Acts as EcoMeter or nightlight locator
Controls and Performance
Time delays:
- Self adjusting 15 seconds/test (10 min. Auto)
- Selectable 5, 15, 30 minutes
Coverage:
- Major motion: 36’ x 30’
- Minor motion: 20’ x 16’
Light sensing level:
- 0 to 200 foot candles
Standards/Ratings
- cULus Listed
- FCC Compliant
- RoHS Compliant
Warning
-
This product is not intended to be used in applications involving the use of ammonia-based or VOC cleaners.
-
Use of ammonia-based or VOC cleaners on this device must be avoided.
Prolonged use may cause loss of integrity and expose electrified components.
If this occurs, turn OFF power to the unit and replace. -
For detailed cleaning guidelines please refer to: Controls Care and Maintenance instructions at the end of this document.
Warranty
Five year warranty standard
Dimensional and Mounting Details Wiring Diagrams
Single Level Switching – Single Circuit Scale or Mounting Height
Three-way wiring diagram: Lights will turn OFF automatically when sensor that detected motion last, times out.
Controls
| Time Delay| Activation| Not Used| PIR
Sensitivity| Walk-Through Mode| EcoMeter| Override|
Not Used| Maintain Lights On| Not Used
---|---|---|---|---|---|---|---|---|---|---
DIP Switch| 1| 2| Relay 1| 4| 5| 6| 7|
8| 9| 10| 11| 12
3
**Auto*| ▼| ▼| Auto| | Full ▼| Disable ▼| Enable ▼|
Disable ▼| | Either ▼| |
5 Minutes| ▼| ▲| Manual ▲| | 50% ▲| Enable ▲|
Disable| Enable ▲| | Both ▲| |
15 Minutes| ▲| ▼|
30 Minutes*| ▲| ▲
_Self-Adjusts to 10 min. user mode_|
Field of View
Minor Motion, IR|
---|---
Major Motion, IR|
Minor Motion, Ultrasonic|
Major Motion, Ultrasonic|
Maximum coverage area may vary somewhat according to room shape and the presence of obstacles.
Controls Care & Maintenance
Cooper Lighting Solutions
Cooper Lighting Solutions has developed recommended guidelines for cleaning
our products that will not impact the operation or finish of the product.
Recommended cleaning tips:
- Never spray any fluids directly into the device.
- Use of ammonia-based or VOC cleaners on this device must be avoided. Prolonged use may cause loss of integrity and expose electrified components. If this occurs, turn OFF power to the unit and replace.
- Use a damp rag or single-use wipe to avoid excess liquid penetrating the device. Be sure to wipe up remaining excess liquid after cleaning.
- Ensure the cleaning agent used does not have harsh chemicals such as bleach, ammonia, highly alkaline or concentrated acids (such as hydrochloric acid that can be found inhousehold cleaners such as toilet bowl cleaners, bathroom tile and porcelain leaners) as they could damage the device, causing them to become brittle and discolored.
- Cooper Lighting Solutions recommends the use of a mild liquid detergent and water to clean the devices. Single use wipes (e.g. Lysol brand or equivalent) are acceptable to use for cleaning the devices, however the single-use wipes cannot contain bleach, ammonia, highly alkaline or concentrated acids.
WARNING
This product is not intended for use in applications involving the use of
ammonia-based or VOC cleaners. Prolonged use may cause loss of integrity and
expose electrified components. If this occurs, turn OFF power to the unit and
replace.
Recommended cleaning instructions:
- Never spray any fluids directly into the device.
- Apply the mild liquid detergent to a damp cloth or paper towel. Single use wipes (e.g. Lysol brand or equivalent) are acceptable to use for cleaning the devices, however single-use wipes cannot contain bleach, ammonia, highly alkaline or concentrated acids.
- If excess liquid is present, remove by wringing out the cloth or paper towel to avoid liquid penetration into the device.
- Clean the Cooper Lighting Solutions device by wiping over the surface with the damp cloth.
- Remove an excess liquid remaining on the device with a dry cloth or paper towel.
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
For service or technical assistance:
1-800-553-3879
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2024 Cooper Lighting Solutions
All Rights Reserved.
Product availability, specifications, and compliances are subject to change
without notice.