COOPER Lighting Solutions ONW-D-1001-DMV-N Dual Tech Occupancy Sensor Switch Owner’s Manual
- June 1, 2024
- COOPER Lighting Solutions
Table of Contents
- COOPER Lighting Solutions ONW-D-1001-DMV-N Dual Tech Occupancy Sensor
- Specifications
- Product Features
- Interactive Menu
- Greengate
- Product Certification
- Product Features
- Order Information
- Product Specifications
- Technology
- Hardware Specifications
- Warranty
- Wiring Diagrams
- Controls
- Field of View
- Care & Maintenance
- Frequently Asked Questions
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
COOPER Lighting Solutions ONW-D-1001-DMV-N Dual Tech Occupancy Sensor
Switch
Specifications
- Model: ONW/VNW-D-1001-DMV-N
- Type: Dual Tech Occupancy Sensor Switch with Dual 120/277VAC Relays
- Voltage: 120/277 VAC, 50/60 Hz
- Color Options : W=White, V=Ivory, LV=Light Almond, G=Gray, B=Black, R=Red
- Warranty: Five-year standard warranty
Product Features
-
PIR Activated and Ultrasonic Activated Self-Adjusting
-
California Title 20 Compliant
-
Air-gap switch ensures no leakage current to load
-
Selectable built-in light level sensor
-
NEMA WD7 Guide robotic method utilized to verify coverage
patterns -
Additional pushbutton with light/fan graphic included
-
LED Rated
Dimensional and Mounting Details
- Mounting Plate/Strap Dimensions: 4.195 H x 1.732 W (106.55mm x 44mm)
- Product Housing Dimensions: 2.618 H x 1.752 W x 1.9 D (66.5mm x 44.5mm x 48.26mm)
Project
| |
Catalog #
| |
Type
|
---|---|---|---|---|---
Prepared by
| |
Notes
| |
Date
|
Order Information
SAMPLE ORDER NUMBER: ONW-D-1001-DMV-N-W (One single gang wallplate
included)
Warranty Information
Five-year standard warranty is provided with the product.
Interactive Menu
- Order Information page 2
- Additional Resources page 2
- Wiring Diagrams page 3
- Connected Systems page 4
- Product Warranty
Top Product Features
- Air-gap switch ensures no leakage current to load
- Selectable built-in light level sensor
- NEMA WD7 Guide robotic method utilized to verify coverage patterns
- Additional pushbutton with light/fan graphic included
- LED Rated
Greengate
ONW/VNW-D-1001-DMV-N
- Dual Tech Occupancy Sensor Switch with
- Dual 120/277VAC Relays (Neutral Required)
Typical Applications
- Office
- Small Conference Rooms
- Lunch/Break Rooms
- Classrooms
- Restrooms (1-2 Stalls)
- Lounges
- Waiting Rooms
- Closets
- Storage Areas
Product Certification
Product Features
Dimensional and Mounting Details
Scale or Mounting Height
Order Information
SAMPLE ORDER NUMBER: ONW-D-1001-DMV-N-W
One single gang wallplate included
Catalog Number
Catalog Number | Ratings | Coverage | Voltage | Color |
---|
ONW-D-1001-DMV-N- (-W, V, LA, G, B, R)
| Incandescent: 0-800W @ 120V Fluorescent: 0-1200W @ 120V Fluorescent: 0-2700W @ 277V Max Load/Relay| ****
180°; 1000 sq. ft.
| ****
120/277 VAC, 50/60 Hz
| ****
W=White, V=Ivory, LV=Light Almond, G=Gray, B=Black, R=Red
| | | | Notes
Not all colors are available in stock and some color options may have extended lead times.
Product Specifications
The Dual Technology Dual Relay Occupancy Sensing Wall Switch is a motion- sensing lighting control and conventional wall switch all-in-one that is used for energy savings and convenience. The unit contains two relays that allow the control of two separate loads. The unit requires a neutral wire for installation.
The ONW-D-1001-DMV combines Ultrasonic (US) and Passive Infrared (PIR) sensor technologies to monitor a room for occupancy to deliver maximum energy savings and ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers. PIR is used to turn the lights ON and then either or both technologies are used to keep the lights ON. In Automatic On Mode, the lights turn ON when a person enters the room. In Manual On Mode, the lights are turned ON by pressing the universally recognized light icon pushbutton. Each relay can be set independently to Automatic or Manual On Mode. The sensor includes self-adaptive technology that continuously self- adjusts sensitivity and time delay in real time, maximizing the potential energy savings that are available in the particular application.
Technology
- Passive Infrared (PIR) and Ultrasonic (US) technology
Mechanical
Mounting Plate/Strap Dimensions: 4.195” H x 1.732” W (106.55mm x 44mm) Product
Housing Dimensions: 2.618” H x 1.752” W x 1.9” D (66.5mm x 44.5mm x 48.26mm)
Environment:
- Operating temperature: 32°F to 104°F (0°C to 40°C)
- Relative humidity operating: 20% to 90% non-condensing
- For indoor use only
Housing: Durable, injection moulded housing. ABS resin complies with UL 94V-0 Mounting: Fits in a standard 3.5” deep back box Can be mounted in multiple gang back box Refer to NEC box calculation for properly sized mounting box
Electrical
Electrical ratings (per relay):
120 VAC
- Incandescent / Tungsten max load: 6.7 amps, 800W, 50/60 Hz
- Fluorescent / Ballast max load: 10 amps, 1200W, 50/60 Hz
- Electronic Ballast (LED): 3A
- Motor Load: 1/4 HP @ 125 VAC
277VAC
- Fluorescent / Ballast max load: 9.8 amps, 2700W, 50/60 Hz
- Electronic Ballast (LED): 3A
Ballast compatibility:
- LED loads
- Magnetic and Electronic ballasts
Hardware Specifications
LED Indicators:
- Red LED = PIR detection
- Green LED = Ultrasonic detection; Green LED acts as EcoMeter or nightlight locator
Controls and Performance
Time delays:
- Self-adjusting 15 seconds/test (10 min. Auto)
- Selectable 5, 15, 30 minutes
Coverage:
- Major motion: 36’ x 30’
- Minor motion: 20’ x 16’
Light sensing level:
- 0 to 200-foot candles
Standards/Ratings
- cULus Listed – Energy Management Equipment (UL916)
- FCC Compliant
- RoHS Compliant
Warning
- This product is not intended to be used in applications involving the use of ammonia-based or VOC cleaners.
- Use of ammonia-based or VOC cleaners on this device must be avoided. Prolonged use may cause loss of integrity and expose electrified components. If this occurs, turn OFF power to the unit and replace.
- For detailed cleaning guidelines please refer to: Controls Care and Maintenance instructions at the end of this document.
Warranty
Five-year warranty standard
Wiring Diagrams
120/277 VAC dual level single circuit wiring diagram
120/277 VAC dual level dual-circuit wiring diagram
Three-way wiring diagram: Lights will turn OFF automatically when the sensor that detected motion last, times out.
Controls
Field of View
Control Systems
- Greengate
Maximum coverage area may vary somewhat according to room shape and the presence of obstacles.
Care & Maintenance
Controls Care & Maintenance
Cooper Lighting Solutions has developed recommended guidelines for cleaning
our products that will not impact the operation or finish of the product.
Recommended cleaning tips:
- Never spray any fluids directly into the device.
- Use of ammonia-based or VOC cleaners on this device must be avoided. Prolonged use may cause loss of integrity and expose electrified components. If this occurs, turn OFF power to the unit and replace.
- Use a damp rag or single-use wipe to avoid excess liquid penetrating the device.
- Be sure to wipe up the remaining excess liquid after cleaning.
- Ensure the cleaning agent used does not have harsh chemicals such as bleach, ammonia, highly alkaline or concentrated acids (such as hydrochloric acid that can be found inhousehold cleaners such as toilet bowl cleaners, bathroom tile and porcelain cleaners) as they could damage the device, causing them to become brittle and discolored.
- Cooper Lighting Solutions recommends the use of a mild liquid detergent and water to clean the devices. Single use wipes (e.g. Lysol brand or equivalent) are acceptable to use for cleaning the devices, however the single-use wipes cannot contain bleach, ammonia, highly alkaline or concentrated acids.
WARNING: This product is not intended for use in applications involving the use of ammonia-based or VOC cleaners.
- Prolonged use may cause loss of integrity and expose electrified components.
- If this occurs, turn OFF the power to the unit and replace it.
Recommended cleaning instructions
- Never spray any fluids directly into the device.
- Apply the mild liquid detergent to a damp cloth or paper towel. Single-use wipes (e.g. Lysol brand or equivalent) are acceptable to use for cleaning the devices, however, single-use wipes cannot contain bleach, ammonia, or highly alkaline or concentrated acids.
- If excess liquid is present, remove by wringing out the cloth or paper towel to avoid liquid penetration into the device.
- Clean the Cooper Lighting Solutions device by wiping over the surface with a damp cloth.
- Remove the excess liquid remaining on the device with a dry cloth or paper towel.
Cooper Lighting Solutions
- ADDRESS: 1121 Highway 74 South Peachtree City, GA 30269
- P : 770-486-4800
- www.cooperlighting.com
- For service or technical assistance: 1-800-553-3879
Canada Sales
- ADDRESS: 5925 McLaughlin Road Mississauga, Ontario L5R 1B8
- P: 905-501-3000
- F: 905-501-3172
© 2024 Cooper Lighting Solutions All Rights Reserved.
Product availability, specifications, and compliances are subject to change
without notice.
Frequently Asked Questions
- Q: What is the warranty period for the product?
- A: The product comes with a standard five-year warranty.
- Q: Are all colour options available in stock?
- A: Not all colours are available in stock, and some colour options may have extended lead times. Please check availability at the time of purchase.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>