COOPER Lighting Solutions PR4R 4 Inch LED Self Flanged Lensed Retrofit Downlight Owner’s Manual

June 1, 2024
COOPER Lighting Solutions

COOPER Lighting Solutions PR4R 4 Inch LED Self Flanged Lensed Retrofit

Downlight

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-PRODUCT

Product Information

  • Specifications:
    • Product Name: High Lumen PR4R | PR4M
    • Type: 4-inch LED self-flanged, lensed retrofit downlight and wall wash
    • Lumen Output Range: 1000 lm – 4000 lm
    • Control Compatibility: WaveLinx LITE, WaveLinx PRO
    • Input Voltage: 120-277VAC
    • Dimming: 0-10V analog dimming

Product Usage Instructions

  • Installation:
    • Ensure the power source is turned off before starting the installation process.
    • Mount the fixture using the provided mounting frame according to the dimensional details in the manual.
    • Connect the wiring following the specified input/control requirements.
    • If using additional accessories like the step-down transformer or sensor kits, refer to the specific instructions for those accessories.
  • Lumen Adjustment:
    • To adjust the lumen output of the fixture, follow these steps:
    • For field-selectable options, ensure the correct LED module is used based on the desired lumen range (FS12 for 1000-2000 lm, FS24 for 2000-4000 lm).
    • For discrete factory-set options, select the appropriate lumen output based on the LED module used (10 for 1000 lm, 15 for 1500 lm, 30 for 3000 lm).
  • Control Compatibility:
    • For integrating with WaveLinx LITE or WaveLinx PRO systems, follow the system specifications provided by the manufacturer for seamless control compatibility.

FAQs

  • Q: Can I use the fixture with a different dimming protocol other than 0-10V analog dimming?
    • A: The fixture is designed for use with 0-10V analog dimming control only. Using a different dimming protocol may result in improper functionality.
  • Q: What is the maximum aperture size for retrofitting?
    • A: The fixture supports retrofitting for apertures ranging from 5.1 min. to 5.75 max. aperture, which can be extended up to 7 max. aperture with the OT450P accessory ring.
  • Q: Can the fixture be used in Chicago Plenum-rated environments?
    • A: Yes, there are specific models available such as PR4RCP that are CCEA Chicago Plenum rated for use in such environments.

OVERVIEW

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(1\)

Interactive Menu

  • Order Information page 2
  • Product Specifications page 3
  • Photometric Data page 4
  • Energy & Performance Data page 6
  • Connected Systems page 8
  • Product Warranty

Top Product Features

  • Selectable lumens 1000/1500/2000 and 2000/3000/4000
  • SeleCCTable color temperature 3000K/3500K/4000K
  • Available in 80 CRI or 90 CRI
  • Retrofit 5” & 6” commercial housings with 4” lens LED
  • Medium / Wide beam distribution reversible “flip” lens
  • Wall wash accessory kit

Product Certification

Product Features

Control Compatibility

Dimensional

Dimensional and Mounting Details

Scale

Order Information

  • SAMPLE ORDER NUMBER: PR4RFS24D010REM7 – PR4M24MD8FSMW
  • A complete luminaire consists of a mounting frame and LED module ordered separately, with optional accessories as noted

Standard Driver 120-277VAC, 0-10V analog dimming

Mounting Frame| Lumens| Input / Control| Options| Accessories
---|---|---|---|---
PR4R = 4″ lens aperture, retrofit frame arm with integrated junction box and driver (4)

PR4RCP = 4″ lens aperture, retrofit frame arm with integrated junction box and driver, CCEA Chicago Plenum rated (4)

| Field Selectable

FS12 = field selectable 1000, 1500 and 2000 lumens (nominal), use with PR4M12* LED modules only (5)

FS24 = field selectable 2000, 3000 and 4000 lumens (nominal), use with PR4M24* LED modules only (5)

**Discrete (fixed) Factory Se t (6)**

10 = 1000 lumens (nominal), use with PR4M12* LED modules only

15 = 1500 lumens (nominal), use with PR4M12* LED modules onlys

30 = 3000 lumens (nominal), use with PR4M24* LED modules only

| D010 = 120-277VAC 50/60Hz,

0-10V analog , 1%-100% dimming

| REM7 = integral 7 watt emergency battery pack with remote test / indicator light, use with D010 only (1)

REM14 = integral 14 watt emergency battery pack with remote test / indicator light, use with D010 only (1) BOD7ST = 7.5 watt Bodine self-test diagnostic emergency module with remote test / indicator light, use with D010 only (1)

WTA = Factory WaveLinx PRO Tilemount Sensor Kit (1)(3)  WTK = Factory WaveLinx LITE Tilemount Sensor Kit (1) (9)  WPN = WaveLinx PRO Wireless Node without sensor (10)  WLN = WaveLinx LITE Wireless Node without Sensor (11)

| H347 = 347 to 120V step down transformer, 75VA

H347200 = 347 to 120V step down transformer, 200VA

WTA = Field WaveLinx PRO Tilemount Sensor Kit (1)(3)

WTK = Field WaveLinx LITE Tilemount Sensor Kit (1) (9)

Notes

(4) Retrofits 5.1” min. to 5.75” max. aperture (up to 7” max. aperture with OT450P accessory ring)

| Notes

(5) FS12 factory preset 2000 lumens in PR4M12 LED module. FS24 factory preset 4000 lumens in PR4M24 LED module. (6) Driver has fixed lumen output. Lumen selector switch on LED modules do not change lumens in fixed output housings.

| Notes| Notes

(1) Not available for Chicago Plenum

(3) WTA = WaveLinx PRO tile mount sensor kit for daylight dimming, PIR motion sensing, and optional RLTS – Real Time Location Services, use with D010 only. (Refer to WaveLinx PRO system specifications.)

(9) WTK = WaveLinx LITE tile mount sensor kit for daylight dimming, PIR motion sensing, use with D010 only. (Refer to WaveLinx LITE system specifications.)

(10) WPN = WaveLinx PRO wireless node provides luminaire-level control with scene and zone configuration without an integrated sensor; Connects wirelessly with daylight dimming sensor and PIR motion sensor if desired. Use with 0-10V driver only. Not compatible with 347V or Chicago plenum. (Refer to WaveLinx PRO system specifications.)

(11) WLN = WaveLinx LITE wireless node provides luminaire-level control with scene and zone configuration without an integrated sensor; Connects wirelessly with daylight dimming sensor and PIR motion sensor if desired. Use with 0-10V driver only. Not compatible with 347V or Chicago plenum. (Refer to WaveLinx LITE system specifications.)

| Notes

(1) Not available for Chicago Plenum

(3) WTA = WaveLinx PRO tile mount sensor kit for daylight dimming, PIR motion sensing, and optional RLTS – Real Time Location Services, use with D010 only. (Refer to WaveLinx PRO system specifications.)

(9) WTK = WaveLinx LITE tile mount sensor kit for daylight dimming, PIR motion sensing, use with D010 only. (Refer to WaveLinx LITE system specifications.)

DLV Driver Distributed Low Voltage Power System

Mounting Frame| Lumens (7)| Input / Control| Options| Accessories
---|---|---|---|---
PR4R = 4″ lens aperture, retrofit frame arm with integrated junction box and low voltage DLVP system driver (8)| 10 = 1000 lumens (nominal), use with PR4M12* LED modules only

15 = 1500 lumens (nominal), use with PR4M12* LED modules only

20 = 2000 lumens (nominal), use with PR4M12 LED modules or with PR4M24 LED modules

30 = 3000 lumens (nominal), use with PR4M24* LED modules only

40 = 4000 lumens (nominal), use with PR4M24* LED modules only

| DLV = Distributed Low Voltage dimming driver 1%-100%, 1000-4000 lumens only. For use with DLVP system only, refer to DLVP specifications for details. (1)| REMV7 = 7 watt emergency battery pack with remote test / indicator light, use with DLV only (1)(2)) REMV14 = 14 watt emergency battery pack with remote test

/ indicator light, use with DLV only (1)(2)

|
Notes

(8) Retrofits 5.1” min. to 5.75” max. aperture (up to 7” max. aperture with OT450P accessory ring)

| Notes

(7) DLV driver has fixed lumen output. Lumen selector switch on LED modules do not change lumens in fixed output housings.

| Notes

(1) Not available for Chicago Plenum

| Notes

(1) Not available for Chicago Plenum

(2) ULus for U.S. only

| Notes
LED Module| Lumen Range| Distribution| CRI / CCT| Finish| Accessories
---|---|---|---|---|---
PR4M = 4″ lens aperture, LED trim/module with self-flanged shallow reflector.

For use with PR4 series housing frames, retrofit frames, and surface cylinders

| 12 = field selectable 1000, 1500 and 2000 lumens (nominal). Factory pre-set for 2000 lumens.

Use with PR4RFS12, PR4R10, PR4R15, PR4R20 mounting frames only.

24 = field selectable 2000, 3000 and

4000 lumens (nominal).

Factory pre-set for 4000 lumens. Use with PR4RFS24, PR4R20, PR4R30, PR4R40 mounting frames only.

| MD = medium / wide beam reversible “flip” lens. Factory set for medium. Tool-less twist-to-lock flip changes from medium to wide distribution.


Medium distribution (70°, 1.01 SC)


Wide distribution (107°, 1.61 SC)

| Field Selectable

8FS = 80 CRI (minimum) with field selectable 3000K, 3500K and

4000K CCT (nominal). Factory pre- set for 3500K.

9FS = 90 CRI (minimum) with field selectable 3000K, 3500K and

4000K CCT (nominal). Factory pre- set for 3500K.


Discrete (fixed) Factory Se t 827 = 80 CRI (minimum) 2700K

927 = 90 CRI (minimum) 2700K

850 = 80 CRI (minimum) 5000K

950 = 90 CRI (minimum) 5000K

| MW = matte white ring/ self- flanged reflector

MMS = matte metallic silver ring/self-flanged reflector

BZ = bronze ring/self-flanged reflector

| PR4WW = 4” wall wash optic, field installed

PR4MDWD = 4” reversible medium

/ wide distribution – replacement lens

OT450P = Oversize metal retrofit ring with 5.5” ID opening, 8” OD flange, matte white finish

Notes| Notes| Notes| Notes| Notes| Notes

Product Specifications

Frame

  • Die-formed galvanized steel retrofit frame arm with integrated junction box
  • One-piece construction attaches to an LED module for installation in an existing commercial downlight from below the finished ceiling
  • UL is listed with Cooper commercial frames and classified with other frames

Mounting

  • Retrofit frame arm attaches to the LED module with knurled thumb screws

Retrofit

  • Retrofit frame arm and LED module may be used to retrofit open frame 5.1” to 5.75” nominal aperture, and up to 7.0” with oversize trim ring OT450P.
  • OT450P oversize trim ring, 5.5” I.D. and 8.0” O.D., matte white finish

LED Module

  • Integrated self-flanged reflector with multiple finish options
  • Patented SeleCCTable™ colour temperature technology and selectable lumen output for selection in the field
  • Integrated dip switches for colour and lumen selection
  • Field Selectable CCT 3000K / 3500K / 4000K
  • Discrete (Fixed) CCT options in 2700K and 5000K
  •  Low and high selectable lumen ranges:
  • Low Lumen: 1000lm / 1500lm / 2000lm (nominal)
  • High Lumen: 2000lm / 3000lm / 4000lm (nominal)
  • Discrete (fixed) lumen models in 1000lm, 1500lm, 3000lm (nominal); use to meet lighting power density codes
  • Available in 80 CRI or 90 CRI (nominal) with colour accuracy within 3 SDCM
  • The LED array uses a plurality of mid-power surface mount LEDs delivering high flux and excellent efficiency
  • Passive cooling achieves L70 at 50,000 hours
  • Integral connector for a quick link to the retrofit frame arm

LED Module – Reflector

  • Integrated self-flanged reflector with LED array and lens
  • Finish options: matte white, matte metallic silver, and dark bronze

LED Module – Optics

  • Reversible “Flip” Lens
  • “Flip” lens is reversible offering medium / wide beam options
  • Lens ships in the medium beam. The twist-to-lock feature allows conversion to a wide beam in the field without tools.
  • The micro-prismatic lens is a precision-molded optical polymer
  • Louvered Wall Wash
  • The optional field-installed wall wash kit offers 360° rotation, allowing the housing to be installed in any orientation.

Driver

  • The driver is preinstalled and prewired to the junction box on the retrofit frame arm
  • Field replaceable constant current driver provides low noise operation
  • UNV 120-277VAC 50/60Hz input standard
  • Continuous 1% – 100% dimming with 0-10V analog control
  • Optional low voltage DC driver for use with DLVP distributed low voltage power system (see DLVP Design Guide for details)

Emergency Option

  • Available with 7 or 14-watt emergency battery pack with remote test switch/charge indicator light
  • Provides 90 minutes of standby lighting meeting most life safety codes for egress lighting
  • Available Self-Test (self-diagnostic), with remote charge indicator and test switch

Connected Lighting System

  • Two WaveLinx-connected solutions to choose from. Refer to WaveLinx system specifications and application guides for details.

WaveLinx PRO Tilemount Sensor Kit

  • WaveLinx PRO WTA tilemount sensor kit offers daylight dimming, PIR motion sensing, scene and zone configuration, automatic commissioning; and optional RLTS – Real Time Location Services available.

WaveLinx PRO Wireless Node

  • WaveLinx PRO WPN wireless node provides luminaire-level control with scene and zone configuration without an integrated sensor; Connects wirelessly with daylight dimming sensor and PIR motion sensor if desired. Use with 0-10V driver only. Note: Not compatible with 347V or Chicago plenum.

WaveLinx LITE Tilemount Sensor Kit

  • WaveLinx LITE WTK tile mount sensor kit offers daylight dimming and PIR motion sensing, scene and grouping configuration.

WaveLinx LITE Wireless Node

  • WaveLinx LITE WLN wireless node provides luminaire level control with scene and zone configuration without an integrated sensor; Connects wirelessly with daylight dimming sensor and PIR motion sensor if desired. Use with 0-10V driver only. Note: Not compatible with 347V or Chicago plenum.

WaveLinx Tilemount Sensor Kits Application

  • The WTA and WTK tile mount sensor kits include a control module mounted on the luminaire junction box via 1/2” knock-out and a tilemount sensor on a 54-inch whip; for ceiling installation by direct-mount spring clips or via mounting bracket in octagon ceiling boxes.
  • The WTA and WTK tile mount sensor kits may be ordered as factory-installed on the luminaire or ordered separately as a field-installed accessory kit.
  • Note: WaveLinx PRO devices are only compatible with the WaveLinx PRO system.
  • Note: WaveLinx LITE devices are only compatible with the WaveLinx LITE system.

Junction Box

  • Galvanized steel junction box
  • 20in3 internal volume excluding voltage barrier
  • 25 in3 internal total volume
  • Voltage divider for 0-10V dimming wires [occupies (1) 1/2” pry-out space]
  • Listed for (8) #12 AWG (four in, four out) 90˚ C conductors and feed-thru branch wiring
  • (3) 1/2” and (2) 3/4” trade size pry-outs available
  • (3) 4-port push wire nuts for mains voltage, with 1-port used for fixture wiring

Compliance

  • cULus Certified to UL 1598 / C22.2 No. 250.0, suitable for damp locations and wet locations in covered ceilings only
  • IP20 – Above finished ceiling; IP65 – Below finished ceiling
  • Field selectable 1000/1500/2000lm, 2000/3000/4000lm models, and fixed output 3000lm models are Non-IC rated, insulation must be kept 3” from top and sides
  • Fixed output 1000lm and 1500lm models are Type IC thermally protected and suitable for direct contact to air permeable insulation (also suitable for Non-IC)
  • Not for use in direct contact with spray foam insulation, consult NEMA LSD57-2013
  • Airtight per ASTM-E283-04
  • Suitable for use in clothes closets when installed in accordance with the NEC 410.16 spacing requirements
  • EMI/RFI emissions FCC CFR Title 47 Part 15 Class A at 120/277V
  • Contains no mercury or lead and RoHS compliant
  • Photometric testing by IES LM-79-08
  • Lumen maintenance projections by IES LM-80-08 and TM-21-11
  • May be used to comply with the State of California Title 24 non-residential code, as a dimmable LED luminaire
  • ENERGY STAR® certified, see Certified Light Fixtures database

Warranty

Photometric Data

  • PR4RFS12D010 – PR4M12MD8FSMW Low lumen module, 2000 lumen, medium lens
  • Spacing criterion: 1.01
  • Lumens: 2135
  • Input Watts: 19.8 W
  • Efficacy: 107.8 LPW
  • UGR: 21
  • Test Report: PR4FS12D010 PR4M12MD8FSMW 2000Lm3500K.ies
  • PR4RFS12D010 – PR4M12MD8FSMW – PR4WW
  • Low lumen module – wall wash, 2000 lumen, wall wash accessory
  • Spacing criterion: 1.12
  • Lumens: 1845
  • Input Watts: 19.8 W
  • Efficacy: 93.2 LPW
  • UGR: 23
  • Test Report: PR4FS12D010 PR4M12WW8FSMW 2000Lm3500K.ies
  • PR4RFS12D010 – PR4M12WD8FSMW Low lumen module, 2000 lumen, wide lens
  • Spacing criterion: 1.61
  • Lumens: 2177
  • Input Watts: 19.8 W
  • Efficacy: 109.9 LPW
  • UGR: 24
  • Test Report: PR4FS12D010 PR4M12WD8FSMW 2000Lm3500K.iesCOOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-Downlight-FIG-1 \(10\)

Photometric Multipliers – Selectable lumen 1000lm – 1500lm – 2000lm

1000 Lumen 1500 Lumen 2000 Lumen
0.47 0.62 1.00

Multipliers for nominal values with other series models

Color Finish Multipliers

Finish code MW MMS BZ
Finish Matte White Matte Metallic Silver Bronze
Multiplier 1.00 0.94 0.83

CCT Multipliers – 80CRI – Selectable CCT 3000K – 3500K – 4000K

3000K 3500K 4000K
0.92 1.00 0.98

Multipliers for nominal values with other series models
CCT Multipliers – 90CRI – Selectable CCT 3000K – 3500K – 4000K

3000K 3500K 4000K
0.93 1.00 0.97

Multipliers for nominal values with other series models

  • PR4RFS24D010- PR4M24MD8FSMW High lumen module, 4000 lumen, medium lens
  • Spacing criterion: 1.01
  • Lumens: 3927
  • Input Watts: 39 W
  • Efficacy: 100.7 LPW
  • UGR: 23
  • Test Report: PR4FS24D010 PR4M24MD8FSMW 4000Lm3500K.ies
  • PR4RFS24D010 – PR4M24MD8FSMW – PR4WW High lumen module – wall wash, 2000 lumen, wall wash accessory
  • Spacing criterion: 1.12
  • Lumens: 3394
  • Input Watts: 39 W
  • Efficacy: 87 LPW
  • UGR: 24
  • Test Report: PR4FS24D010 PR4M24WW8FSMW 4000Lm3500K.ies
  • PR4RFS24D010 – PR4M24MD8FSMW High lumen module, 4000 lumen, wide lens
  • Spacing criterion: 1.61
  • Lumens: 4004
  • Input Watts: 39 W
  • Efficacy: 102.7 LPW
  • UGR: 25
  • Test Report: PR4FS24D010 PR4M24WD8FSMW 4000Lm3500K.iesCOOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-Downlight-FIG-1 \(14\)

Photometric Multipliers – Selectable lumen 2000lm-3000lm-4000lm

2000 Lumen 3000 Lumen 4000 Lumen
0.53 0.70 1.00

Multipliers for nominal values with other series models

Color Finish Multipliers

Finish code MW MMS BZ
Finish Matte White Matte Metallic Silver Bronze
Multiplier 1.00 0.94 0.83

Multipliers for nominal values with other series models

CCT Multipliers – 80CRI – Selectable CCT 3000K – 3500K – 4000K

3000K 3500K 4000K
0.90 1.00 0.96

Multipliers for nominal values with other series models

CCT Multipliers – 90CRI – Selectable CCT 3000K – 3500K – 4000K

3000K 3500K 4000K
0.91 1.00 0.95

Multipliers for nominal values with other series models

Energy and Performance Data

COLOR METRICS – TM-30-15 & CRI/CIE (3500K)

80 CRI & 90 CRI Color Metric Summary – Low Lumen / 3500K*

80 CRI & 90 CRI Color Metric Summary – High Lumen / 3500K*

PR4FS12 LED MODULE LOW LUMEN RANGE

Series 1000 lumen
Input Voltage 120-277VAC 120V
Input Current (A) 0.089
Input Power (W) 10.5
In-rush (A) 8.9
In-rush Duration (ms) 0.145
THD (%) <15.1
PF ≥ 0.98

Minimum starting temperature -20°C (-4°F)
Sound Rating: Class A standards
Series| 1500 lumen
---|---
Input Voltage 120-277VAC| 120V| 277V
Input Current (A)| 0.112| 0.052
Input Power (W)| 13.4| 13.8
In-rush (A)| 9.9| 24.8
In-rush Duration (ms)| 0.198| 0.107
THD (%)| <13.3| <15.5
PF| ≥ 0.98| ≥ 0.94
Minimum starting temperature -20°C (-4°F)

Sound Rating: Class A standards
Series| 2000 lumen
---|---
Input Voltage 120-277VAC| 120V| 277V
Input Current (A)| 0.178| 0.079
Input Power (W)| 21.3| 21.4
In-rush (A)| 8| 19.1
In-rush Duration (ms)| 0.185| 0.133
THD (%)| <8.2| <10.6
PF| ≥ 0.99| ≥ 0.97
Minimum starting temperature -20°C (-4°F)*
Sound Rating: Class A standards

PR4FS24 LED MODULE HIGH LUMEN RANGE

Series 2000 lumen
Input Voltage 120-277VAC 120V
Input Current (A) 0.176
Input Power (W) 21
In-rush (A) 15.3
In-rush Duration (ms) 0.237
THD (%) <11
PF ≥ 0.99

Minimum starting temperature -20°C (-4°F)
Sound Rating: Class A standards
Series| 3000 lumen
---|---
Input Voltage 120-277VAC| 120V| 277V
Input Current (A)| 0.225| 0.101
Input Power (W)| 26.9| 27
In-rush (A)| 11.6| 27.9
In-rush Duration (ms)| 0.187| 0.081
THD (%)| <9.05| <11.8
PF| ≥ 0.99| ≥ 0.96
Minimum starting temperature -20°C (-4°F)

Sound Rating: Class A standards
Series| 4000 lumen
---|---
Input Voltage 120-277VAC| 120V| 277V
Input Current (A)| 0.332| 0.145
Input Power (W)| 39.8| 39.4
In-rush (A)| 12.8| 27.5
In-rush Duration (ms)| 0.211| 0.107
THD (%)| <5.9| <8.8
PF| ≥ 0.99| ≥ 0.98
Minimum starting temperature -20°C (-4°F)*
Sound Rating: Class A standards

Notes: Emergency Battery packs are rated for a minimum starting temperature of 0°C.

Dimensional Details

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(17\)

Connected Solutions

WaveLinx LITE – WTK Tilemount Sensor

WaveLinx LITE devices are only compatible with the WaveLinx LITE system.

  • Intuitive Android™ or Apple® iOS® app for basic system code compliant set-up and configuration via Bluetooth
  • Up to 28 unique areas per project site (WaveLinx LITE Bluetooth network)
  • Up to 50 devices for an area, any one of 16 control zones, up to 6 occupancy sets, and custom lighting scenes
  • Automatic occupancy or vacancy, sensor sensitivity, daylight dimming, etc. configurable through the app
  • Refer to the WaveLinx system specifications for detailsCOOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-Downlight-FIG-1 \(19\)

WaveLinx LITE WTK Tilemount Wiring Diagram

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(20\)

WaveLinx LITE Bluetooth Enabled System

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(21\)

WaveLinx PRO – WTA Tilemount Sensor

WaveLinx PRO devices are only compatible with the WaveLinx PRO system.

  • WaveLinx PRO tile mount functionality configures zones and customizes settings from one secure mobile app
  • Automatic code commissioning that meets the strictest codes
  • Fixtures and sensors integrate with Wireless Area Controllers, Wall Stations, and Control Devices
  • Stand-alone offices or Entire Building Network Installations

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(23\)

WaveLinx mobile app settings

WaveLinx WTA Tilemount Wiring Diagram

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(25\)

WaveLinx CORE Building Management Integration

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(26\) WaveLinx LITE Wireless Node – WLN

WaveLinx LITE devices are only compatible with the WaveLinx LITE system.

  • Intuitive Android™ or Apple® iOS® app for basic system code compliant set-up and configuration via Bluetooth
  • Up to 28 unique areas per project site (WaveLinx LITE Bluetooth network)
  • Up to 50 devices for an area, any one of 16 control zones, up to 6 occupancy sets, and custom lighting scenes
  • Refer to the WaveLinx system specifications for details
  • WaveLinx mobile app settingsCOOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-Downlight-FIG-1 \(28\)

WaveLinx LITE Wireless Node (WLN) Wiring Diagram

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(29\)

WaveLinx LITE Bluetooth Enabled System

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(30\)

WaveLinx PRO Wireless Node – WPN

WaveLinx PRO devices only compatible with the WaveLinx PRO system.

  • WaveLinx Wireless functionality configures zones and customizes settings from one secure mobile app
  • Automatic code commissioning that meets the strictest codes
  • Fixtures and sensors integrate with WaveLinx Area Controller, Wall Stations, and Control Devices
  • Stand-alone offices or Entire Building Network Installations

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(32\)

WaveLinx mobile app settings

WaveLinx PRO Wireless Node (WPN) Wiring Diagram

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(34\)

WaveLinx CORE Building Management Integration

COOPER-Lighting-Solutions-PR4R-4-Inch-LED-Self-Flanged-Lensed-Retrofit-
Downlight-FIG-1 \(35\)

CONTACT

  • Cooper Lighting Solutions
  • 1121 Highway 74 South
  • Peachtree City, GA 30269
  • P: 770-486-4800
  • www.cooperlighting.com.
  • © 2023 Cooper Lighting Solutions All Rights Reserved.
  • Specifications and dimensions are subject to change without notice.
  • Typical Applications
    • Office
    • Healthcare
    • Hospitality
    • Institutional
  • 4-inch LED self-flanged, lensed retrofit downlight and wall wash
    • PR4R
    • PR4M
    • April 3, 2024, 8:39 PM